Plan Review Details - Permit 19040009
Plan Review Stops For Permit 19040009
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-14 Cont ID  
Sent By jgomez Date 2019-06-14 Time 10:03 Rev Time 0.00
Received By jgomez Date 2019-06-14 Time 08:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2019-04-29 Time 15:05 Sent To  
Notes
2019-04-30 06:57:362017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040009
 ADD: 525 S. FLAGLER DR. SUITE 29 A-B
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 30/ 2019
 ACTION: DENIED
  
 1) SHEET A-002 THE PROPOSED FLOOR PLAN UNDER THE
 HEADING GENERAL NOTE # 10 THE PLAN STATES NEW STRUCTURE
 AND BUILDING ELEMENTS SHALL BE DESIGNED TO RESIST 140
 MPH. THE PLANS SHOULD BE UPDATED TO THE 2017 FBC-B WIND
 SPEEDS. SEE 1609.3 ULTIMATE WIND DESIGN AND FIGURE
 1609.3(1), ULTIMATE DESIGN WIND SPEED, VULT FOR RISK
 CATEGORY II BUILDINGS AND STRUCTURES. 1609.3.1 WIND
 SPEED CONVERSION VULT TO VASD. 170 VULT = 132 VASD
 (PRODUCT APPROVALS ARE IN VASD). THIS LOCATION EXPOSURE
 D LOCATION.
  
 2) SHEET A-002 THE PROPOSED FLOOR PLAN UNDER THE
 HEADING GENERAL NOTE # 13 THE PLAN STATES NEW FLOOR
 FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
 (FBC-B 2017) FOR TILE, STONE, MARBLE, AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING. PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE
 WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 08:40 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 08:40 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By jpearson Date 2019-04-23 Time 14:17 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 14:17 Sent To  
Notes
2019-04-23 14:17:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS EXISTING ELECTRICAL PANEL B IN AN AREA
 THAT WILL BECOME A WALK IN CLOSET. OVERCURRENT DEVICES
 ARE NOT PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 240.24(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By pleduc Date 2019-05-30 Time   Rev Time 0.00
Received By pleduc Date 2019-05-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 12:05 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 12:01 Sent To  
Notes
2019-04-09 12:05:04PERMIT # 19040009
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 3) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 4) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-24 Time 14:41 Sent To  
Notes
2019-05-28 14:41:58B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-01 Time 09:27 Sent To  
Notes
2019-04-03 09:27:51B06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2019-04-29 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-07 Cont ID  
Sent By ccole Date 2019-06-07 Time 09:02 Rev Time 0.00
Received By ccole Date 2019-06-07 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-18 Cont ID  
Sent By ccole Date 2019-04-18 Time 17:06 Rev Time 0.00
Received By ccole Date 2019-04-18 Time 16:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By jesmith Date 2019-06-06 Time 09:24 Rev Time 0.00
Received By jesmith Date 2019-06-06 Time 08:35 Sent To  
Notes
2019-06-06 08:51:47 
 PLUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PER WPB FBC 107.2.1, PROVIDE AS A DEFERRED SUBMITTAL
 AS ALLOWED BY WPB FBC 107.3.4.1, A DETAIL FOR TYPICAL
 SHOWER PAN. THE DETAIL SHOWER PAN AND CURB DETAIL SHALL
 SHOW COMPLIANCE WITH FBC PL SECTION 417 INCLUDING THE
 REQUIRED 2% PITCH REQUIRED FOR THE MEMBRANE PER WPB FBC
 107.2.1. SHOW TYPE OF MATERIAL OF SHOWER DRAIN PIPE.
 PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE SHOWER
 FLOOR PENETRATION AND THE ELIMINATED TUB DRAIN OPENING
 AS REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB
 FPC 107.2.1. THE DETAIL SHALL BE SUBMITTED, APPROVED
 AND IN PLACE PRIOR TO THE FIRST INSPECTION.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-17 Cont ID  
Sent By jesmith Date 2019-04-17 Time 10:46 Rev Time 0.00
Received By jesmith Date 2019-04-17 Time 08:43 Sent To  
Notes
2019-04-17 10:46:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. PROVIDE SPEC AND DETAIL OF FIRE RATED ASSEMBLIES FOR
 FLOOR AND WALL PENETRATIONS TO SUPPORT PLUMBING GENERAL
 NOTE 13 PER WPB FBC 107.2.1.
 2. P0.1, PLUMBING MATERIALS-DOMESTIC WATER, NOTE 3;
 REVISE NOTE TO REFLECT 2017 FBC PER WPB FBC 107.2.1.
 3. PER WPB FBC 107.3.5.3, THIS OCCUPANCY DOES NOT MEET
 THE CRITERIA FOR RESIDENTIAL (ONE AND TWO FAMILY) AND
 MUST COMPLY WITH THE REQUIREMENTS OF FBC PL, NOT FBC
 RES.PER WPB FBC 107.2.1, ON P0.1, REVISE PLUMBING
 FIXTURE LIST NOTES 4 AND 5 TO REFLECT 2017 FBC PL CODE
 WITH APPLICABLE SECTIONS.
 4. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR TYPICAL
 SHOWER PAN SHOWING COMPLIANCE WITH FBC PL 417.5.
 5. RE P1.1:
 A. HER BATHROOM; PER WPB FBC 107.2.1, PROVIDE LOCATION
 AND TYPE OF STACK(S) OR HORIZONTAL BRANCH INTO WHICH
 THE BATHTUB DRAINS AND SHOW THAT THE FIXTURE DRAIN IS
 PROPERLY VENTED. THE CHANGED FOOTPRINT OF WHAT APPEARS
 TO BE A CHASE WALL FOR THE PLUMBING INDICATES THAT THE
 STACK(S) ARE TO BE RELOCATED (OFFSET). PLEASE BE
 ADVISED THAT IF THIS IS A WASTE STACK VENT AS DESCRIBED
 IN FBC PL 913, THAT SUCH STACKS ARE NOT PERMITTED TO
 OFFSET VERTICALLY OR HORIZONTALLY PER FBC PL 913.2 AND
 THE CHASE LAYOUT WILL BE REQUIRED TO ACCOMMODATE THAT
 REQUIREMENT.
 B. STAFF BATHROOM;
 1) PROVIDE LOCATION AND TYPE OF STACK(S) OR HORIZONTAL
 BRANCH INTO WHICH THE LAVATORIES DRAIN. PLEASE BE
 ADVISED THAT IF THIS IS A WASTE STACK VENT AS DESCRIBED
 IN FBC PL 913, THAT SUCH STACKS ARE NOT PERMITTED TO
 RECEIVE THE DISCHARGE OF ANYTHING OTHER THAN FIXTURE
 DRAINS PER FBC PL 913.2. TO COMPLY, EACH LAVATORY WOULD
 HAVE TO CONNECT SEPARATELY TO THE STACK.
 2) PER FBC PL 912.1, THE LAUNDRY TUB SHALL NOT BE USED
 TO WET VENT THE WATER CLOSET. PROVIDE COMPLETE CLARITY
 ON SANITARY ISO AND FLOOR PLAN SHOWING HOW WATER
 CLOSETS ARE CONNECTED TO STACK AND HOW VENTED. SHOW HOW
 LAUNDRY TUB IS TO CONNECT TO STACK WITHOUT IMPACTING
 THE WATER CLOSETS.
 C. LAUNDRY; FLOOR PLAN SHOWS CLOTHES WASHER CONNECTING
 TO STACK AND SANITARY ISO SHOWS CONNECTING TO EXISTING
 HORIZONTAL BRANCH. RECONCILE THE TWO AND IF CONNECTED
 TO STACK, SHOW VENTING COMPLYING WITH FBC CHAPTER 9 ON
 THE SANITARY ISO. DO THESE STACKS EVEN EXIST. ON THE
 DEMO PLAN A-0001, THERE DID NOT APPEAR TO BE ANY
 PLUMBING FIXTURES IN THE VICINITY.
  
 END OF COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  