| Plan Review Stops For Permit 19031396 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-18 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-18 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-06-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-14 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-14 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2019-06-14 13:18:42 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND REVIEW DENIED: | | | | | | FBC B 107. PROVIDE ENGINEER OF RECORD CONNECTION DETAIL | | | INDICATING THE TYPE, SIZE/DIMENSIONS, AND QUANTITY OF | | | ANCHORS FOR EACH BIKE RACK TO FOUNDATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-05 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-05 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2019-06-05 14:57:46 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING PLAN REVIEW DENIED: | | | | | | FBC B 107.2.1 PROVIDE MORE DETAILED INFORMATION | | | INCLUDING THE MEASUREMENTS ON THE HANDRAILS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-18 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-03 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-06-20 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-13 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-05 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-24 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-18 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-18 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-20 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-20 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2019-06-20 09:48:49 | DIGITAL SIGNATURE OK; LANDSCAPE ARCHITECT (ANGELA M | | | BIAGI, LA) WILL ADD AN IMAGE OF HER SEAL TO FUTURE | | | SUBMITTALS. | | | | | | REVIEW REMAINS IN "FAILED" STATUS AS STRUCTURAL DETAILS | | | WILL BE SUBMITTED NEXT REVIEW CYCLE. | | | | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-17 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-17 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2019-06-17 07:51:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE SEAL FOR ANGELA M BIAGI IS NOT IN ACCORDANCE | | | WITH FAC61G10-11.011(2) (LANGUAGE, SEAL), REVISE | | | ACCORDINGLY. | | | | | | 2. PLANS REFER TO STRUCTURAL DRAWINGS; PLEASE PROVIDE, | | | FBC 107. | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-05 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-05 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2019-06-05 15:18:54 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | SIGNATURES; | | | FBC B 107.1 THE DIGITAL SIGNATURES ON THE BIKE RACK | | | PLANS NEED TO BE SIGNED/SEALED BY A STRUCTURAL ENGINEER | | | DUE TO THE STRUCTURAL REQUIREMENTS FROM LOADS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-07-16 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-07-16 |
Time |
13:00 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2019-07-16 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-06-20 |
Time |
16:45 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2019-06-20 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
escneide |
Date |
2019-06-03 |
Time |
13:57 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2019-06-03 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2019-06-03 14:10:01 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) SHEET LG 1.04 IS PROVIDED TWO TIMES - ONE DATED | | | 4/18/19 AND ONE DATED 5/14/19. ONLY ONE IS TOO BE | | | SUBMITTED. NOTE: IT APPEARS THAT THE DIFFERENCE IS HAND | | | RAILS ON THE STAIRS WHICH ARE NOT PART OF THIS PERMIT | | | REVIEW. | | | | | | 2) SHEET LG 2.01 FAILS TO PROVIDE DIMENSIONS TO VERIFY | | | THAT THE RACK SIZE AND PLACEMENT ON THE PADS MEET CITY | | | REQUIREMENTS. PLEASE NOTE THAT THE PLANS SUBMITTED TO | | | THE CITY AND APPROVED AS PART OF THE SITE PLAN REVIEW | | | PROCESS PROVIDE THIS INFORMATION. | | | | | | 3) THE SITE PLANS NEED TO INCLUDE THE CODE COMPLIANT | | | PAD DIMENSIONS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] |
|
|