Plan Review Details - Permit 19031394
Plan Review Stops For Permit 19031394
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-03 Cont ID  
Sent By pvalenti Date 2019-08-03 Time 12:59 Rev Time 0.00
Received By pvalenti Date 2019-08-03 Time 12:59 Sent To  
Notes
2019-08-03 13:11:35PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW APPROVED WITH PROVISO:
  
  
 THE WALL R-VALUE FROM FROM THE ENERGY REPORT NEEDS TO
 MATCH THE THE DETAILS ON THE ARCHITECTURAL PLANS PRIOR
 TO INSPECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-12 Cont ID  
Sent By jgomez Date 2019-07-12 Time 14:58 Rev Time 0.00
Received By jgomez Date 2019-07-11 Time 16:52 Sent To  
Notes
2019-07-12 14:59:02NEW RESTAURANT (A2 ASSEMBLY) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- OK
  
 2- OK
  
 3- OK
  
 4- ENERGY CALCULATIONS:
 A) OK.
  
 B) CEILING R-VALUE INSULATION AND WALL R-VALUE
 INSULATION DOESN'T MATCH ARCHITECTURAL PLANS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 ENERGY CALCULATIONS WERE REVISED, BUT THEY STILL DON'T
 MATCH. SEE PLANS AND REVISE AS REQUIRED.
 NOTE: ALSO, CHECK TYPE OF WALLS SPECIFIED FOR THE
 KITCHEN. THEY DON'T SEEM TO MATCH PLANS EITHER. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C)OK.
  
 5- OK
  
 6- PRODUCT APPROVALS SUBMITTED:FAC 61G20-3.001
 A) OK
  
 B) OK
  
 C) OK
  
  
 7- OK
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By jgomez Date 2019-04-29 Time 17:02 Rev Time 0.00
Received By jgomez Date 2019-04-26 Time 17:27 Sent To  
Notes
2019-04-30 14:00:25NEW RESTAURANT (A2 ASSEMBLY) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 2- REVISE OCCUPANT LOAD SHOWN ON THE LIFE SAFETY PLAN
 AND COVER SHEET
 A)NUMBER OF PEOPLE IN KITCHEN AREA IS BASED ON THE
 TOTAL GROSS AREA AS REQUIRED BY TABLE 1004.1.2
 FBC-BUILDING. THIS INCLUDES THE WALK-IN FREEZER AND
 COOLER. ALSO, NUMBER OF PEOPLE SHOWN ON THE LIFE SAFETY
 PLAN DOESN'T MATCH NUMBER SHOWN ON THE COLUMN WHEN
 ADDING THE TOTAL NUMBER OF PEOPLE. REVISE AS REQUIRED
 TO MATCH.
  
 B) NUMBER OF PEOPLE ON THE ROUND BOOTH NEEDS TO BE
 REVISED CONSIDERING A 24 INCH PER PERSON OF SEATING
 LENGTH AS REQUIRED BY SEC. 1004.4 FBC-BUILDING. ALSO,
 NEED TO ADD THE ADDITIONAL SPACE SHOWN FOR THE
 WHEELCHAIR.
  
 C) NUMBER OF PEOPLE SHOWN ON THE QUEUE LINE NEEDS TO BE
 REVISED. THIS AREA IS MORE THAN 80S.F. TABLE 1004.1.2
 FBC-BUILDING.
  
 3- THE BUILDING THERMAL ENVELOPE NEEDS TO BE CLEARLY
 DEPICTED ON PLANS AS REQUIRED BY SEC. C103.2.1
 FBC-ENERGY CONSERVATION. ARCHITECTURAL WALL SECTIONS
 SHOW FURRING STRIPS ON CMU WALLS UP TO 6 INCHES ABOVE
 THE SUSPENDED CEILING. WHAT HAPPENS TO THE REST OF THE
 WALL. ARCHITECT TO SHOW COMPLETE THERMAL ENVELOPE AND
 SPECIFY R-VALUE OF WALL. COORDINATE WITH ENERGY
 CALCULATIONS TO AVOID CONFLICTS/DELAYS.
  
 4- ENERGY CALCULATIONS:
 A) A/C AREA SPECIFIED ON THE ENERGY CALCULATIONS
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) CEILING R-VALUE INSULATION AND WALL R-VALUE
 INSULATION DOESN'T MATCH ARCHITECTURAL PLANS. REVISE
 ASD REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) BUILDING ADDRESS SHOWN ON THE ENERGY CALCULATIONS IS
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- DOORS AND WINDOWS BUCK DETAILS DON'T PROVIDE
 SPECIFICATIONS FOR THE FASTENING OF THE STRUCTURAL
 BUCK. PROVIDE COMPLETE SPECIFICATIONS. SEC. 1609.1
 FBC-BUILDING.
  
 6- PRODUCT APPROVALS SUBMITTED:FAC 61G20-3.001
 A) PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE FOR
 EACH FLORIDA PRODUCT APPROVAL SUBMITTED. THIS IS
 REQUIRED BECAUSE THE COVER PAGE SHOWS THE STATUS OF THE
 PRODUCT APPROVAL AND THE CODE IN EFFECT.
  
 B) PROVIDE LATEST REVISION OF FLORIDA PRODUCT APPROVAL
 FOR:
 (1)FL1559. CURRENT REVISION IS R-12 NOT R-11.
 (2) FL8787. CURRENT REVISION IS R-9 NOT R-8.
 (3)FL4553. CURRENT REVISION IS R-11 NOT R-10.
  
  
 C) FLAT ROOF MEMBRANE ROOFING FLORIDA PRODUCT APPROVAL
 FL1559-R12: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES. NOTE: RAS 117 CALCULATIONS NEED TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 7- CONTRACTOR TO CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR ) FOR COORDINATION OF SPECIAL INSPECTIONS
 LISTED ON SHEET S002.
  KEN CONRAD
  CHIEF BUILDING INSPECTOR
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  401 CLEMATIS STREET
 P.O.BOX 3366
 WEST PALM BEACH, FL 33402
  PHONE: 805-6666 EXT: 6666
  FAX: 659-8026
  E-MAIL: [email protected]
  SERVING SINCE SEP 30, 2001
  EMPLOYMENT CATEGORY: FR
  SUPERVISOR: GATHRIGHT, RICHARD EUGENE JR
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-22 Cont ID  
Sent By jpearson Date 2019-06-22 Time 16:29 Rev Time 0.00
Received By jpearson Date 2019-06-22 Time 16:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By jpearson Date 2019-04-26 Time 11:01 Rev Time 0.00
Received By jpearson Date 2019-04-26 Time 10:36 Sent To  
Notes
2019-04-26 11:01:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. SHEET E101, GENERAL NOTE 2 STATES THAT INTERIOR
 LIGHTING WILL BE CONTROLLED BY LOCAL SWITCHES. PROVIDE
 THE ADDITIONAL INTERIOR LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. BE ADVISED THAT FIRE ALARM, PV SYSTEMS, LOW VOLTAGE
 SYSTEMS, DAS, LIGHTNING PROTECTION, GENERATORS,
 COMMERCIAL HOOD SYSTEMS, WALK IN COOLERS, SIGNS, SITE
 LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB
 FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-07-08 Cont ID  
Sent By mgonzale Date 2019-07-08 Time   Rev Time 1.00
Received By mgonzale Date 2019-07-08 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 08:14 Rev Time 0.00
Received By shill Date 2019-04-30 Time 08:14 Sent To  
Notes
2019-04-30 08:14:25CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By pleduc Date 2019-07-29 Time   Rev Time 0.00
Received By pleduc Date 2019-07-29 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 12:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By scaldero Date 2019-04-04 Time 11:32 Rev Time 0.00
Received By scaldero Date 2019-04-04 Time 09:56 Sent To  
Notes
2019-04-04 11:32:43PERMIT # 19031394
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SHEET A000: PLEASE CORRECT FIRE DEPARTMENT CONTACT
 INFORMATION. MIKE CARSILLO HAS RETIRED. THE CURRENT
 FIRE MARSHAL IS PETER LEDUC.
  
 2) SEPERATE PLANS AND PERMIT(S) REQUIRED FOR HOOD
 SUPPRESSION SYSTEMS.
  
 3) AN CCUPANT LOAD OF THE ROOM SHALL BE POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT. SIGNS SHALL BE
 DURABLE AND INDICATE THE NUMBER OF OCCUPANTS PERMITTED
 FOR EACH ROOM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-08-05 Cont ID  
Sent By shill Date 2019-08-05 Time 11:28 Rev Time 0.00
Received By shill Date 2019-08-05 Time 11:28 Sent To  
Notes
2019-08-05 11:29:131) MIRROR SHALL BE MOUNTED 40" TO THE REFLECTIVE
 SURFACE.
  
 2) PIPING INSULATION SHALL BE MIN 1" WALL THICKNESS
  
 3) BACKFLOW FOR COMMERCIAL IRRIGATION SYSTEMS SHALL BE
 RPZ AND LEAD FREE
  
 4) 4 COMPARTMENT SINK SHALL DISCHARGE WITH MIN 3" PIPE
 TO A MIN 3" FLOOR SINK.
  
 5) PLB, GAS, INTERCEPTOR, BACKFLOWS, AND IRRIGATION ALL
 REQUIRE SEPARATE PERMITS.
  
  
 REVIEWED REMOTELY BY T.HUNT
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By jesmith Date 2019-06-26 Time 15:08 Rev Time 0.00
Received By jesmith Date 2019-06-26 Time 15:06 Sent To  
Notes
2019-06-26 15:08:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96-08
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMEMTS: DENIED
 A SEPARATE GAS PERMIT IS REQUIRED
 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED
 COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505.
 3. P101/PLUMBING KEY NOTE 24; PER WPB FBC 107.2.1,
 PROVIDE SPECIFICATION FOR THE VENTLESS GAS PRESSURE
 REGULATOR INDICATED IN NOTE.
 4. P101/PLUMBING KEY NOTES 13 AND 23; PER WPB FBC
 107.2.1, PROVIDE SPECIFICATION FOR THE GAS PRESSURE
 REGULATOR INDICATED IN NOTE. PR SHALL BE RATED FOR
 OUTDOOR APPLICATION AND SHALL BE NOTED AS SUCH IN THE
 SPECIFICATION.
 5. PER WPB FBC 107.2.1, SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER FBC FG, SECS. 402.4.1, 402.4.2. SHOW ALL
 SIZING, VALVES AND PRESSURE REGULATORS. EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING.
 THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA
 96-08.
 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37).
 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF
 GAS (LP OR NATURAL).
 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE
 POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 FBC FG SEC.402.4.1, 402.4.2. NOTE THAT THERE IS A 2PSI
 SYSTEM AND LOW PRESSURE SYSTEM(S). CLEARLY INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN.
 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING
 REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU
 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM.
 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 MANUAL GAS SHUTOFF VALVES AND THE EMERGENCY HOOD SHUT
 DOWN SHUT OFF VALVE.
 11. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS
 CONNECTION TO RTU INCLUDING MP REGULATOR, SHUT OFF
 VALVE, UNION AND DIRT LEG.
 12. PER WPB FBC 107.2.1, PROVIDE DETAIL OF EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE, MANUAL SHUTOFF VALVE, MP
 REGULATOR AND UNION. PROVIDE DIRT LEG. COMPLY WITH
 SECS. 10.4, 10.5 OF NFPA 96-08.
 13. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS
 CONNECTION TO FS ITEM 11, DEEP FAT FRYER INCLUDING SHUT
 OFF VALVE AND UNION. IF FLEXIBLE CONNECTORS ARE TO BE
 USED, PROVIDE SPECIFICATION.
 14. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1
 15. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED
 IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19031394 1345 N CONGRESS AVE
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 14:38 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 14:38 Sent To  
Notes
2019-06-26 13:27:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC
 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL
 REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND
 NOT TO TABLE 1003.5.1 FLORIDA PLUMBING CODE.
 NEW COMMENTS:
 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN
 ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2,
 PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY;
 SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE
 COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW
 LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE
 PLAN.
 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT VENT.
 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1
 FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2
 FLOOR DRAINS IN ACCORDANCE WITH FBC PL 1002.4.
 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS
 FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE DETAIL.
 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP
 SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF
 RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL WS-11.
 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X
 ?? & 1? METER INSTALLATION DETAIL
 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW
 ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS
 DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION.
 PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE
 DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD
 DETAIL WS-11
 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR IRRIGATION
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19031394 1345 N CONGRESS AVE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-05 Cont ID  
Sent By shill Date 2019-08-05 Time 11:29 Rev Time 0.00
Received By shill Date 2019-07-26 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-12 Cont ID  
Sent By jgomez Date 2019-07-12 Time 15:02 Rev Time 0.00
Received By jgomez Date 2019-06-17 Time 08:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By lmarchan Date 2019-04-30 Time 16:32 Rev Time 0.00
Received By lmarchan Date 2019-04-01 Time 11:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By lmarchan Date 2019-08-14 Time 14:43 Rev Time 0.00
Received By lmarchan Date 2019-08-05 Time 15:06 Sent To  
Notes
2019-08-14 14:44:27RECEIPT MU2019-025493-0000 - $0.00 DUE
2019-08-05 15:07:098/5/19 SENT EMAIL TO CONFIRM IF IMPACT WAS PREVIOUSLY
 DONE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-29 Cont ID  
Sent By jgomez Date 2019-04-29 Time 17:42 Rev Time 0.00
Received By jgomez Date 2019-04-29 Time 17:42 Sent To  
Notes
2019-04-29 17:42:31IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-02 Cont ID  
Sent By shill Date 2019-08-02 Time 15:15 Rev Time 0.00
Received By ccole Date 2019-08-02 Time 16:44 Sent To  
Notes
2019-08-02 15:15:31REVIEWED BY C.COLE WORKING REMOTELY
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-01 Cont ID  
Sent By ccole Date 2019-07-01 Time 15:37 Rev Time 0.00
Received By ccole Date 2019-07-01 Time 12:58 Sent To  
Notes
2019-07-01 15:56:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19031394
 7/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #6 & #8 FROM THE 1ST REVIEW HAVE ONLY BEEN
 PARTIALLY ADDRESS. SEE COMMENTS AND REMARKS BELOW.
  
 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND
 COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE
 RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M &
 SECTION 1609 FBC B.
  
 REMARK: THE NARRATIVE RESPONSE FROM THE ARCHITECT
 INDICATES THE ENGINEERING HAS BEEN PROVIDED HOWEVER IT
 IS INCOMPLETE.
 A) THE SUBMITTED PRODUCT APPROVAL FOR THE ROOF STAND IS
 MISSING INSTALLATION PAGES 3-10.
 B) THE PRODUCT APPROVAL FOR THE CURB DOES NOT PROVIDE
 RTU ATTACHMENT.
 C) THE WINDLOAD DESIGN CRITERIA HAS NOT BEEN PROVIDED.
 D) NO FASTENING DETAILS HAVE BEEN PROVIDED FOR
 ATTACHING THE RTU'S TO THE CURBS, OR THE CONDENSER TO
 THE STANDS.
  
 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT
 DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1
 FBC FG.
  
 REMARK: THE REQUESTED CUT SHEETS FOR THE GAS-FIRED
 COOKING APPLIANCES HAVE NOT BEEN PROVIDED.
  
 PLEASE NOTE THAT THE MISSING ITEMS ADDRESSED ABOVE MAY
 BE DEFERRED SUBMITTALS BY REQUEST.
  
 PLEASE NOTE: THE DIGITALLY SIGNED PLANS SHALL ALSO BEAR
 THIS STATEMENT IN ACCORDANCE WITH SECTION 61G15-23.005-
 "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 _________ON DATE________USING A SHA-1 AUTHENTICATION
 CODE." THE CURRENT MECHANICAL PLANS INDICATE THEY ARE
 SIGNED ONLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-29 Cont ID  
Sent By ccole Date 2019-04-29 Time 10:39 Rev Time 0.00
Received By ccole Date 2019-04-29 Time 10:39 Sent To  
Notes
2019-04-29 10:45:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19031394
 4/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC EC.
  
 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKES- SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 3) SEPERATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS,
 FIRE SUPPRESSION SYSTEMS, AND THE WALKIN COOLER AND
 FREEZER- SECTION 107.2.1 WPB. PLEASE PLACE NOTES ON THE
 PLAN ACCORDINGLY.
  
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE RTU'S, MUA, WALKIN CONDENSERS, AND THE GREASE
 EXHAUST AND MAKEUP AIR FANS. PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS FROM EXHAUST AIR OUTLETS TO AIR INTAKES,
 AND DISTANCES OF SERVICEABLE EQUIPMENT TO ROOF EDGES-
 SEE SECTIONS 304.11 & 501.3.1 FBC M.
  
 5) CLARIFY HOW ACCESS TO THE ROOF TO SERVICE EQUIPMENT
 WILL BE PROVIDED- SEE SECTION 306.5 FBC M.
  
 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND
 COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE
 RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M &
 SECTION 1609 FBC B.
  
 7) M100: PROVIDE A GAS PIPING PLAN FOR THE NEW RTU'S-
 SECTION
  
 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT
 DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-05 Cont ID  
Sent By shill Date 2019-08-05 Time 11:29 Rev Time 0.00
Received By shill Date 2019-08-05 Time 11:29 Sent To  
Notes
2019-08-05 11:29:371) MIRROR SHALL BE MOUNTED 40" TO THE REFLECTIVE
 SURFACE.
  
 2) PIPING INSULATION SHALL BE MIN 1" WALL THICKNESS
  
 3) BACKFLOW FOR COMMERCIAL IRRIGATION SYSTEMS SHALL BE
 RPZ AND LEAD FREE
  
 4) 4 COMPARTMENT SINK SHALL DISCHARGE WITH MIN 3" PIPE
 TO A MIN 3" FLOOR SINK.
  
 5) PLB, GAS, INTERCEPTOR, BACKFLOWS, AND IRRIGATION ALL
 REQUIRE SEPARATE PERMITS.
  
  
 REVIEWED REMOTELY BY T.HUNT
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By jesmith Date 2019-06-26 Time 13:27 Rev Time 0.00
Received By jesmith Date 2019-06-26 Time 07:44 Sent To  
Notes
2019-06-26 15:06:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS:
 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC
 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL
 REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND
 NOT TO TABLE 1003.5.1 FLORIDA PLUMBING
 CODE.
 NEW COMMENTS:
 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN
 ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2,
 PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY;
 SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE
 COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW
 LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE
 PLAN.
 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT
 VENT.
 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1
 FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2
 FLOOR DRAINS IN ACCORDANCE WITH FBC PL
 1002.4.
 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS
 FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE
 DETAIL.
 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP
 SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF
 RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL
 WS-11.
 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X
 ?? & 1? METER INSTALLATION DETAIL
 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW
 ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS
 DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION.
 PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE
 DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD
 DETAIL WS-11
 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR
 IRRIGATION
 8. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED
 IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19010472 2841 VILLAGE BLVD
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 15:57 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 09:10 Sent To  
Notes
2019-04-26 15:57:591ST REVIEW: 19031394
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR
  
 2. SHT. A111 PROVIDE OVERALL DIMENSIONS OF THE
 BATHROOMS TO VERIFY COMPLIANCE WITH FBC ACC 604.3.1,
 606.2
  
 3.WHAT IS THE WH ON THE BACK WALL NEXT TO CO2 IT IS NOT
 CONNECTED WATER SYSTEM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. PLEASE PROVIDE WATER ISOMETRIC PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 5. PROVIDE GREASE TRAP SIZING CALCULATIONS. FBC PL
 1003.1
  
 6. SHT. SHT P100 NOTES ON THE PLAN CALLS OUT THE CIVIL
 DRAWING FOR THE SEWER AND GREASE INTERCEPTOR CIVIL
 SHEETS NOT INCUDED IN PLAN SET. PER WPB AMEND TO FBC
 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-08-05 Cont ID  
Sent By shill Date 2019-08-05 Time 11:27 Rev Time 0.00
Received By shill Date 2019-08-05 Time 11:27 Sent To  
Notes
2019-08-05 11:28:21SEPARATE PERMIT REQUIRED
 REVIEWED REMOTELY BY T.HUNT
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 10:22 Rev Time 0.00
Received By pvalenti Date 2019-08-05 Time 10:22 Sent To  
Notes
2019-08-05 10:32:01PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING APPROVED WITH PROVISO:
  
 PROVIDE ENGINEER APPROVED PRODUCT APPROVALS WITH
 REQUIRED ROOFING SUB-PERMIT PACKAGE AND HAVE ON-SITE AT
 TIME OF INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-07-12 Cont ID  
Sent By jgomez Date 2019-07-12 Time 14:59 Rev Time 0.00
Received By jgomez Date 2019-07-12 Time 14:59 Sent To  
Notes
2019-07-12 15:00:271- PRODUCT APPROVALS SUBMITTED
 A) FLAT ROOF: FL1559-R12.
  
 B) METAL ROOF: FL 10094.R6

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By jgomez Date 2019-04-30 Time 14:03 Rev Time 0.00
Received By jgomez Date 2019-04-30 Time 14:03 Sent To  
Notes
2019-04-30 14:04:441- FLAT ROOF MEMBRANE ROOFING FLORIDA PRODUCT APPROVAL
 FL1559-R12: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES. NOTE: RAS 117 CALCULATIONS NEED TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By shill Date 2019-08-02 Time 15:27 Rev Time 0.00
Received By shill Date 2019-08-02 Time 15:27 Sent To  
Notes
2019-06-22 16:24:56FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED
 AND SEALED" AS PER FAC 61G15-23.004. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 08:35 Rev Time 0.00
Received By shill Date 2019-04-30 Time 08:14 Sent To  
Notes
2019-04-30 08:48:33SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SHEETS SIGNED AND SEALED BY ALLEN MORRIS, PE
 (STRUCTURAL) LACK THE LANGUAGE REQUIRED BY
 FAC61G15-23.004.
  
 THE CERTIFICATE OF AUTHORIZATION FOR STABILITY
 ENGINEERING, LLC IS DELINQUENT (PLEASE CONTACT FBPE).
 THE CERTIFICATE OF AUTHORIZATION NUMBER (32087) IS
 REQUIRED TO BE INCLUDED IN THE TITLE BLOCK.
  
 2. THE SHEETS SIGNED AND SEALED BY JONATHAN EDWARDS, PE
 (MECHANICAL, PLUMBING), JESSE MCCULLOUGH, PE
 (ELECTRICAL) LACK THE LANGUAGE REQUIRED BY
 FAC61G15-23.004.
  
 THE CERTIFICATE OF AUTHORIZATION FOR MRP DESIGN GROUP
 IS IN CLOSED STATUS (AS OF 9/03/2004). A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED TO PRACTICE ENGINEERING
 THROUGH A COMPANY IN FLORIDA.
  
 3. GEOTECHNICAL REPORT PREPARED BY ROBERTO E. BALBIS,
 PE IS NOT DIGITALLY SIGNED. DOES THIS ENGINEER HAVE A
 DIGITAL SIGNATURE? IF YES, PLEASE UPLOAD A DIGITALLY
 SIGNED DOCUMENT. IF NOT, A PAPER ORIGINAL WILL BE
 REQUIRED TO BE SUBMITTED TO THE BUILDING DIVISION WITH
 A SUBMITTAL FORM. A SIGNATURE REVIEW WILL BE REQUIRED.
  
 4. THE GEOTECHNICAL ENGINEERING ANALYSIS PREPARED BY G.
 RYAN BRIDGER, PE IS NOT DIGITALLY SIGNED. IF APPLICANT
 HAS EVIDENCE OF THIS DOCUMENT BEING SUBMITTED WITH A
 PERMIT PREVIOUSLY ISSUED, PROVIDE A CITY STAMPED COPY.
 OTHERWISE, AN ORIGINAL WILL BE REQUIRED.
  
  
  
  
  
  
2019-04-26 10:36:03ELECTRICAL SHEETS GOOD.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-01 Cont ID  
Sent By eschneid Date 2019-08-01 Time 13:35 Rev Time 0.25
Received By eschneid Date 2019-08-01 Time 13:19 Sent To  
Notes
2019-08-01 13:20:49THE FOLLOWING FEATURES SHOWN ON THIS PLAN REQUIRE
 SEPARATE PERMITS WITH PLANS:
  
 A. PARKING LOT STRIPING
 B. HARDSCAPE
 C. DUMPSTER ENCLOSURE
 D. STORAGE ROOM
 E. CALL BOXES AND MENU BOARDS
 F. BICYCLE RACK AND PAD
 G. FENCE AROUND THE PATIO AREA
 H. SITE LIGHTING
 I. SIGNS
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By eschneid Date 2019-06-24 Time 14:20 Rev Time 0.75
Received By eschneid Date 2019-06-24 Time 14:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By eschneid Date 2019-04-30 Time 16:09 Rev Time 2.00
Received By eschneid Date 2019-04-30 Time 16:09 Sent To  
Notes
2019-04-30 16:30:08FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PROVIDE A COPY OF THE SURVEY.
  
 2) PROVIDE A SITE PLAN SHOWING THE SETBACK DIMENSIONS
 FOR THE BUILDING.
  
 3) SHEET A100-1 IS NOT THE APPROVED SITE LAYOUT. THE
 FOLLOWING FEATURES SHOWN ON THIS PLAN REQUIRE SEPARATE
 PERMITS WITH PLANS:
  
 A. PARKING LOT STRIPING
 B. HARDSCAPE
 C. DUMPSTER ENCLOSURE
 D. STORAGE ROOM
 E. CALL BOXES AND MENU BOARDS
 F. BICYCLE RACK AND PAD
 G. FENCE AROUND THE PATIO AREA
 H. SITE LIGHTING
  
 4) SIGNS REQUIRE SEPARATE PERMIT WITH PLANS.
  
 5) THE ZAXBY?S LOGO IS NOT PERMITTED ON THE WEATHER
 VANE. ROOFTOP SIGNS AND SIGNS WITH VISIBLE MOVING PARTS
 ARE NOT PERMITTED BY THE PALM BEACH OUTLETS DESIGN
 GUIDELINES.
  
 6) THE ELEVATION DRAWINGS MUST LIST THE DIRECTION THAT
 THE ELEVATION FACES (EX. NORTH, SOUTH) AND NOT JUST
 FRONT, BACK, ETC.
  
 7) THE GLAZING NOTES STATE THAT THE ?EXTERIOR SIDE?
 GLAZING WILL HAVE GRAY TINT. THE WINDOWS IN THE PALM
 BEACH OUTLETS MUST PERMIT VISIBILITY INTO THE
 ESTABLISHMENT. PLEASE VERIFY THAT THE TINT WILL PERMIT
 VISIBILITY INTO THE ZAXBY?S.
  
 8) THE SECTION DRAWINGS SHOW THE RTUS, A HOSHIZAKI
 REMOTE CONDENSER AND MAU-1 EXCEEDING THE HEIGHT OF THE
 PARAPET. THE APPROVED ELEVATION PLANS SHOWED THESE AT A
 LOWER HEIGHT THAN THE PARAPETS. PROVIDE DRAWINGS TO
 VERIFY THAT THE FULL HEIGHT OF THE ROOF TOP MECHANICAL
 EQUIPMENT IS SCREENED FROM PUBLIC VIEW. PLEASE NOTE
 THAT NOTATIONS STATING THAT THE ROOFTOP EQUIPMENT IS
 ONLY FOR GRAPHIC REPRESENTATION ARE NOT SUFFICIENT. THE
 EXACT EQUIPMENT AND CURB HEIGHT MUST BE SHOWN TO VERIFY
 SCREENING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  