| Plan Review Stops For Permit 19031394 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-03 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-03 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2019-08-03 13:11:35 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 3RD BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | | | | THE WALL R-VALUE FROM FROM THE ENERGY REPORT NEEDS TO | | | MATCH THE THE DETAILS ON THE ARCHITECTURAL PLANS PRIOR | | | TO INSPECTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-07-12 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-07-11 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2019-07-12 14:59:02 | NEW RESTAURANT (A2 ASSEMBLY) SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR | | | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME | | | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | | ISSUANCE. | | | | | | | | | 1- OK | | | | | | 2- OK | | | | | | 3- OK | | | | | | 4- ENERGY CALCULATIONS: | | | A) OK. | | | | | | B) CEILING R-VALUE INSULATION AND WALL R-VALUE | | | INSULATION DOESN'T MATCH ARCHITECTURAL PLANS. REVISE AS | | | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | ENERGY CALCULATIONS WERE REVISED, BUT THEY STILL DON'T | | | MATCH. SEE PLANS AND REVISE AS REQUIRED. | | | NOTE: ALSO, CHECK TYPE OF WALLS SPECIFIED FOR THE | | | KITCHEN. THEY DON'T SEEM TO MATCH PLANS EITHER. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | C)OK. | | | | | | 5- OK | | | | | | 6- PRODUCT APPROVALS SUBMITTED:FAC 61G20-3.001 | | | A) OK | | | | | | B) OK | | | | | | C) OK | | | | | | | | | 7- OK | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-04-29 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-26 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2019-04-30 14:00:25 | NEW RESTAURANT (A2 ASSEMBLY) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). | | | SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). | | | | | | 2- REVISE OCCUPANT LOAD SHOWN ON THE LIFE SAFETY PLAN | | | AND COVER SHEET | | | A)NUMBER OF PEOPLE IN KITCHEN AREA IS BASED ON THE | | | TOTAL GROSS AREA AS REQUIRED BY TABLE 1004.1.2 | | | FBC-BUILDING. THIS INCLUDES THE WALK-IN FREEZER AND | | | COOLER. ALSO, NUMBER OF PEOPLE SHOWN ON THE LIFE SAFETY | | | PLAN DOESN'T MATCH NUMBER SHOWN ON THE COLUMN WHEN | | | ADDING THE TOTAL NUMBER OF PEOPLE. REVISE AS REQUIRED | | | TO MATCH. | | | | | | B) NUMBER OF PEOPLE ON THE ROUND BOOTH NEEDS TO BE | | | REVISED CONSIDERING A 24 INCH PER PERSON OF SEATING | | | LENGTH AS REQUIRED BY SEC. 1004.4 FBC-BUILDING. ALSO, | | | NEED TO ADD THE ADDITIONAL SPACE SHOWN FOR THE | | | WHEELCHAIR. | | | | | | C) NUMBER OF PEOPLE SHOWN ON THE QUEUE LINE NEEDS TO BE | | | REVISED. THIS AREA IS MORE THAN 80S.F. TABLE 1004.1.2 | | | FBC-BUILDING. | | | | | | 3- THE BUILDING THERMAL ENVELOPE NEEDS TO BE CLEARLY | | | DEPICTED ON PLANS AS REQUIRED BY SEC. C103.2.1 | | | FBC-ENERGY CONSERVATION. ARCHITECTURAL WALL SECTIONS | | | SHOW FURRING STRIPS ON CMU WALLS UP TO 6 INCHES ABOVE | | | THE SUSPENDED CEILING. WHAT HAPPENS TO THE REST OF THE | | | WALL. ARCHITECT TO SHOW COMPLETE THERMAL ENVELOPE AND | | | SPECIFY R-VALUE OF WALL. COORDINATE WITH ENERGY | | | CALCULATIONS TO AVOID CONFLICTS/DELAYS. | | | | | | 4- ENERGY CALCULATIONS: | | | A) A/C AREA SPECIFIED ON THE ENERGY CALCULATIONS | | | DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | B) CEILING R-VALUE INSULATION AND WALL R-VALUE | | | INSULATION DOESN'T MATCH ARCHITECTURAL PLANS. REVISE | | | ASD REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | C) BUILDING ADDRESS SHOWN ON THE ENERGY CALCULATIONS IS | | | INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 5- DOORS AND WINDOWS BUCK DETAILS DON'T PROVIDE | | | SPECIFICATIONS FOR THE FASTENING OF THE STRUCTURAL | | | BUCK. PROVIDE COMPLETE SPECIFICATIONS. SEC. 1609.1 | | | FBC-BUILDING. | | | | | | 6- PRODUCT APPROVALS SUBMITTED:FAC 61G20-3.001 | | | A) PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE FOR | | | EACH FLORIDA PRODUCT APPROVAL SUBMITTED. THIS IS | | | REQUIRED BECAUSE THE COVER PAGE SHOWS THE STATUS OF THE | | | PRODUCT APPROVAL AND THE CODE IN EFFECT. | | | | | | B) PROVIDE LATEST REVISION OF FLORIDA PRODUCT APPROVAL | | | FOR: | | | (1)FL1559. CURRENT REVISION IS R-12 NOT R-11. | | | (2) FL8787. CURRENT REVISION IS R-9 NOT R-8. | | | (3)FL4553. CURRENT REVISION IS R-11 NOT R-10. | | | | | | | | | C) FLAT ROOF MEMBRANE ROOFING FLORIDA PRODUCT APPROVAL | | | FL1559-R12: CLEARLY MARK WHICH APPROVED ASSEMBLY IS | | | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES. NOTE: RAS 117 CALCULATIONS NEED TO BE | | | SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN | | | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | | | | 7- CONTRACTOR TO CONTACT KEN CONRAD (CHIEF BUILDING | | | INSPECTOR ) FOR COORDINATION OF SPECIAL INSPECTIONS | | | LISTED ON SHEET S002. | | | KEN CONRAD | | | CHIEF BUILDING INSPECTOR | | | DEVELOPMENT SERVICES | | | BUILDING INSPECTIONS | | | 401 CLEMATIS STREET | | | P.O.BOX 3366 | | | WEST PALM BEACH, FL 33402 | | | PHONE: 805-6666 EXT: 6666 | | | FAX: 659-8026 | | | E-MAIL: [email protected] | | | SERVING SINCE SEP 30, 2001 | | | EMPLOYMENT CATEGORY: FR | | | SUPERVISOR: GATHRIGHT, RICHARD EUGENE JR | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-06-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-22 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-22 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-04-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-04-26 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-04-26 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2019-04-26 11:01:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10 | | | 2. SHEET E101, GENERAL NOTE 2 STATES THAT INTERIOR | | | LIGHTING WILL BE CONTROLLED BY LOCAL SWITCHES. PROVIDE | | | THE ADDITIONAL INTERIOR LIGHTING CONTROLS STIPULATED IN | | | THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | | AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | | 4. BE ADVISED THAT FIRE ALARM, PV SYSTEMS, LOW VOLTAGE | | | SYSTEMS, DAS, LIGHTNING PROTECTION, GENERATORS, | | | COMMERCIAL HOOD SYSTEMS, WALK IN COOLERS, SIGNS, SITE | | | LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT | | | INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A | | | BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND | | | PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB | | | FBC 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2019-07-08 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2019-07-08 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-30 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-30 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2019-04-30 08:14:25 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-07-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-07-29 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-20 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-04-04 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-04-04 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-04-04 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2019-04-04 11:32:43 | PERMIT # 19031394 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) SHEET A000: PLEASE CORRECT FIRE DEPARTMENT CONTACT | | | INFORMATION. MIKE CARSILLO HAS RETIRED. THE CURRENT | | | FIRE MARSHAL IS PETER LEDUC. | | | | | | 2) SEPERATE PLANS AND PERMIT(S) REQUIRED FOR HOOD | | | SUPPRESSION SYSTEMS. | | | | | | 3) AN CCUPANT LOAD OF THE ROOM SHALL BE POSTED IN A | | | CONSPICUOUS PLACE NEAR THE MAIN EXIT. SIGNS SHALL BE | | | DURABLE AND INDICATE THE NUMBER OF OCCUPANTS PERMITTED | | | FOR EACH ROOM. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-05 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-05 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2019-08-05 11:29:13 | 1) MIRROR SHALL BE MOUNTED 40" TO THE REFLECTIVE | | | SURFACE. | | | | | | 2) PIPING INSULATION SHALL BE MIN 1" WALL THICKNESS | | | | | | 3) BACKFLOW FOR COMMERCIAL IRRIGATION SYSTEMS SHALL BE | | | RPZ AND LEAD FREE | | | | | | 4) 4 COMPARTMENT SINK SHALL DISCHARGE WITH MIN 3" PIPE | | | TO A MIN 3" FLOOR SINK. | | | | | | 5) PLB, GAS, INTERCEPTOR, BACKFLOWS, AND IRRIGATION ALL | | | REQUIRE SEPARATE PERMITS. | | | | | | | | | REVIEWED REMOTELY BY T.HUNT | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-06-26 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-06-26 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-06-26 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2019-06-26 15:08:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 96-08 | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | GAS COMMEMTS: DENIED | | | A SEPARATE GAS PERMIT IS REQUIRED | | | 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE | | | INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER | | | HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER | | | APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS | | | SYSTEMS | | | 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED | | | COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION, | | | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND | | | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL | | | GAS SECS. 502 THRU 505. | | | 3. P101/PLUMBING KEY NOTE 24; PER WPB FBC 107.2.1, | | | PROVIDE SPECIFICATION FOR THE VENTLESS GAS PRESSURE | | | REGULATOR INDICATED IN NOTE. | | | 4. P101/PLUMBING KEY NOTES 13 AND 23; PER WPB FBC | | | 107.2.1, PROVIDE SPECIFICATION FOR THE GAS PRESSURE | | | REGULATOR INDICATED IN NOTE. PR SHALL BE RATED FOR | | | OUTDOOR APPLICATION AND SHALL BE NOTED AS SUCH IN THE | | | SPECIFICATION. | | | 5. PER WPB FBC 107.2.1, SUBMIT AN ISOMETRIC DRAWING | | | THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF | | | PIPE PER FBC FG, SECS. 402.4.1, 402.4.2. SHOW ALL | | | SIZING, VALVES AND PRESSURE REGULATORS. EMERGENCY HOOD | | | SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING. | | | THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA | | | 96-08. | | | 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH | | | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER | | | TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1) | | | THRU 402.4 (37). | | | 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF | | | GAS (LP OR NATURAL). | | | 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE | | | POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE | | | MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER | | | FBC FG SEC.402.4.1, 402.4.2. NOTE THAT THERE IS A 2PSI | | | SYSTEM AND LOW PRESSURE SYSTEM(S). CLEARLY INDICATE THE | | | DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN. | | | 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING | | | REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU | | | 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING | | | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON | | | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) | | | FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS | | | SYSTEM. | | | 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR | | | MANUAL GAS SHUTOFF VALVES AND THE EMERGENCY HOOD SHUT | | | DOWN SHUT OFF VALVE. | | | 11. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS | | | CONNECTION TO RTU INCLUDING MP REGULATOR, SHUT OFF | | | VALVE, UNION AND DIRT LEG. | | | 12. PER WPB FBC 107.2.1, PROVIDE DETAIL OF EMERGENCY | | | HOOD SHUT DOWN SHUT OFF VALVE, MANUAL SHUTOFF VALVE, MP | | | REGULATOR AND UNION. PROVIDE DIRT LEG. COMPLY WITH | | | SECS. 10.4, 10.5 OF NFPA 96-08. | | | 13. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS | | | CONNECTION TO FS ITEM 11, DEEP FAT FRYER INCLUDING SHUT | | | OFF VALVE AND UNION. IF FLEXIBLE CONNECTORS ARE TO BE | | | USED, PROVIDE SPECIFICATION. | | | 14. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS | | | APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1 | | | 15. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED | | | IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB | | | FBC 107.2.1 | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19031394 1345 N CONGRESS AVE | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-26 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-26 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2019-06-26 13:27:39 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 30A | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMEMTS: DENIED | | | | | | 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC | | | 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL | | | REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND | | | NOT TO TABLE 1003.5.1 FLORIDA PLUMBING CODE. | | | NEW COMMENTS: | | | 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN | | | ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2, | | | PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY; | | | SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE | | | COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW | | | LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE | | | PLAN. | | | 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE | | | INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER | | | HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER | | | APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS | | | SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT VENT. | | | 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1 | | | FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2 | | | FLOOR DRAINS IN ACCORDANCE WITH FBC PL 1002.4. | | | 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS | | | FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE DETAIL. | | | 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP | | | SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF | | | RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL WS-11. | | | 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X | | | ?? & 1? METER INSTALLATION DETAIL | | | 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW | | | ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS | | | DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION. | | | PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE | | | DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD | | | DETAIL WS-11 | | | 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR IRRIGATION | | | | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19031394 1345 N CONGRESS AVE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-05 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-26 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-07-12 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-06-17 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-04-30 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-04-01 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-14 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-05 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2019-08-14 14:44:27 | RECEIPT MU2019-025493-0000 - $0.00 DUE | | 2019-08-05 15:07:09 | 8/5/19 SENT EMAIL TO CONFIRM IF IMPACT WAS PREVIOUSLY | | | DONE |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-04-29 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-29 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2019-04-29 17:42:31 | IMPACT FEES - DIGITAL SUBMITTALS | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-02 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-08-02 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2019-08-02 15:15:31 | REVIEWED BY C.COLE WORKING REMOTELY | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-01 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-01 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2019-07-01 15:56:53 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19031394 | | | 7/1/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENTS #6 & #8 FROM THE 1ST REVIEW HAVE ONLY BEEN | | | PARTIALLY ADDRESS. SEE COMMENTS AND REMARKS BELOW. | | | | | | 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND | | | COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE | | | RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M & | | | SECTION 1609 FBC B. | | | | | | REMARK: THE NARRATIVE RESPONSE FROM THE ARCHITECT | | | INDICATES THE ENGINEERING HAS BEEN PROVIDED HOWEVER IT | | | IS INCOMPLETE. | | | A) THE SUBMITTED PRODUCT APPROVAL FOR THE ROOF STAND IS | | | MISSING INSTALLATION PAGES 3-10. | | | B) THE PRODUCT APPROVAL FOR THE CURB DOES NOT PROVIDE | | | RTU ATTACHMENT. | | | C) THE WINDLOAD DESIGN CRITERIA HAS NOT BEEN PROVIDED. | | | D) NO FASTENING DETAILS HAVE BEEN PROVIDED FOR | | | ATTACHING THE RTU'S TO THE CURBS, OR THE CONDENSER TO | | | THE STANDS. | | | | | | 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT | | | DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1 | | | FBC FG. | | | | | | REMARK: THE REQUESTED CUT SHEETS FOR THE GAS-FIRED | | | COOKING APPLIANCES HAVE NOT BEEN PROVIDED. | | | | | | PLEASE NOTE THAT THE MISSING ITEMS ADDRESSED ABOVE MAY | | | BE DEFERRED SUBMITTALS BY REQUEST. | | | | | | PLEASE NOTE: THE DIGITALLY SIGNED PLANS SHALL ALSO BEAR | | | THIS STATEMENT IN ACCORDANCE WITH SECTION 61G15-23.005- | | | "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY | | | _________ON DATE________USING A SHA-1 AUTHENTICATION | | | CODE." THE CURRENT MECHANICAL PLANS INDICATE THEY ARE | | | SIGNED ONLY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-04-29 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-04-29 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2019-04-29 10:45:36 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19031394 | | | 4/29/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC EC. | | | | | | 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR | | | THE O/A INTAKES- SECTION C403.2.4.3 FBC-17 ENERGY | | | CONSERVATION. | | | | | | 3) SEPERATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS, | | | FIRE SUPPRESSION SYSTEMS, AND THE WALKIN COOLER AND | | | FREEZER- SECTION 107.2.1 WPB. PLEASE PLACE NOTES ON THE | | | PLAN ACCORDINGLY. | | | | | | 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS | | | OF THE RTU'S, MUA, WALKIN CONDENSERS, AND THE GREASE | | | EXHAUST AND MAKEUP AIR FANS. PROVIDE CLEARANCE DISTANCE | | | MEASUREMENTS FROM EXHAUST AIR OUTLETS TO AIR INTAKES, | | | AND DISTANCES OF SERVICEABLE EQUIPMENT TO ROOF EDGES- | | | SEE SECTIONS 304.11 & 501.3.1 FBC M. | | | | | | 5) CLARIFY HOW ACCESS TO THE ROOF TO SERVICE EQUIPMENT | | | WILL BE PROVIDED- SEE SECTION 306.5 FBC M. | | | | | | 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND | | | COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE | | | RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M & | | | SECTION 1609 FBC B. | | | | | | 7) M100: PROVIDE A GAS PIPING PLAN FOR THE NEW RTU'S- | | | SECTION | | | | | | 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT | | | DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1 | | | FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-05 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-05 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2019-08-05 11:29:37 | 1) MIRROR SHALL BE MOUNTED 40" TO THE REFLECTIVE | | | SURFACE. | | | | | | 2) PIPING INSULATION SHALL BE MIN 1" WALL THICKNESS | | | | | | 3) BACKFLOW FOR COMMERCIAL IRRIGATION SYSTEMS SHALL BE | | | RPZ AND LEAD FREE | | | | | | 4) 4 COMPARTMENT SINK SHALL DISCHARGE WITH MIN 3" PIPE | | | TO A MIN 3" FLOOR SINK. | | | | | | 5) PLB, GAS, INTERCEPTOR, BACKFLOWS, AND IRRIGATION ALL | | | REQUIRE SEPARATE PERMITS. | | | | | | | | | REVIEWED REMOTELY BY T.HUNT | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-06-26 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-06-26 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-06-26 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2019-06-26 15:06:49 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 30A | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMEMTS: | | | 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC | | | 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL | | | REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND | | | NOT TO TABLE 1003.5.1 FLORIDA PLUMBING | | | CODE. | | | NEW COMMENTS: | | | 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN | | | ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2, | | | PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY; | | | SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE | | | COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW | | | LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE | | | PLAN. | | | 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE | | | INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER | | | HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER | | | APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS | | | SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT | | | VENT. | | | 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1 | | | FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2 | | | FLOOR DRAINS IN ACCORDANCE WITH FBC PL | | | 1002.4. | | | 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS | | | FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE | | | DETAIL. | | | 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP | | | SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF | | | RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL | | | WS-11. | | | 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X | | | ?? & 1? METER INSTALLATION DETAIL | | | 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW | | | ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS | | | DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION. | | | PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE | | | DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD | | | DETAIL WS-11 | | | 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR | | | IRRIGATION | | | 8. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED | | | IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB | | | FBC 107.2.1 | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19010472 2841 VILLAGE BLVD | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-26 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-26 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2019-04-26 15:57:59 | 1ST REVIEW: 19031394 | | | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | | FLOOR | | | | | | 2. SHT. A111 PROVIDE OVERALL DIMENSIONS OF THE | | | BATHROOMS TO VERIFY COMPLIANCE WITH FBC ACC 604.3.1, | | | 606.2 | | | | | | 3.WHAT IS THE WH ON THE BACK WALL NEXT TO CO2 IT IS NOT | | | CONNECTED WATER SYSTEM PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 4. PLEASE PROVIDE WATER ISOMETRIC PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | 5. PROVIDE GREASE TRAP SIZING CALCULATIONS. FBC PL | | | 1003.1 | | | | | | 6. SHT. SHT P100 NOTES ON THE PLAN CALLS OUT THE CIVIL | | | DRAWING FOR THE SEWER AND GREASE INTERCEPTOR CIVIL | | | SHEETS NOT INCUDED IN PLAN SET. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-05 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-05 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2019-08-05 11:28:21 | SEPARATE PERMIT REQUIRED | | | REVIEWED REMOTELY BY T.HUNT | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-05 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-05 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2019-08-05 10:32:01 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ROOFING APPROVED WITH PROVISO: | | | | | | PROVIDE ENGINEER APPROVED PRODUCT APPROVALS WITH | | | REQUIRED ROOFING SUB-PERMIT PACKAGE AND HAVE ON-SITE AT | | | TIME OF INSPECTION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-07-12 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-07-12 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2019-07-12 15:00:27 | 1- PRODUCT APPROVALS SUBMITTED | | | A) FLAT ROOF: FL1559-R12. | | | | | | B) METAL ROOF: FL 10094.R6 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-04-30 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-04-30 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2019-04-30 14:04:44 | 1- FLAT ROOF MEMBRANE ROOFING FLORIDA PRODUCT APPROVAL | | | FL1559-R12: CLEARLY MARK WHICH APPROVED ASSEMBLY IS | | | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES. NOTE: RAS 117 CALCULATIONS NEED TO BE | | | SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN | | | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-08-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-02 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-02 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2019-06-22 16:24:56 | FOR ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE | | | FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND | | | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THE | | | DIGITAL SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED | | | AND SEALED" AS PER FAC 61G15-23.004. PROVIDE | | | CORRECTION. WPB FBC 107.1; FS 471/481 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-30 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-30 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2019-04-30 08:48:33 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE SHEETS SIGNED AND SEALED BY ALLEN MORRIS, PE | | | (STRUCTURAL) LACK THE LANGUAGE REQUIRED BY | | | FAC61G15-23.004. | | | | | | THE CERTIFICATE OF AUTHORIZATION FOR STABILITY | | | ENGINEERING, LLC IS DELINQUENT (PLEASE CONTACT FBPE). | | | THE CERTIFICATE OF AUTHORIZATION NUMBER (32087) IS | | | REQUIRED TO BE INCLUDED IN THE TITLE BLOCK. | | | | | | 2. THE SHEETS SIGNED AND SEALED BY JONATHAN EDWARDS, PE | | | (MECHANICAL, PLUMBING), JESSE MCCULLOUGH, PE | | | (ELECTRICAL) LACK THE LANGUAGE REQUIRED BY | | | FAC61G15-23.004. | | | | | | THE CERTIFICATE OF AUTHORIZATION FOR MRP DESIGN GROUP | | | IS IN CLOSED STATUS (AS OF 9/03/2004). A CERTIFICATE OF | | | AUTHORIZATION IS REQUIRED TO PRACTICE ENGINEERING | | | THROUGH A COMPANY IN FLORIDA. | | | | | | 3. GEOTECHNICAL REPORT PREPARED BY ROBERTO E. BALBIS, | | | PE IS NOT DIGITALLY SIGNED. DOES THIS ENGINEER HAVE A | | | DIGITAL SIGNATURE? IF YES, PLEASE UPLOAD A DIGITALLY | | | SIGNED DOCUMENT. IF NOT, A PAPER ORIGINAL WILL BE | | | REQUIRED TO BE SUBMITTED TO THE BUILDING DIVISION WITH | | | A SUBMITTAL FORM. A SIGNATURE REVIEW WILL BE REQUIRED. | | | | | | 4. THE GEOTECHNICAL ENGINEERING ANALYSIS PREPARED BY G. | | | RYAN BRIDGER, PE IS NOT DIGITALLY SIGNED. IF APPLICANT | | | HAS EVIDENCE OF THIS DOCUMENT BEING SUBMITTED WITH A | | | PERMIT PREVIOUSLY ISSUED, PROVIDE A CITY STAMPED COPY. | | | OTHERWISE, AN ORIGINAL WILL BE REQUIRED. | | | | | | | | | | | | | | | | | | | | 2019-04-26 10:36:03 | ELECTRICAL SHEETS GOOD. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-01 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-08-01 |
Time |
13:35 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2019-08-01 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2019-08-01 13:20:49 | THE FOLLOWING FEATURES SHOWN ON THIS PLAN REQUIRE | | | SEPARATE PERMITS WITH PLANS: | | | | | | A. PARKING LOT STRIPING | | | B. HARDSCAPE | | | C. DUMPSTER ENCLOSURE | | | D. STORAGE ROOM | | | E. CALL BOXES AND MENU BOARDS | | | F. BICYCLE RACK AND PAD | | | G. FENCE AROUND THE PATIO AREA | | | H. SITE LIGHTING | | | I. SIGNS | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-06-24 |
Time |
14:20 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
2019-06-24 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-04-30 |
Time |
16:09 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2019-04-30 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2019-04-30 16:30:08 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) PROVIDE A COPY OF THE SURVEY. | | | | | | 2) PROVIDE A SITE PLAN SHOWING THE SETBACK DIMENSIONS | | | FOR THE BUILDING. | | | | | | 3) SHEET A100-1 IS NOT THE APPROVED SITE LAYOUT. THE | | | FOLLOWING FEATURES SHOWN ON THIS PLAN REQUIRE SEPARATE | | | PERMITS WITH PLANS: | | | | | | A. PARKING LOT STRIPING | | | B. HARDSCAPE | | | C. DUMPSTER ENCLOSURE | | | D. STORAGE ROOM | | | E. CALL BOXES AND MENU BOARDS | | | F. BICYCLE RACK AND PAD | | | G. FENCE AROUND THE PATIO AREA | | | H. SITE LIGHTING | | | | | | 4) SIGNS REQUIRE SEPARATE PERMIT WITH PLANS. | | | | | | 5) THE ZAXBY?S LOGO IS NOT PERMITTED ON THE WEATHER | | | VANE. ROOFTOP SIGNS AND SIGNS WITH VISIBLE MOVING PARTS | | | ARE NOT PERMITTED BY THE PALM BEACH OUTLETS DESIGN | | | GUIDELINES. | | | | | | 6) THE ELEVATION DRAWINGS MUST LIST THE DIRECTION THAT | | | THE ELEVATION FACES (EX. NORTH, SOUTH) AND NOT JUST | | | FRONT, BACK, ETC. | | | | | | 7) THE GLAZING NOTES STATE THAT THE ?EXTERIOR SIDE? | | | GLAZING WILL HAVE GRAY TINT. THE WINDOWS IN THE PALM | | | BEACH OUTLETS MUST PERMIT VISIBILITY INTO THE | | | ESTABLISHMENT. PLEASE VERIFY THAT THE TINT WILL PERMIT | | | VISIBILITY INTO THE ZAXBY?S. | | | | | | 8) THE SECTION DRAWINGS SHOW THE RTUS, A HOSHIZAKI | | | REMOTE CONDENSER AND MAU-1 EXCEEDING THE HEIGHT OF THE | | | PARAPET. THE APPROVED ELEVATION PLANS SHOWED THESE AT A | | | LOWER HEIGHT THAN THE PARAPETS. PROVIDE DRAWINGS TO | | | VERIFY THAT THE FULL HEIGHT OF THE ROOF TOP MECHANICAL | | | EQUIPMENT IS SCREENED FROM PUBLIC VIEW. PLEASE NOTE | | | THAT NOTATIONS STATING THAT THE ROOFTOP EQUIPMENT IS | | | ONLY FOR GRAPHIC REPRESENTATION ARE NOT SUFFICIENT. THE | | | EXACT EQUIPMENT AND CURB HEIGHT MUST BE SHOWN TO VERIFY | | | SCREENING. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|