| Plan Review Stops For Permit 19031380 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-15 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-15 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2019-11-15 15:38:41 | PROVISO: | | | DEFERRED SUBMITTAL TO BE PROVIDED FOR WINDOW AND DOOR | | | PRODUCT APPROVALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-09-25 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-09-25 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2019-09-25 16:00:25 | PREVIOUS REVIEW WAS LOCKED AND CANNOT ADD NOTES | | | BUILDING NOTES WERE PUT INTO THE ROOF REVIEW STOP: | | | | | | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19031380 | | | REVIEWED: MAY 9, 2019 | | | 2ND REVIEW AUGUST 28, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) OK-ENERGY CALCS RECEIVED. IF NO CRAWL SPACE PROVIDED | | | THEY WILL NEED TO BE REVISED (SEE COMMENT 4). | | | | | | 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU | | | WOULD LIKE THEM DEFERED. | | | 2ND REVIEW - NONE RECEIVED. IF THESE ARE TO BE DEFERRED | | | SUBMITTAL THAN PLEASE INDICATE, OR PROVIDE PRODUCT | | | APPROVALS. | | | | | | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE | | | IT DEFERED. | | | 2ND REVIEW - NONE RECEIVED. PROVIDE PRODUCT APPROVALS | | | OR INDICATE THAT IT WILL BE SUBMITTED WITH THE SUB | | | PERMIT APPLICATION. | | | | | | 4) 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS | | | SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF | | | THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS | | | NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO | | | STRUCTURE. | | | THE PLAN CALLS FOR SLAB ON COMPACTED FILL AND THE | | | SECTION SHOWS CRAWL SPACE WITH NO CONNECTION DETAIL. | | | PLEASE COORDINATE THE PLANS AND DETAILS TO MATCH FLOOR | | | CONDITION. IF IT IS CRAWLSPACE THAN SEE SECTIONS FBC | | | R408.1, 408.2 AND 408.4 | | | | | | NOTES: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | 2ND REVIEW - NO COMMENT RESPONSE SHEET WAS SUBMITTED | | | AND NO CHANGES TO PLANS, SO SOME COMMENTS WERE NOT | | | ADDRESSED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-08-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-28 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-28 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-09 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-08 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2019-05-09 10:25:07 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19031380 | | | REVIEWED: MAY 9, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET | | | REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE | | | METHOD IN R401.2 AND SUPPLY DOCUMENTATION. | | | - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLIST AND | | | EPL CARD. | | | | | | 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU | | | WOULD LIKE THEM DEFERED. | | | | | | 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE | | | IT DEFERED. | | | | | | 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS | | | SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF | | | THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS | | | NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO | | | STRUCTURE. | | | | | | NOTES: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-08-27 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-08-27 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-04-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-20 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-04-20 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2019-04-20 08:16:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. SHOW CONDUCTOR SIZE FROM RISER TO METER-CAN FBC | | | 107.2.1 | | | | | | 2. SHOW CONDUCTOR SIZE FROM METER-CAN TO MAIN-BREAKER | | | PANEL. FBC 107.2.1 | | | | | | 3. PROVIDE ACCUATE LOAD CALCULATION. OCP FOR COOKTOP IS | | | SHOWN AS 40AMPS BUT ONLY 1200 WATTS SHOWN IN LOAD | | | CALCULATION. FBC 107.2.1 NEC 220 | | | | | | 4. SHOW CIRCUITS BEING FED FROM MAIN-BREAKER PANEL (IF | | | ANY). FBC 107.2.1 | | | | | | 5. SHOW AFCI PROTECTION FOR KITCHEN LIGHTING AND | | | KITCHEN COUNTERTOP RECEPTACLES. NEC 210.12 | | | | | | 6.SHOW AFCI PROTECTION FOR DISHWASHER AND DISPOSAL. NEC | | | 210.12 | | | | | | 7. SHOW GFCI PROTECTION FOR DISHWASHER. NEC 210.8D | | | | | | 8. RECEPTACLE REQUIRED ON ISLAND. RECEPTACLE SHOWN IS | | | NOT CODE COMPLIANT. OVERHANG OF COUNTERTOP IS MORE THAN | | | 6''. PLEASE SEE NEC 210.52C5 (EXCEPTION TO #5) | | | | | | 9. SMOKE ALARM REQUIRED OUTSIDE OF NEW BEDROOM. FBC | | | 314&315 | | | | | | 10. SHOW AFCI PROTECTION FOR RECEPTACLES IN | | | LAUNDRY/UTILITY ROOM. NEC 210.12 | | | | | | 11. NOTE ON PLANS STATES 50% OF ALL LIGHTING WILL BE | | | ENERGY EFFICIENT. PLEASE SEE FBC EC R404.1. MINIMUM IS | | | 75% | | | | | | PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | | FBC EC R404.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-15 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-15 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-10-01 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-08-21 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2019-09-25 15:40:34 | TO HM DESK | | | | | 2019-08-22 11:00:42 | R17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-13 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-29 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-08 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-08 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2019-05-08 14:50:42 | 109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT | | | FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | | OFFICE. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | | AIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-09-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-09-27 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-09-27 |
Time |
07:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-13 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-13 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2019-05-13 16:19:41 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE ENERGY SUBMITTAL. | | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | | STORIES. | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD | | | (MANDATORY). | | | THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY | | | PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND | | | CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT | | | BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. | | | FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)] | | | REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN | | | ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND | | | NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD | | | CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE | | | LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A | | | DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT | | | THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE | | | BUILDER ACCURATELY REFLECTS THE PLANS AND | | | SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE | | | FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE | | | FOUND IN APPENDIX C. | | | | | | 2. PROVIDE EQUIPMENT SPECIFICATIONS. | | | RE403.7.1EQUIPMENT SIZING. | | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT | | | SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE | | | LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING | | | EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR | | | GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR | | | THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS | | | INSTALLED. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-30 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-08-30 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-08-30 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2019-08-30 07:33:11 | 08/30/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-04-16 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-15 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2019-04-16 07:55:37 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE SANITARY ISOMETRIC HAS THE FOLLOWING CODE | | | VIOLATIONS. | | | A) THE FIXTURE BRANCH FOR THE WC SHALL BE MIN OF 3" PER | | | FBC PL 420.4 | | | B) THE FIXTURE BRANCHES FOR ALL THE FIXTURES IN THE | | | BATHROOM GROUP SHALL CONNECT TO THE HORIZONTAL WET VENT | | | INDIVIDUALLY THEY APPEAR TO BE CONNECTED TO THE | | | VERTICAL VENT FOR THE LAVATORY. PER FBC PL 912.1.1 | | | C) THE KITCHEN SINK SHALL NOT DISCHARGE TO THE BATHROOM | | | GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM | | | FROM ALL THE BATHROOM GROUP. PER FBC PL 912.1.1 | | | D) THE WASHING MACHINE IS MISSING FROM THE SANITARY | | | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2019-11-15 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-15 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-15 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2019-11-15 15:36:54 | PROVIDE PRODUCT APPROVALS WITH SUB PERMIT APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-08-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-28 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-28 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2019-08-28 15:39:51 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19031380 | | | REVIEWED: MAY 9, 2019 | | | 2ND REVIEW AUGUST 28, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) OK-ENERGY CALCS RECEIVED. IF NO CRAWL SPACE PROVIDED | | | THEY WILL NEED TO BE REVISED (SEE COMMENT 4). | | | | | | 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU | | | WOULD LIKE THEM DEFERED. | | | 2ND REVIEW - NONE RECEIVED. IF THESE ARE TO BE DEFERRED | | | SUBMITTAL THAN PLEASE INDICATE, OR PROVIDE PRODUCT | | | APPROVALS. | | | | | | 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR | | | FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE | | | IT DEFERED. | | | 2ND REVIEW - NONE RECEIVED. PROVIDE PRODUCT APPROVALS | | | OR INDICATE THAT IT WILL BE SUBMITTED WITH THE SUB | | | PERMIT APPLICATION. | | | | | | 4) 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS | | | SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF | | | THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS | | | NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO | | | STRUCTURE. | | | THE PLAN CALLS FOR SLAB ON COMPACTED FILL AND THE | | | SECTION SHOWS CRAWL SPACE WITH NO CONNECTION DETAIL. | | | PLEASE COORDINATE THE PLANS AND DETAILS TO MATCH FLOOR | | | CONDITION. IF IT IS CRAWLSPACE THAN SEE SECTIONS FBC | | | R408.1, 408.2 AND 408.4 | | | | | | NOTES: | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | 2ND REVIEW - NO COMMENT RESPONSE SHEET WAS SUBMITTED | | | AND NO CHANGES TO PLANS, SO SOME COMMENTS WERE NOT | | | ADDRESSED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-09 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-09 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2019-05-09 10:25:38 | SEE BUILDING COMMENT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2019-10-01 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2019-10-01 |
Time |
14:02 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-11 |
|
|
Cont ID |
|
| Sent By |
mcurz |
Date |
2019-04-11 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-04-11 |
Time |
09:28 |
Sent To |
PC |
|
| Notes |
| 2019-04-11 10:09:45 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) INDICATE THE SETBACK DIMENSION FROM THE PROPOSED | | | ADDITION TO ALL ADJACENT PROPERTY LINES. | | | 2) THE A/C IS BEING RELOCATED FROM THE REAR TO THE | | | SIDE? IF SO, PLEASE CHECK WITH BUILDING TO SEE IF A | | | SEPARATE PERMIT IS REQUIRED. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER | | | THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO | | | SCHEDULE AN APPOINTMENT. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|