Plan Review Details - Permit 19031380
Plan Review Stops For Permit 19031380
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 15:35 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 15:35 Sent To  
Notes
2019-11-15 15:38:41PROVISO:
 DEFERRED SUBMITTAL TO BE PROVIDED FOR WINDOW AND DOOR
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-09-25 Cont ID  
Sent By shill Date 2019-09-25 Time 15:59 Rev Time 0.00
Received By shill Date 2019-09-25 Time 15:59 Sent To  
Notes
2019-09-25 16:00:25PREVIOUS REVIEW WAS LOCKED AND CANNOT ADD NOTES
 BUILDING NOTES WERE PUT INTO THE ROOF REVIEW STOP:
  
 ****CORRECTIONS****
 W.P.B. PERMIT: 19031380
 REVIEWED: MAY 9, 2019
 2ND REVIEW AUGUST 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) OK-ENERGY CALCS RECEIVED. IF NO CRAWL SPACE PROVIDED
 THEY WILL NEED TO BE REVISED (SEE COMMENT 4).
  
 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
 2ND REVIEW - NONE RECEIVED. IF THESE ARE TO BE DEFERRED
 SUBMITTAL THAN PLEASE INDICATE, OR PROVIDE PRODUCT
 APPROVALS.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERED.
 2ND REVIEW - NONE RECEIVED. PROVIDE PRODUCT APPROVALS
 OR INDICATE THAT IT WILL BE SUBMITTED WITH THE SUB
 PERMIT APPLICATION.
  
 4) 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS
 SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF
 THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS
 NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO
 STRUCTURE.
 THE PLAN CALLS FOR SLAB ON COMPACTED FILL AND THE
 SECTION SHOWS CRAWL SPACE WITH NO CONNECTION DETAIL.
 PLEASE COORDINATE THE PLANS AND DETAILS TO MATCH FLOOR
 CONDITION. IF IT IS CRAWLSPACE THAN SEE SECTIONS FBC
 R408.1, 408.2 AND 408.4
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 2ND REVIEW - NO COMMENT RESPONSE SHEET WAS SUBMITTED
 AND NO CHANGES TO PLANS, SO SOME COMMENTS WERE NOT
 ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-28 Cont ID  
Sent By dbattles Date 2019-08-28 Time 13:40 Rev Time 0.00
Received By dbattles Date 2019-08-28 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 10:24 Rev Time 0.00
Received By dbattles Date 2019-05-08 Time 14:47 Sent To  
Notes
2019-05-09 10:25:07****CORRECTIONS****
 W.P.B. PERMIT: 19031380
 REVIEWED: MAY 9, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 401.2 FBC[RE] PROVIDE ENERGY CALCULATIONS TO MEET
 REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 - PLEASE SUPPLY ENERGY CALCULATIONS WITH CHECKLIST AND
 EPL CARD.
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERED.
  
 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS
 SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF
 THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS
 NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO
 STRUCTURE.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By ppetty Date 2019-08-27 Time 15:09 Rev Time 0.00
Received By ppetty Date 2019-08-27 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-20 Cont ID  
Sent By fgiaquin Date 2019-04-20 Time 08:16 Rev Time 0.00
Received By fgiaquin Date 2019-04-20 Time 07:30 Sent To  
Notes
2019-04-20 08:16:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW CONDUCTOR SIZE FROM RISER TO METER-CAN FBC
 107.2.1
  
 2. SHOW CONDUCTOR SIZE FROM METER-CAN TO MAIN-BREAKER
 PANEL. FBC 107.2.1
  
 3. PROVIDE ACCUATE LOAD CALCULATION. OCP FOR COOKTOP IS
 SHOWN AS 40AMPS BUT ONLY 1200 WATTS SHOWN IN LOAD
 CALCULATION. FBC 107.2.1 NEC 220
  
 4. SHOW CIRCUITS BEING FED FROM MAIN-BREAKER PANEL (IF
 ANY). FBC 107.2.1
  
 5. SHOW AFCI PROTECTION FOR KITCHEN LIGHTING AND
 KITCHEN COUNTERTOP RECEPTACLES. NEC 210.12
  
 6.SHOW AFCI PROTECTION FOR DISHWASHER AND DISPOSAL. NEC
 210.12
  
 7. SHOW GFCI PROTECTION FOR DISHWASHER. NEC 210.8D
  
 8. RECEPTACLE REQUIRED ON ISLAND. RECEPTACLE SHOWN IS
 NOT CODE COMPLIANT. OVERHANG OF COUNTERTOP IS MORE THAN
 6''. PLEASE SEE NEC 210.52C5 (EXCEPTION TO #5)
  
 9. SMOKE ALARM REQUIRED OUTSIDE OF NEW BEDROOM. FBC
 314&315
  
 10. SHOW AFCI PROTECTION FOR RECEPTACLES IN
 LAUNDRY/UTILITY ROOM. NEC 210.12
  
 11. NOTE ON PLANS STATES 50% OF ALL LIGHTING WILL BE
 ENERGY EFFICIENT. PLEASE SEE FBC EC R404.1. MINIMUM IS
 75%
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 15:36 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-01 Cont ID  
Sent By cpuell Date 2019-10-01 Time 17:05 Rev Time 0.00
Received By cpuell Date 2019-08-21 Time 11:00 Sent To  
Notes
2019-09-25 15:40:34TO HM DESK
  
2019-08-22 11:00:42R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By cthroop Date 2019-05-13 Time 16:19 Rev Time 0.00
Received By cthroop Date 2019-03-29 Time 13:37 Sent To  
Notes
2019-04-01 13:38:04R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-08 Cont ID  
Sent By dbattles Date 2019-05-08 Time 14:52 Rev Time 0.00
Received By dbattles Date 2019-05-08 Time 14:47 Sent To  
Notes
2019-05-08 14:50:42109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By cthroop Date 2019-09-27 Time 09:33 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By cthroop Date 2019-05-13 Time 16:08 Rev Time 0.00
Received By cthroop Date 2019-05-13 Time 16:08 Sent To  
Notes
2019-05-13 16:19:41MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 2. PROVIDE EQUIPMENT SPECIFICATIONS.
 RE403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By lcrespo Date 2019-08-30 Time 07:32 Rev Time 0.00
Received By lcrespo Date 2019-08-30 Time 06:49 Sent To  
Notes
2019-08-30 07:33:1108/30/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By gjohnson Date 2019-04-16 Time 07:55 Rev Time 0.00
Received By gjohnson Date 2019-04-15 Time 13:13 Sent To  
Notes
2019-04-16 07:55:371ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY ISOMETRIC HAS THE FOLLOWING CODE
 VIOLATIONS.
 A) THE FIXTURE BRANCH FOR THE WC SHALL BE MIN OF 3" PER
 FBC PL 420.4
 B) THE FIXTURE BRANCHES FOR ALL THE FIXTURES IN THE
 BATHROOM GROUP SHALL CONNECT TO THE HORIZONTAL WET VENT
 INDIVIDUALLY THEY APPEAR TO BE CONNECTED TO THE
 VERTICAL VENT FOR THE LAVATORY. PER FBC PL 912.1.1
 C) THE KITCHEN SINK SHALL NOT DISCHARGE TO THE BATHROOM
 GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM
 FROM ALL THE BATHROOM GROUP. PER FBC PL 912.1.1
 D) THE WASHING MACHINE IS MISSING FROM THE SANITARY
 ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2019-11-15 Cont ID  
Sent By dbattles Date 2019-11-15 Time 15:36 Rev Time 0.00
Received By dbattles Date 2019-11-15 Time 15:36 Sent To  
Notes
2019-11-15 15:36:54PROVIDE PRODUCT APPROVALS WITH SUB PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-08-28 Cont ID  
Sent By dbattles Date 2019-08-28 Time 15:32 Rev Time 0.00
Received By dbattles Date 2019-08-28 Time 15:32 Sent To  
Notes
2019-08-28 15:39:51****CORRECTIONS****
 W.P.B. PERMIT: 19031380
 REVIEWED: MAY 9, 2019
 2ND REVIEW AUGUST 28, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) OK-ENERGY CALCS RECEIVED. IF NO CRAWL SPACE PROVIDED
 THEY WILL NEED TO BE REVISED (SEE COMMENT 4).
  
 2) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, AND DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
 2ND REVIEW - NONE RECEIVED. IF THESE ARE TO BE DEFERRED
 SUBMITTAL THAN PLEASE INDICATE, OR PROVIDE PRODUCT
 APPROVALS.
  
 3) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 FLAT ROOF AT ADDITION, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERED.
 2ND REVIEW - NONE RECEIVED. PROVIDE PRODUCT APPROVALS
 OR INDICATE THAT IT WILL BE SUBMITTED WITH THE SUB
 PERMIT APPLICATION.
  
 4) 107.4.5 FBC[AMENDED] THE SECTION LABELED A/S2 SHOWS
 SLAB ON GRADE AND A SPACE BETWEEN. PLEASE CLARIFY IF
 THERE IS A CRAWL SPACE, OR IF THE SLAB IS ON FILL AS
 NOTED. IF CRAWL SPACE SHOW HOW FLOORING IS CONNECTED TO
 STRUCTURE.
 THE PLAN CALLS FOR SLAB ON COMPACTED FILL AND THE
 SECTION SHOWS CRAWL SPACE WITH NO CONNECTION DETAIL.
 PLEASE COORDINATE THE PLANS AND DETAILS TO MATCH FLOOR
 CONDITION. IF IT IS CRAWLSPACE THAN SEE SECTIONS FBC
 R408.1, 408.2 AND 408.4
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 2ND REVIEW - NO COMMENT RESPONSE SHEET WAS SUBMITTED
 AND NO CHANGES TO PLANS, SO SOME COMMENTS WERE NOT
 ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By dbattles Date 2019-05-09 Time 10:25 Rev Time 0.00
Received By dbattles Date 2019-05-09 Time 10:25 Sent To  
Notes
2019-05-09 10:25:38SEE BUILDING COMMENT.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-01 Cont ID  
Sent By rfalcone Date 2019-10-01 Time 14:03 Rev Time 0.00
Received By rfalcone Date 2019-10-01 Time 14:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-11 Cont ID  
Sent By mcurz Date 2019-04-11 Time 10:09 Rev Time 0.00
Received By mcruz Date 2019-04-11 Time 09:28 Sent To PC
Notes
2019-04-11 10:09:45ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) INDICATE THE SETBACK DIMENSION FROM THE PROPOSED
 ADDITION TO ALL ADJACENT PROPERTY LINES.
 2) THE A/C IS BEING RELOCATED FROM THE REAR TO THE
 SIDE? IF SO, PLEASE CHECK WITH BUILDING TO SEE IF A
 SEPARATE PERMIT IS REQUIRED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy