| Plan Review Stops For Permit 19031379 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-24 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-20 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-28 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2019-05-30 08:11:52 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | 1. PROVIDE SITE DRAINAGE PLAN. 2ND REQUEST. | | | FBC R401.3 | | | | | | DRAINAGE PLAN C-1 MISSING EXISTING GRADES AND PROPOSED | | | GRADES. | | | | | | 2. PROVIDE FINISH FLOOR ELEVATION. | | | R403.1.7.3 FOUNDATION ELEVATION. | | | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION | | | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER | | | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED | | | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 | | | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO | | | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN | | | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF | | | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT | | | ALL LOCATIONS ON THE SITE. | | | | | | FINISH FLOOR ELEVATION ON PLAN PAGE C-1 (DRAINAGE PLAN) | | | SHOWS 13.88 FEET. | | | FINISH FLOOR ELEVATION ON PROPOSED SURVEY SHOWS 13.00 | | | FEET. | | | PLEASE CLARIFY. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-15 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-10 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2019-04-15 15:56:42 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE SITE DRAINAGE PLAN. | | | FBC R401.3 SITE DRAINAGE | | | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING | | | COMPLIANCE WITH FBC R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER | | | PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 | | | FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE | | | DRAINAGE AWAY FROM THE STRUCTURE. | | | IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING | | | FOUNDATION SHALL BE SLOPED A MINIMUM OF | | | 2 PERCENT AWAY FROM THE BUILDING. | | | | | | 2. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | 3. ROOFING PERMIT REQUIRED. FBC 105 PERMITS | | | | | | 4. PROVIDE WINDOW AND DOOR SCHEDULE. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5. PROVIDE DESIGN PRESSURES FOR WINDOW AND DOOR | | | OPENINGS. | | | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. | | | | | | R301.2.1 WIND DESIGN CRITERIA. | | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | | FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF | | | THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND | | | DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1. | | | WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL | | | MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING, | | | THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH | | | PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE | | | WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR | | | HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED | | | TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR | | | WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR | | | WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN | | | GARAGE DOORS). | | | | | | 6. SHOW LOCATION AND TYPE OF WATER HEATER ON PLAN. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-16 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-10 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2019-04-16 07:02:31 | ELECTRICAL PLAN REVIEW - CABANA | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | PLEASE REVIEW ELECTRICAL PLAN REVIEW COMMENTS FOR THE | | | MAIN HOUSE AND CABANA AT 19031377. | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-30 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2019-05-30 08:03:06 | GAS PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | | EDITION | | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | GAS PLAN REVIEW | | | | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | | WATER HEATER INSTALLATION. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-06-24 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-10 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-31 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-05-24 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-04-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-04-19 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-29 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2019-04-18 14:25:56 | CONVERTED TO DIGITAL | | | | | | | | | | | 2019-04-01 13:31:12 | R27 | | | **TRAVELLING TOGETHER - 19031377 & 19031379** |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-25 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2019-06-29 10:28:56 | 6/29/19 IMPACT FEES PAID & PROJECTDOX STAMPED - MU | | | 2019-020101 | | 2019-06-25 13:52:08 | 6/25/19 SENT EMAIL TO IMPACT OFFICE. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-15 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-10 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2019-04-15 15:57:35 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-15 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-10 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2019-04-15 16:02:19 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SPECIFY EQUIPMENT TO BE INSTALLED. LIST EQUIPMENT ON | | | ENERGY SUBMITTAL AND PLANS. | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 2. PROVIDE EQUIPMENT SIZING. | | | M1401.3 EQUIPMENT AND APPLIANCE SIZING. | | | HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE | | | SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER | | | APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | | | | 3. PROVIDE DETAIL FOR C/U ANCHORAGE. | | | M1307.2 ANCHORAGE OF APPLIANCES. | | | APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE | | | FASTENED OR ANCHORED IN AN APPROVED MANNER. IN SEISMIC | | | DESIGN CATEGORIES D0, D1 AND D2, AND IN TOWNHOUSES IN | | | SEISMIC DESIGN CATEGORY C, WATER HEATERS AND THERMAL | | | STORAGE UNITS SHALL BE ANCHORED OR STRAPPED TO RESIST | | | HORIZONTAL DISPLACEMENT CAUSED BY EARTHQUAKE MOTION IN | | | ACCORDANCE WITH ONE OF THE FOLLOWING: | | | 1. 1. ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO | | | RESIST A HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE | | | OPERATING WEIGHT OF THE WATER HEATER STORAGE TANK, | | | ACTING IN ANY HORIZONTAL DIRECTION. STRAPPING SHALL BE | | | AT POINTS WITHIN THE UPPER ONE-THIRD AND LOVER | | | ONE-THIRD OF THE APPLIANCE?S VERTICAL DIMENSIONS. AT | | | THE LOWER POINT, THE STRAPPING SHALL MAINTAIN A MINIMUM | | | DISTANCE OF 4 INCHES (102 MM) ABOVE THE CONTROLS. | | | 2. 2. THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE | | | WITH THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS. | | | | | | 4. PROVIDE DETAIL FOR LOCKING SERVICE PORTS. | | | M1411.8 LOCKING ACCESS PORT CAPS. | | | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL | | | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR | | | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED | | | ACCESS. | | | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE | | | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING | | | UNIT CABINET. | | | | | | 5. PROVIDE CFM OF EXHAUST FANS. | | | 6. PROVIDE DETAIL OF EXHAUST FAN DISCHARGE TO EXTERIOR. | | | | | | MINI-SPLIT SHALL PROVIDE HEAT. | | | DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES - | | | WINTER | | | | | | FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION | | | R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN | | | TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), | | | EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING | | | FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF | | | NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) | | | ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS | | | IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE | | | INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS | | | SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS | | | SECTION. | | | TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR | | | DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE | | | COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-30 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-04-09 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-04-09 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2019-04-09 13:39:48 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL | | | MANUAL | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW: | | | PLUMBING COMMENTS: DENIED | | | | | | 1. SP SANITARY RISER DIAGRAM AND 1B FLOOR PLAN | | | A. PER FBC PL 701.3 AND FBC RES P2601.1, THE SANITARY | | | BUILDING DRAIN SHALL CONNECT TO A COMMON BUILDING SEWER | | | FOR ITSELF AND THE MAIN HOUSE AND SHALL NOT DISCHARGE | | | THROUGH THE MAIN HOUSE BUILDING DRAIN. | | | B. GUEST HOUSE FLOOR PLAN SHOWS A SINK. SANITARY RISER | | | DOES NOT SHOW THE SINK. PER WPB FBC 107.2.1, SHOW SINK | | | ON SANITARY RISER AND CONNECT DOWNSTREAM OF BATHROOM | | | GROUP PER FBC RES P3108.1. | | | 2.PER WPB FBC 107.2.1, SHOW HOW HOT WATER SHALL BE | | | SUPPLIED IN COMPLIANCE WITH FBC PL 607.1 AND FBC RES | | | P2601.1 | | | | | | | | | END OF COMMENTS | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-15 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-10 |
Time |
13:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-07-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-07-01 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-06-20 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2019-06-24 09:13:39 | HARD COPY OF PLANS WITH ORIGINAL SIGNATURE AND SEAL | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-05-30 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-05-30 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2019-05-30 08:23:56 | HARD COPY OF PLANS WITH ORIGINAL SIGNATURES AND SEALS | | | REQUIRED PRIOR TO PERMITTING. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-15 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-15 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2019-04-15 15:58:45 | 1. UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL WITH | | | SIGNATURE OF DESIGNER AS APPLICABLE; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | 2. HARD COPY OF PLANS WITH ORIGINAL SIGNATURES AND | | | SEALS WILL BE REQUIRED AFTER ALL REVIEWS HAVE PASSED. | | | | | | | | 2019-04-10 13:13:15 | 4/10/19 HARD COPIES WITH CTHROOP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2019-06-25 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-06-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-06-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-25 09:59:18 | ******ZONING PROVISO******* | | | | | | PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY, THE | | | FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMT, WHICH INCLUDED A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | LANDSCAPE INSPECTION. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-06-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-20 09:12:41 | *****************************ZONING REVIEW FAILED | | | (REPEAT COMMENT)********************************* | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-05-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-05-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-05-31 10:25:53 | *****************************ZONING REVIEW FAILED | | | (REPEAT COMMENTS) ********************************* | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-04-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2019-04-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-04-19 11:23:02 | *****************************ZONING REVIEW | | | FAILED********************************* | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | 2019-04-10 13:10:16 | SUBMITTAL HAS BEEN CHANGED FROM PAPER TO DIGITAL. CT |
|
|