Plan Review Details - Permit 19031377
Plan Review Stops For Permit 19031377
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 09:11 Rev Time 0.00
Received By cthroop Date 2019-06-20 Time 17:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 08:05 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 11:23 Sent To  
Notes
2019-05-30 08:11:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE SITE DRAINAGE PLAN. 2ND REQUEST.
 FBC R401.3
  
 DRAINAGE PLAN C-1 MISSING EXISTING GRADES AND PROPOSED
 GRADES.
  
 2. PROVIDE FINISH FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 FINISH FLOOR ELEVATION ON PLAN PAGE C-1 (DRAINAGE PLAN)
 SHOWS 13.88 FEET.
 FINISH FLOOR ELEVATION ON PROPOSED SURVEY SHOWS 13.00
 FEET.
 PLEASE CLARIFY.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By cthroop Date 2019-04-15 Time 14:52 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 13:07 Sent To  
Notes
2019-04-15 14:59:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 2. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 3. ROOFING PERMIT REQUIRED. FBC 105 PERMITS
  
 4. PROVIDE WINDOW AND DOOR SCHEDULE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PROVIDE DESIGN PRESSURES FOR WINDOW AND DOOR
 OPENINGS.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. SHOW LOCATION AND TYPE OF WATER HEATER ON PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 08:12 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 11:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By cthroop Date 2019-04-16 Time 07:03 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 13:07 Sent To  
Notes
2019-04-16 07:14:30BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING REVIEW COMMENTS APPLY TO THE MAIN HOUSE
 AND CABANA. A NOTE HAS BEEN PROVIDED WHERE THE COMMENT
 APPLIES ONLY TO ONE STRUCTURE.
  
 1. PROVIDE AIC CALCULATIONS
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE AIC RATING.
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 3. PROVIDE ACCURATE LOAD CALCULATIONS FOR EACH PANEL
 SEPERATELY, INCLUDING ALL LOADS. NEC 220; FBC RE
 E3602.2
 3A. MAIN HOUSE CALCULATIONS -
 3B. CABANA CALCULATIONS -
 3C. COMBINATION CALCULATIONS - PROVIDED
  
 4. HOUSE ONLY COMMENT - PLAN INDICATES A FPL METER
 COMBO AND A 150 AMP PANEL LOCATED IN FOYER. RISER
 DIAGRAHM INDICATES A SEPERATE METER CAN WITH A 200 AMP
 PANEL WITH A MCB. IF METER COMBO IS UTILIZED THEN THE
 DETAIL SHOWING A 2 INCH CONDUIT WITH 3-#3/0 CONDUCTORS
 WITH A #6 GRND. ( THIS WOULD BE AN INTERNAL CONNECTION)
 AND THE 150 AMP PANEL IN THE FOYER NEEDS TO BE REMOVED.
 PLEASE CLARIFY.
  
 5. INDICATE ON PLAN THE TYPE OF GROUND TO BE USED AT
 EACH STRUCTURE. (I.E. GROUND RODS, CONCRETE ENCASED
 STEEL RE-INFORCING, WATER PIPES, ETC.)
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
 6. IDENTIFY INTERSYSTEM BONDING TERMINAL AT EACH
 SERVICE.
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 7. GROUNDING ELECTRODE SHALL BE SIZED PER TABLE
 E3603.4. THIS IS IN REFERENCE TO THE DETAIL SHOWING
 SEPERATE METER AND SERVICE. #6 GROUND WIRE IS
 UNDERSIZED FOR 3-#3/0 UNGROUNDED CONDUCTORS.
  
 8. CABANA ONLY COMMENT - PROVIDE SERVICE OUTLET FOR
 MINI-SPLIT OUTDOOR C/U UNIT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 9. HOUSE ONLY COMMENT - LAUNDRY ROOM OUTLET SHALL BE
 GFCI PROTECTED.
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)] E3902.16.
  
 10. PROVIDE ARC FAULT CIRCUT PROTECTION PER E3902.16
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 11. PROVIDE THE FOLLOWING STATEMENT ON PLAN FOR
 PERMENTELY INSTALLED LUMINAIRES:
 PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 12. EXHAUST FAN SYMBOL MISSING FROM LEGEND. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 13. STATE CFM FOR EACH EXHAUST FANS. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 09:41 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 09:38 Sent To  
Notes
2019-05-28 09:45:55GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 GAS PLAN REVIEW
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 WATER HEATER INSTALLATION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-10 Cont ID  
Sent By cthroop Date 2019-07-10 Time 16:34 Rev Time 0.00
Received By cthroop Date 2019-07-10 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 09:12 Rev Time 0.00
Received By cthroop Date 2019-06-10 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-03 Cont ID  
Sent By shill Date 2019-05-31 Time 06:08 Rev Time 0.00
Received By shill Date 2019-05-24 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-22 Cont ID  
Sent By shill Date 2019-04-19 Time 08:06 Rev Time 0.00
Received By shill Date 2019-03-29 Time 13:30 Sent To  
Notes
2019-04-18 06:43:504/15 CONVERTED TO DIGITAL IN ORDER TO FACILITATE FASTER
 REVIEWS
  
  
  
  
2019-04-01 13:30:51R27
 **TRAVELLING TOGETHER - 19031377 & 19031379**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-29 Cont ID  
Sent By cpuell Date 2019-06-29 Time 10:12 Rev Time 0.00
Received By cpuell Date 2019-06-25 Time 13:48 Sent To  
Notes
2019-06-29 10:13:216/29/19 IMPACT FEES PAID & PROJECTDOX STAMPED - MU
 2019-020101
2019-06-25 13:51:546/25/19 SENT EMAIL TO IMPACT OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By cthroop Date 2019-04-15 Time 14:59 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 13:07 Sent To  
Notes
2019-04-15 15:00:54PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 09:33 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 11:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By cthroop Date 2019-04-15 Time 15:07 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 13:08 Sent To  
Notes
2019-04-15 15:20:12MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SPECIFY EQUIPMENT TO BE INSTALLED. LIST EQUIPMENT ON
 ENERGY SUBMITTAL AND PLANS.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. PROVIDE EQUIPMENT SIZING.
 M1401.3 EQUIPMENT AND APPLIANCE SIZING.
 HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE
 SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER
 APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
 3. PROVIDE DETAIL FOR C/U ANCHORAGE.
 M1307.2 ANCHORAGE OF APPLIANCES.
 APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
 FASTENED OR ANCHORED IN AN APPROVED MANNER. IN SEISMIC
 DESIGN CATEGORIES D0, D1 AND D2, AND IN TOWNHOUSES IN
 SEISMIC DESIGN CATEGORY C, WATER HEATERS AND THERMAL
 STORAGE UNITS SHALL BE ANCHORED OR STRAPPED TO RESIST
 HORIZONTAL DISPLACEMENT CAUSED BY EARTHQUAKE MOTION IN
 ACCORDANCE WITH ONE OF THE FOLLOWING:
 1. 1. ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO
 RESIST A HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE
 OPERATING WEIGHT OF THE WATER HEATER STORAGE TANK,
 ACTING IN ANY HORIZONTAL DIRECTION. STRAPPING SHALL BE
 AT POINTS WITHIN THE UPPER ONE-THIRD AND LOVER
 ONE-THIRD OF THE APPLIANCE?S VERTICAL DIMENSIONS. AT
 THE LOWER POINT, THE STRAPPING SHALL MAINTAIN A MINIMUM
 DISTANCE OF 4 INCHES (102 MM) ABOVE THE CONTROLS.
 2. 2. THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE
 WITH THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS.
  
 4. PROVIDE DETAIL FOR LOCKING SERVICE PORTS.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 5. PROVIDE CFM OF EXHAUST FANS.
 6. PROVIDE DETAIL OF EXHAUST FAN DISCHARGE TO EXTERIOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By cthroop Date 2019-05-30 Time 08:13 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By jesmith Date 2019-04-09 Time 14:08 Rev Time 0.00
Received By jesmith Date 2019-04-09 Time 13:40 Sent To  
Notes
2019-04-09 14:07:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW:
 A GAS METER IS SHOWN ON 5A. A SEPARATE GAS PERMIT IS
 REQUIRED.A GAS PLAN AND PERMIT APPLICATION SHALL BE
 PROVIDED FOR REVIEW.
  
 PLUMBING COMMENTS: DENIED
  
 1. SP SANITARY RISER DIAGRAM
 A. PER FBC PL 701.3 AND FBC RES P2601.1, THE MAIN HOUSE
 BUILDING DRAIN SHALL NOT RECIEVE THE DISCHARGE OF THE
 GUEST HOUSE. THE GUEST HOUSE SHALL CONNECT TO A COMMON
 BUILDING SEWER FOR ITSELF AND THE MAIN HOUSE.
 B. DOUBLE SINK SHALL CONNECT DOWNSTREAM OF BATHROOM
 GROUP PER FBC RES P3108.1.
 C. BACK TO BACK SHOWER FIXTURE DRAINS SHALL EACH
 CONNECT INDEPENDENTLY TO THE HORIZONTAL WET VENT PER
 FBC RES P3108.1.
 2.PER WPB FBC 107.2.1, SHOW HOW HOT WATER SHALL BE
 SUPPLIED IN COMPLIANCE WITH FBC PL 607.1 AND FBC RES
 P2601.1
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-04-15 Cont ID  
Sent By cthroop Date 2019-04-15 Time 15:01 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-07-10 Cont ID  
Sent By cthroop Date 2019-07-10 Time 16:33 Rev Time 0.00
Received By cthroop Date 2019-07-10 Time 16:27 Sent To  
Notes
2019-07-10 09:35:217/10/19 ROUTED TO HARD COPIES TO CTHROOP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-06-26 Cont ID  
Sent By cthroop Date 2019-06-26 Time 12:59 Rev Time 0.00
Received By cthroop Date 2019-06-20 Time 17:05 Sent To  
Notes
2019-06-24 09:11:31HARD COPY OF PLANS WITH ORIGINAL SIGNATURE AND SEAL
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-05-28 Cont ID  
Sent By cthroop Date 2019-05-28 Time 09:17 Rev Time 0.00
Received By cthroop Date 2019-05-24 Time 11:24 Sent To  
Notes
2019-05-28 09:18:04HARD COPY OF PLANS WITH SIGNATURES AND SEALS REQUIRED
 PRIOR TO PERMIT. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By cthroop Date 2019-04-15 Time 15:01 Rev Time 0.00
Received By cthroop Date 2019-04-15 Time 11:22 Sent To  
Notes
2019-04-15 15:03:251. UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL WITH
 SIGNATURE OF DESIGNER AS APPLICABLE; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT.
  
 2. HARD COPY OF PLANS WITH ORIGINAL SIGNATURES AND
 SEALS WILL BE REQUIRED AFTER ALL REVIEWS HAVE PASSED.
  
  
2019-04-10 13:12:454/10/19 HARD COPIES WITH CTHROOP

Review Stop Z ZONING
Rev No 4 Status P Date 2019-06-25 Cont ID  
Sent By awooten Date 2019-06-25 Time   Rev Time 0.00
Received By awooten Date 2019-06-25 Time   Sent To  
Notes
2019-06-25 10:21:30******ZONING PROVISO*******
  
 PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY, THE
 FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMT, WHICH INCLUDED A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2019-06-20 Cont ID  
Sent By awooten Date 2019-06-20 Time   Rev Time 0.00
Received By awooten Date 2019-06-20 Time   Sent To  
Notes
2019-06-20 09:31:22**************************************ZONING REVIEW
 FAILED (REPEAT COMMENTS) ************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By awooten Date 2019-05-31 Time   Rev Time 0.00
Received By awooten Date 2019-05-31 Time   Sent To  
Notes
2019-05-31 10:24:22**************************************ZONING REVIEW
 FAILED (REPEAT COMMENTS) ************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A
 SEPARATE PERMIT.
  
 THE SIDE SETBACKS ARE NOT CONSISTENT ON BOUNDARY SURVEY
 AND SITE PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By awooten Date 2019-04-19 Time   Rev Time 0.00
Received By awooten Date 2019-04-19 Time 13:08 Sent To  
Notes
2019-04-19 11:20:43**************************************ZONING REVIEW
 FAILED************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A
 SEPARATE PERMIT.
  
 THE SIDE SETBACKS ARE NOT CONSISTENT ON BOUNDARY SURVEY
 AND SITE PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
2019-04-10 13:08:53SUBMITTAL HAS BEEN CHANGED FROM PAPER TO DIGITAL. CT