Plan Review Details - Permit 19031344
Plan Review Stops For Permit 19031344
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By shill Date 2019-05-01 Time 16:56 Rev Time 0.00
Received By shill Date 2019-05-01 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2019-06-10 Cont ID  
Sent By jpearson Date 2019-06-10 Time 14:42 Rev Time 0.00
Received By jpearson Date 2019-06-10 Time 14:42 Sent To  
Notes
2019-06-10 14:42:11ELECTRICAL UNDER PERMIT 19050284

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-07 Cont ID  
Sent By jpearson Date 2019-06-07 Time 09:38 Rev Time 0.00
Received By jpearson Date 2019-06-07 Time 09:38 Sent To P
Notes
2019-06-07 09:38:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT THE PLAN SUBMITTED STATES THER EIS
 ELECTRICAL WORK. THE PREVIOUS COMMENT BELOW HAVE NOT
 BEEN ADDRESSED. PROVIDE CORRECTIONS AS NOTED BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1,
 107.3.5; FS 471, 481
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. INDICATE WHICH BREAKERS ARE BEING REPLACED.
 NEC 210.8, 210.12, 210.19, 210.20, 215.5, 408.4; WPB
 FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 4. PER NEC: INTEGRITY OF ELECTRICAL EQUIPMENT AND
 CONNECTIONS. INTERNAL PARTS OF ELECTRICAL EQUIPMENT,
 INCLUDING BUSBARS, WIRING TERMINALS, INSULATORS, AND
 OTHER SURFACES, SHALL NOT BE DAMAGED OR CONTAMINATED BY
 FOREIGN MATERIALS SUCH AS PAINT, PLASTER, CLEANERS,
 ABRASIVES, OR CORROSIVE RESIDUES. THERE SHALL BE NO
 DAMAGED PARTS THAT MAY ADVERSELY AFFECT SAFE OPERATION
 OR MECHANICAL STRENGTH OF THE EQUIPMENT SUCH AS PARTS
 THAT ARE BROKEN; BENT; CUT; OR DETERIORATED BY
 CORROSION, CHEMICAL ACTION, OR OVERHEATING. ELECTRICAL
 PANEL SHOULD BE REPLACED. PROVIDE CORRECTION. NEC
 110.12(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jpearson Date 2019-04-25 Time 07:39 Rev Time 0.00
Received By jpearson Date 2019-04-25 Time 07:39 Sent To  
Notes
2019-04-25 07:39:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1,
 107.3.5; FS 471, 481
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. INDICATE WHICH BREAKERS ARE BEING REPLACED.
 NEC 210.8, 210.12, 210.19, 210.20, 215.5, 408.4; WPB
 FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 4. PER NEC: INTEGRITY OF ELECTRICAL EQUIPMENT AND
 CONNECTIONS. INTERNAL PARTS OF ELECTRICAL EQUIPMENT,
 INCLUDING BUSBARS, WIRING TERMINALS, INSULATORS, AND
 OTHER SURFACES, SHALL NOT BE DAMAGED OR CONTAMINATED BY
 FOREIGN MATERIALS SUCH AS PAINT, PLASTER, CLEANERS,
 ABRASIVES, OR CORROSIVE RESIDUES. THERE SHALL BE NO
 DAMAGED PARTS THAT MAY ADVERSELY AFFECT SAFE OPERATION
 OR MECHANICAL STRENGTH OF THE EQUIPMENT SUCH AS PARTS
 THAT ARE BROKEN; BENT; CUT; OR DETERIORATED BY
 CORROSION, CHEMICAL ACTION, OR OVERHEATING. ELECTRICAL
 PANEL SHOULD BE REPLACED. PROVIDE CORRECTION. NEC
 110.12(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 06:28 Rev Time 0.00
Received By thunt Date 2019-06-03 Time 15:05 Sent To  
Notes
2019-06-04 15:06:00RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-03 Cont ID  
Sent By hmoser Date 2019-05-03 Time 08:47 Rev Time 0.00
Received By hmoser Date 2019-04-09 Time 15:49 Sent To  
Notes
2019-04-10 15:49:39R15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-05-03 Cont ID  
Sent By hmoser Date 2019-05-03 Time 08:43 Rev Time 0.00
Received By hmoser Date 2019-05-03 Time 08:43 Sent To I
Notes
2019-05-03 08:46:56NO MECHANICAL WORK REQUIRED, PER PLAN AND APPLICATION
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 06:28 Rev Time 0.00
Received By thunt Date 2019-06-10 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 14:51 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 14:50 Sent To  
Notes
2019-04-16 14:53:03PLUMBING 1ST REVIEW**DENIED**NO INFORMATION REGRADING
 PLUMBING WAS PROVIDE TO REVIEW
  
 PROVIDE LOCATION OF WATER HEATER AND SUPPLY
 MANUFACTURES INSTALLATION MANUAL/ SPEC. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  