Plan Review Details - Permit 19031334
Plan Review Stops For Permit 19031334
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 10:11 Rev Time 0.00
Received By jduprey Date 2019-04-30 Time 09:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By jleahy Date 2019-04-26 Time 07:33 Rev Time 0.00
Received By jleahy Date 2019-04-26 Time 07:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 16:11 Rev Time 0.00
Received By thunt Date 2019-05-22 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-05-20 Cont ID  
Sent By thunt Date 2019-05-20 Time 10:21 Rev Time 0.00
Received By thunt Date 2019-05-20 Time 10:21 Sent To  
Notes
2019-05-20 10:21:45GAS 2NDREVIEW**DENIED**
  
  
 1) OK
  
 2) 2ND REQUEST**YOU PLAN HAS L.P TANK SUBMITTAL
 INFORMATION BUT AN EXISTING TANK ALREADY EXIST. ARE YOU
 REPLACE THE EXISTING 500 L.P TANK? PLEASE CLARIFY. FBC
 107.2.1
  
 3) OK
  
 4) NEW COMMENT: NEWLY SUBMITTED L.P TANK TIE DOWN
 DOCUMENTS CONTAIN COPIES OF (P.E) W.C FARISH SIGNATURE
 . ANY DOCUMENT THAT BEAR'S A P.E SEAL MUST CONTAIN A
 WET SIGNATURE. FAC 61G15-23.001
  
 5) REMOVE OLD ISOMETRIC DRAWING FROM THE PACKETS. FBC
 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By thunt Date 2019-04-04 Time 15:07 Rev Time 0.00
Received By thunt Date 2019-04-04 Time 15:07 Sent To  
Notes
2019-04-04 15:07:05GAS 1ST REVIEW**DENIED**
  
 YOUR PLAN CALLS OUT A GAS POOL HEATER WAS REMOVED AND
 ELC ONE INSTALLED IN ITS PLACE WITH NO OTHER GAS
 APPLIANCE'S IN HOME. CITY RECORDS (PERMIT#07040709)
 SHOW EXISTING HWH, FIRE PLACE, AND FUTURE GRILL AND
 RANGE.
  
  
 1) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2) YOU PLAN HAS L.P TANK SUBMITTAL INFORMATION BUT AN
 EXISTING TANK ALREADY EXIST. ARE YOU REPLACE THE
 EXISTING 500 L.P TANK? PLEASE CLARIFY. FBC 107.2.1
  
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM INCLUDING FUTURE FIXTURES. REFER
 TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21).
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 16:11 Rev Time 0.00
Received By thunt Date 2019-05-21 Time 13:49 Sent To  
Notes
2019-05-22 13:49:32RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-20 Cont ID  
Sent By thunt Date 2019-05-20 Time 10:21 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 10:59 Sent To  
Notes
2019-05-17 10:59:12RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 10:11 Rev Time 0.00
Received By jduprey Date 2019-03-28 Time 11:39 Sent To  
Notes
2019-03-29 11:39:27ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-03 Cont ID  
Sent By mcruz Date 2019-04-03 Time 13:00 Rev Time 0.00
Received By mcruz Date 2019-04-03 Time 12:59 Sent To  
Notes
***NONE***