| 2019-05-07 08:29:16 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19031293 |
| | ADD: 901 45TH ST. |
| | CONT: WESTBROOKE CORP. |
| | TEL: 561-395-4126 |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 07/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 023-S000 STRUCTURAL SHEET SECTION AT CURB |
| | SUPPORT. THE DETAIL INDICATES THAT NEWLY PREFABRICATED |
| | NOA RATED METAL CURB. PLEASE SUBMIT THE PRODUCT |
| | APPROVAL FOR ROOF CURBS. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF |
| | TOP FANS, INTAKE AND EXHAUST AND NEW TECHNOLOGIES? |
| | |
| | 2A) SHEET 023-S000 STRUCTURAL SHEET SECTION AT CURB |
| | SUPPORT. THE DETAIL INDICATES A NEW EXHAUST ROOF FAN. |
| | PLEASE SUBMIT THE PRODUCT APPROVAL FOR THE ROOF TOP |
| | EXHAUST FAN. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF |
| | TOP FANS, INTAKE AND EXHAUST AND NEW TECHNOLOGIES? |
| | |
| | 2B) THE DETAIL INDICATES A NEW ROOF TOP EXHAUST ROOF |
| | FAN. THE NOTE ON THE PLAN INDICATES ATTACH UNIT TO CURB |
| | PER UNITS MANUFACTURED RECOMMENDATIONS. THE PROVIDED |
| | POSITIVE & NEGATIVE PRESSURES TO SECURE THE ROOF TOP |
| | FAN TO THE CURB INDICATE THE PRESSURES, BUT NOT THE |
| | MEAN ROOF HEIGHT AND ROOF ZONE, THESE PRESSURES ARE |
| | ASSOCIATED WITH. |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 2017 FBC-M- 301.15 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | 2C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 3A) THE STRUCTURAL PLAN 024-S000 SHOWS A SERIES OF NEW |
| | SLAB PENETRATIONS BUT THERE IS NO INDICATION ON THE |
| | PLAN, IF REINFORCING AROUND THE NEW OPENING IS |
| | REQUIRED? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3B) THE STRUCTURAL PLAN 024-S000 SHOWS A SERIES OF NEW |
| | ROOF TOP STEEL RAISED PLATFORMS. SECTION 1 SHOWS AN |
| | ELEVATION VIEW OF THE PLATFORM BUT THERE IS NO WELD |
| | INFORMATION HOW THE STRUCTURAL FRAME IS TO BE WELDED. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3C) THE PLANS DO NOT SHOW HOW THE NEW ROOF TOP UNITS |
| | AHU 1 OR AHU2 ARE TO BE ANCHORED TO THE FRAME TO RESIST |
| | THE MOMENT OF OVERTURNING. |
| | |
| | 2017 FBC-M- 301.15 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 4) THE STRUCTURAL SHEETS S000 & S100 BOTH CREATED BY |
| | TOMMY TAVERAS ARE NOT DIGITALLY SIGNED NOR SEALED. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |