Plan Review Details - Permit 19031293
Plan Review Stops For Permit 19031293
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 14:52 Rev Time 0.00
Received By shill Date 2019-07-18 Time 14:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 09:31 Sent To  
Notes
2019-07-15 10:10:392017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19031293
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JULY 15/ 2019
 ACTION: BUILDING PROVISO
  
 1) THE ROOFING PRODUCT APPROVAL SUBMITTED (17-1227.05
 CARLISLE SURE WELD SINGLE PLY TPO ROOF SYSTEMS OVER
 LIGHTWEIGHT CONCRETE DECKS) AND REVIEWED BY THE
 DESIGNER OF RECORD HAS NOT IDENTIFIED WHICH SUB-SYSTEM
 IS TO BE INSTALLED AND ASSOCIATED PRESSURES.
  
 2) THE ROOFING PERMIT WILL REQUIRE A SEPARATE PLAN
 REVIEW FOR CODE COMPLIANCE. FOR ALL ROOFING PRODUCTS
 PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE
 PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS
 ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL
 BE INCREASED FOR EITHER OR BOTH INSULATION & THE BASE
 SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING
 APPLICATION STANDARDS RAS 117. CALCULATION PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT. 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 3) SHEET S-100 SHOWS BOTH WELDED AND BOLTED
 CONNECTIONS. IF THERE ARE FIELD WELDED CONNECTIONS THEN
 SHOW COMPLIANCE FOR FIELD WELDED CONNECTIONS AND BOLTED
 CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2019-05-07 Time 06:35 Sent To  
Notes
2019-05-07 08:29:162017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19031293
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 07/ 2019
 ACTION: DENIED
  
 1) SHEET 023-S000 STRUCTURAL SHEET SECTION AT CURB
 SUPPORT. THE DETAIL INDICATES THAT NEWLY PREFABRICATED
 NOA RATED METAL CURB. PLEASE SUBMIT THE PRODUCT
 APPROVAL FOR ROOF CURBS.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP FANS, INTAKE AND EXHAUST AND NEW TECHNOLOGIES?
  
 2A) SHEET 023-S000 STRUCTURAL SHEET SECTION AT CURB
 SUPPORT. THE DETAIL INDICATES A NEW EXHAUST ROOF FAN.
 PLEASE SUBMIT THE PRODUCT APPROVAL FOR THE ROOF TOP
 EXHAUST FAN.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP FANS, INTAKE AND EXHAUST AND NEW TECHNOLOGIES?
  
 2B) THE DETAIL INDICATES A NEW ROOF TOP EXHAUST ROOF
 FAN. THE NOTE ON THE PLAN INDICATES ATTACH UNIT TO CURB
 PER UNITS MANUFACTURED RECOMMENDATIONS. THE PROVIDED
 POSITIVE & NEGATIVE PRESSURES TO SECURE THE ROOF TOP
 FAN TO THE CURB INDICATE THE PRESSURES, BUT NOT THE
 MEAN ROOF HEIGHT AND ROOF ZONE, THESE PRESSURES ARE
 ASSOCIATED WITH.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 2C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3A) THE STRUCTURAL PLAN 024-S000 SHOWS A SERIES OF NEW
 SLAB PENETRATIONS BUT THERE IS NO INDICATION ON THE
 PLAN, IF REINFORCING AROUND THE NEW OPENING IS
 REQUIRED? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) THE STRUCTURAL PLAN 024-S000 SHOWS A SERIES OF NEW
 ROOF TOP STEEL RAISED PLATFORMS. SECTION 1 SHOWS AN
 ELEVATION VIEW OF THE PLATFORM BUT THERE IS NO WELD
 INFORMATION HOW THE STRUCTURAL FRAME IS TO BE WELDED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) THE PLANS DO NOT SHOW HOW THE NEW ROOF TOP UNITS
 AHU 1 OR AHU2 ARE TO BE ANCHORED TO THE FRAME TO RESIST
 THE MOMENT OF OVERTURNING.
  
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4) THE STRUCTURAL SHEETS S000 & S100 BOTH CREATED BY
 TOMMY TAVERAS ARE NOT DIGITALLY SIGNED NOR SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-15 Cont ID  
Sent By jleahy Date 2019-05-15 Time 14:18 Rev Time 0.00
Received By jleahy Date 2019-05-14 Time 15:59 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-24 Cont ID  
Sent By pleduc Date 2019-04-24 Time   Rev Time 0.00
Received By pleduc Date 2019-04-17 Time 10:55 Sent To  
Notes
2019-04-17 11:17:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 15:11 Rev Time 0.00
Received By shill Date 2019-07-18 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-07-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-06 Time 12:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-15 Cont ID  
Sent By jleahy Date 2019-05-15 Time 14:18 Rev Time 0.00
Received By jleahy Date 2019-04-05 Time 11:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2019-05-07 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By ccole Date 2019-07-18 Time 14:42 Rev Time 0.00
Received By ccole Date 2019-07-18 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-10 Cont ID  
Sent By ccole Date 2019-07-10 Time 10:10 Rev Time 0.00
Received By ccole Date 2019-07-02 Time 15:09 Sent To  
Notes
2019-07-10 10:34:572ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19031293
 7/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN REFERENCE TO COMMENT #1 FROM THE 1ST REVIEW, AC
 COOLING AND HEATING CALCULATIONS FOR THE NEW SYSTEMS
 ARE REQUIRED PER SECTION 312.1 FBC M.
  
 2) IN REFERENCE TO COMMENT #4 FROM THE 1ST REVIEW,
 SHEET M3.2 MUST BE CORRECTED TO SHOW THE CORRECT LOW
 SIDE WALL GRILL LOCATIONS IN THE OR ROOMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By ccole Date 2019-05-07 Time 12:07 Rev Time 0.00
Received By ccole Date 2019-05-06 Time 08:27 Sent To  
Notes
2019-05-07 12:37:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 ASHRAE 170-2008
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AHU'S AND FAN COIL SYSTEMS IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC.
  
 2) COMMISSIONING OF THE MECHANICAL AND SERVICE WATER
 HEATING SYSTEMS IS REQUIRED PER SECTION C408.2 FBC-17
 ENERGY CONSERVATION. SUBMIT A COMMISSIONING PLAN AS
 OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS
 C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION.
  
 3) SHEET M7.3: THE AHU-2 SUMMARY IS MISSING THE MINIMUM
 REQUIRED 2 OA ACH. THE AHU-3 SUMMARY IS MISSING THE
 MINIMUM REQUIRED 8 TOTAL ACH- TABLE 7-1 ASHRAE
 170-2008.
  
 4) M2.2, 3.2, 4.2, & 5.2: THE LOW SIDE WALL RETURN
 GRILLS IN THE OR'S SHALL BE INSTALLED APRROXIMATELY 8
 IN. ABOVE THE FLOOR- SECTION 7.4.1 ASHRAE 170-2008.
  
 5) M8.2: PLEASE INDICATE THE PRESSURE DIFFERENTIAL
 VALUE TO BE MAINTAINED BETWEEN THE OR'S AND ALL
 ADJOINING ROOMS AND SPACES- SECTION 7.4.1 ASHRAE
 170-2008. REFER TO NOTE 1.3 (3) ON THE PLAN.
  
 6) THE WIND LOAD ENGINEERING FOR THE RTU'S AND THE
 EXHAUST FANS ON THE ROOF IS INCOMPLETE. REFER TIO THE
 BUILDING REVIEW COMMENTS AND COMPLY- SECTION 301.15 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By gjohnson Date 2019-06-28 Time 15:46 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
2019-06-28 15:49:17MED GAS CERTIFICATION FROM CONTRACTOR AND INSTALLER
 REQUIRED BEFORE PERMIT CAN BE ISSUED
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 13:43 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 13:43 Sent To  
Notes
2019-05-01 13:39:54PLUMBING 1ST REVISION REVIEW**DENIED**
  
 1) PLAN'S THAT CONTAIN MED GAS PIPING IS SO CONGRESSED
 THAT IT IS IMPOSSIBLE TO PERFORM AN ACTUATE PLAN
 REVIEW. PROVIDE FLAT DRAWINGS OF ALL MED GAS PIPING IN
 SMALLER SECTION ON FULL SHEETS AND PROVIDE A COMPLETE
 ISOMETRIC DRAWING TO INCLUDE DETAIL PIPING OF ALL NEW
 MED GAS EQUIPMENT. FBC 107.3.5.
  
 2) PROVIDE COMPLETED INSTALLATION MANUALS FOR ALL NEW
 MED GAS EQUIPMENT. FBC 107.3.5
  
 3) CERTIFICATION FOR THE PLUMBING CONTRACTOR AND ANY
 AND ALL EMPLOYEES SHOWING MED GAS CERTIFIED IS REQUIRED
 TO BE SUBMITTED PRIOR TO THE MED GAS PERMIT BEING
 ISSUED. FBC 105.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By gjohnson Date 2019-06-28 Time 15:46 Rev Time 0.00
Received By gjohnson Date 2019-06-26 Time 12:12 Sent To  
Notes
2019-06-26 12:13:05GPJ TO DO REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 13:38 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 08:43 Sent To  
Notes
2019-05-01 13:38:22PLUMBING 1ST REVISION REVIEW**DENIED**
  
 1) SHT. P1.2 CALLS OUT OF 2 NEW RPZ BACKFLOWS. PROVIDE
 NOTE THAT BACKFLOWS ARE REQUIRED TO HAVE A SEPERATE
 PERMIT AND ARE TO BE LEAD-FREE. , WPB CROSS CONNECTION
 MANUAL 2017
  
 2) PROVIDE DETAIL WHERE THE DISCHARGE PIPING FOR THE
 RELIEF VALVES OF THE BACKFLOW DEVICES IS DISCHARGING
 TO. FBC 107.2.1
  
 3) SHT. P2.1 NOTE #18 CALLS OUT TO INSTALL NEW 2" FLOOR
 SINK, NOTE #16 CALLS OUT NEW WASHING MACHINE BOX, SHT.
 A1.2 CALLS FOR NEW SINK NOTE #5 WHICH ON DEMO PLAN ON
 IN A DIFFERENT LOCATION. ALL THREE ARE NOT SHOWN ON
 PLUMBING ISOMETRIC ON SHT. P0.1.PLEASE ADVISE AND
 PROVIDE A COMPLETE SANITARY RISER DRAWING. FBC 107.3.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 10:11 Sent To  
Notes
2019-07-15 10:12:31ROOFING PROVISO UNDER BUILDING PERMIT:
  
 1) THE ROOFING PRODUCT APPROVAL SUBMITTED (17-1227.05
 CARLISLE SURE WELD SINGLE PLY TPO ROOF SYSTEMS OVER
 LIGHTWEIGHT CONCRETE DECKS) AND REVIEWED BY THE
 DESIGNER OF RECORD HAS NOT IDENTIFIED WHICH SUB-SYSTEM
 IS TO BE INSTALLED AND ASSOCIATED PRESSURES.
  
 2) THE ROOFING PERMIT WILL REQUIRE A SEPARATE PLAN
 REVIEW FOR CODE COMPLIANCE. FOR ALL ROOFING PRODUCTS
 PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE
 PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS
 ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL
 BE INCREASED FOR EITHER OR BOTH INSULATION & THE BASE
 SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING
 APPLICATION STANDARDS RAS 117. CALCULATION PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT. 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 3) SHEET S-100 SHOWS BOTH WELDED AND BOLTED
 CONNECTIONS. IF THERE ARE FIELD WELDED CONNECTIONS THEN
 SHOW COMPLIANCE FOR FIELD WELDED CONNECTIONS AND BOLTED
 CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 15:10 Rev Time 0.00
Received By shill Date 2019-07-18 Time 15:10 Sent To  
Notes
2019-07-18 15:11:52PROVISO: SUBMIT ONE PAPER FP1.0 WITH A SUBMITTAL OR
 PLAN REVIEW REQUEST FORM TO THE BUILDING DIVISION,
 DESCRIPTION "SIGNATURE DOCUMENTS"

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By shill Date 2019-07-17 Time 06:41 Rev Time 0.00
Received By shill Date 2019-07-17 Time 06:41 Sent To  
Notes
2019-07-17 06:41:37SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FP1.0 SIGNED BY DOCUSIGN; FAC61G15-23.004 THE
 INDIVIDUAL SIGNING CANNOT BE CONFIRMED. ROBERT MARK
 WEINSTEIN, PE ON THE TITLE BLOCK (SIGNATURE STATES
 "SIGNED BY DOCUSIGN; DIGITAL SIGNATURE DOES NOT INCLUDE
 THE NAME OF THE INDIVIDUAL SIGNING). ONE PAPER ORIGINAL
 CAN BE SUBMITTED AFTER ALL REVIEWS HAVE PASSED.
  
 FOR MEP ENGINEER, DIGITAL SIGNATURE ISSUE WILL NOT
 DELAY PERMIT ISSUANCE. UPLOAD ONLY SHEETS WHICH CHANGE
 (TO AVOID A RE-REVIEW BY ALL TRADES).
  
  
  
  
  
  
  
2019-07-15 10:31:13THE STRUCTURAL ENGINEER HAS BEEN NOTIFIED:
 61G15-23.003 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 (3) AN ELECTRONIC SIGNATURE IS A DIGITAL AUTHENTICATION
 PROCESS ATTACHED TO OR LOGICALLY ASSOCIATED WITH AN
 ELECTRONIC DOCUMENT AND SHALL CARRY THE SAME WEIGHT,
 AUTHORITY, AND EFFECT AS AN ORIGINAL SIGNATURE. THE
 ELECTRONIC SIGNATURE, WHICH CAN BE GENERATED BY USING
 EITHER PUBLIC KEY INFRASTRUCTURE OR SIGNATURE DYNAMICS
 TECHNOLOGY, MUST BE AS FOLLOWS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT;
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
  
2019-07-10 10:38:58THE MECH EOR HAS BEEN NOTIFIED THAT SELF CERTIFICATION
 OF DIGITAL PLANS IS NO LONGER ACCEPTABLE.
 CCOLE- 7/10/19

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jleahy Date 2019-05-15 Time 14:19 Rev Time 0.00
Received By jleahy Date 2019-05-01 Time 11:27 Sent To  
Notes
2019-05-01 11:28:12ALL SHEETS REVIEWED
  
 S-000 AND S-100 ARE NOT DIGITALLY SIGNED

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 16:24 Sent To  
Notes
2019-06-13 16:25:10PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2019-05-14 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-14 Time 15:02 Sent To  
Notes
2019-05-14 15:02:49PAUL GREILICH, SENIOR PLANNER