Plan Review Details - Permit 19031262
Plan Review Stops For Permit 19031262
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-20 Cont ID  
Sent By rmcdouga Date 2019-05-20 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2019-05-20 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By rmcdouga Date 2019-03-28 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2019-03-28 Time 18:23 Sent To I
Notes
2019-03-28 18:32:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED
  
 1) THE BUILDING IS LOCATED IN EXPOSURE C WITH A 170 MPH
 VULT WINDSPEED. THE MAXIMUM DESIGN PRESSURE FOR THE
 SYSTEM YOU SELECTED IS -60 PSF. THIS IS NOT ADEQUATE AT
 THE CORNER AND PERIMETER AREAS. GENERAL LIMITATION
 NUMBER 7 ON THE NOA, ALLOWS FOR ENHANCED FASTENING IN
 THESE AREAS TO INCREASE UPLIFT PRESSURES. SUBMIT SIGNED
 AND SEALED RAS 117 CALCULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-20 Cont ID  
Sent By rmcdouga Date 2019-05-20 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2019-05-16 Time 13:42 Sent To  
Notes
2019-05-17 13:42:36RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-28 Cont ID  
Sent By rmcdouga Date 2019-03-28 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2019-03-27 Time 14:52 Sent To  
Notes
2019-03-28 14:52:19REVISION ROUTED TO RMCDOUGAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved