Plan Review Details - Permit 19031242
Plan Review Stops For Permit 19031242
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By jduprey Date 2019-04-05 Time 15:13 Rev Time 0.00
Received By jduprey Date 2019-04-05 Time 15:13 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-29 Cont ID  
Sent By fgiaquin Date 2019-05-29 Time 06:35 Rev Time 0.00
Received By fgiaquin Date 2019-05-29 Time 06:15 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-13 Cont ID  
Sent By fgiaquin Date 2019-05-13 Time 07:19 Rev Time 0.00
Received By fgiaquin Date 2019-05-13 Time 06:57 Sent To I
Notes
2019-05-13 07:19:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD CALC
 FOR PANEL "A" INCLUDING ALL LOADS BOTH EXISTING AND
 NEW. "LOAD CALC" PROVIDED ON SHEET E.1 IS NOT A LOAD
 CALC. THAT MERELY SHOWS THE NEW PROPOSED LOAD. THERE
 ARE SEVERAL BREAKERS ALREADY IN PANEL A:
  
 1-40AMP LABELED "S BTS"
  
 1-40AMP LABELED "UMTS"
  
 1-100AMP LABELED "IV BTS"
  
 1-40AMP LABELED "EXISTING SSC"
  
 NEC 220, FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By fgiaquin Date 2019-04-19 Time 13:20 Rev Time 0.00
Received By fgiaquin Date 2019-04-19 Time 06:41 Sent To I
Notes
2019-04-19 07:01:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATIONS FOR PANEL A THAT IS
 FEEDING NEW V1 & V2 CABINETS. FBC 107.2.1 NEC 220.
  
 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL FOR NEW V1 &
 V2 CABINETS MUST BE UL OR OTHER NRTL (NATIONALLY
 RECOGNIZED TESTING LABRATORY). FBC 107.2.1 NEC 90.7,
 110.2, 110.3B
  
 3. VALUE FOR WORK SEEMS LOW. PROVIDE SIGNED CONTRACT
 INCLUDING ALL MATERIALS AND LABOR. SIGNED BY BOTH OWNER
 AND CONTACTOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-29 Cont ID  
Sent By fgiaquin Date 2019-05-29 Time 06:36 Rev Time 0.00
Received By fgiaquin Date 2019-05-23 Time 13:37 Sent To  
Notes
2019-05-24 13:38:05RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-13 Cont ID  
Sent By fgiaquin Date 2019-05-13 Time 07:19 Rev Time 0.00
Received By fgiaquin Date 2019-05-09 Time 13:20 Sent To  
Notes
2019-05-09 13:20:25RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-19 Cont ID  
Sent By cpuell Date 2019-04-19 Time 13:47 Rev Time 0.00
Received By cpuell Date 2019-03-27 Time 13:42 Sent To  
Notes
2019-04-04 14:42:45ROUTED FROM ZONING TO PERMIT LIBRARIAN 4/4/2019 EL
2019-03-28 13:42:43ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By elevesqu Date 2019-04-04 Time 14:41 Rev Time 0.00
Received By elevesqu Date 2019-04-04 Time 14:41 Sent To B
Notes
2019-04-04 14:42:32PER CITYSCAPE,
  
 IN LOOKING AT THIS: CABINETS ?G? AND ?I? ARE THE SAME
 AS PROPOSED IN 2017, EXCEPT ?G? IS SHIFTED FURTHER FROM
 ?I?, CLOSER TO WHERE EXISTING CABINET ?A? IS. THE
 LARGER CHANGE IS THAT IN 2017, CABINET ?C? WAS TO
 REMAIN AND A SMALL SURGE SUPPRESSOR WAS TO BE ADDED TO
 IT. INSTEAD, THIS CABINET ?C? IS BEING REMOVED AND A
 NEW CABINET ?H? IS BEING MOUNTED TO THE OUTER EDGE OF
 THE PLATFORM AS SHOWN IN C-1.
  
 AS LONG AS THEY ARE ONLY DOING THE CABINET WORK IT
 WON?T NEED ANOTHER REVIEW.
  