| Plan Review Stops For Permit 19031168 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-09-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-09-23 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-09-23 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-08-22 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-08-21 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2019-08-22 18:27:32 | THIRD BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE; | | | THE COMMENTS REGARDING THE METAL STRUCTURE WERE NOT | | | ADDRESSED AT ALL. PLEASE SEE BELOW FOR COPY OF | | | COMMENTS. IF THERE IS ANY QUESTION, PLEASE FEEL FREE TO | | | CONTACT ME. | | | | | | ORIGINAL COMMENT: | | | 1- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED: | | | A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO | | | REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS | | | REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY | | | III. | | | NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III | | | AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS. | | | | | | B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR | | | RISK CATEGORY I. COORDINATE WITH RISK CATEGORY | | | SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM | | | ABOVE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN | | | PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE | | | C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE | | | DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH | | | ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | | | D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN | | | ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND | | | SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE | | | CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1 | | | FBC-BUILDING. | | | | | | E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT | | | APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF | | | PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR | | | MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS | | | #2(A) AND 2(C) ABOVE. | | | SEC. 1609.1 FBC-BUILDING. | | | | | | F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT | | | APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL | | | PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR | | | MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS | | | #2(A) AND 2(C) ABOVE. | | | SEC. 1609.1 FBC-BUILDING. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A)METAL ROOF PANELS SPECIFIED ON PLANS. | | | | | | B)METAL WALL PANELS SPECIFIED ON PLANS. | | | | | | C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH | | | ITEM #2(A) AND #2(C) ABOVE. | | | NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203 | | | SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED | | | PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-06-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-06-21 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-06-20 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2019-06-20 17:02:40 | SECOND BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION | | | SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING | | | TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY | | | ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS | | | NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED. | | | OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED | | | FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE | | | FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | SCOPE OF WORK STILL IS NO CLEAR. PLANS SUBMITTED SHOW | | | ON SHEET C-YPP-02 THE CONSTRUCTION OF A CONCRETE SLAB | | | FOR TEMPORARY PSW PUMPS. THIS IS OK. BUT IT IS NOT | | | CLEAR WHY SUBMITTING SEPARATE ENGINEERED DRAWINGS FOR | | | FOR A METAL STRUCTURE. THERE ARE NO PLANS SHOWING WHERE | | | THIS STRUCTURE IS GOING TO BE INSTALLED. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | NEW COMMENTS: | | | 2- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED: | | | A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO | | | REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS | | | REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY | | | III. | | | NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III | | | AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS. | | | | | | B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR | | | RISK CATEGORY I. COORDINATE WITH RISK CATEGORY | | | SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM | | | ABOVE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN | | | PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE | | | C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE | | | DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH | | | ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS. | | | | | | D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN | | | ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND | | | SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE | | | CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1 | | | FBC-BUILDING. | | | | | | E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT | | | APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF | | | PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR | | | MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS | | | #2(A) AND 2(C) ABOVE. | | | SEC. 1609.1 FBC-BUILDING. | | | | | | F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT | | | APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL | | | PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR | | | MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS | | | #2(A) AND 2(C) ABOVE. | | | SEC. 1609.1 FBC-BUILDING. | | | | | | 3- ENGINEER OF RECORD FOR THE PROJECT TO INDICATE ON | | | PLANS THE LOCATION OF THE METAL STRUCTURE. IF HE IS NOT | | | DESIGNING THE METAL STRUCTURE, THEN INDICATE ON PLANS | | | THAT IS A DEFERRED SUBMITTAL. DESIGNER OF RECORD TO | | | REVIEW AND APPROVE IN WRITING THE METAL STRUCTURE | | | SUBMITTAL PRIOR TO SUBMITAL TO THIS OFFICE AS REQUIRED | | | BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A)METAL ROOF PANELS SPECIFIED ON PLANS. | | | | | | B)METAL WALL PANELS SPECIFIED ON PLANS. | | | | | | C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH | | | ITEM #2(A) AND #2(C) ABOVE. | | | NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203 | | | SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED | | | PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES. | | | | | | | | | 5- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND | | | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. | | | | | | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD | | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-02 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-05-02 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2019-05-02 12:01:07 | BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | SEC. 801.3 FBC-EXISTING BUILDING. | | | | | | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION | | | SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING | | | TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY | | | ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS | | | NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED. | | | OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED | | | FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE | | | FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 2- PLANS SUBMITTED DON'T HAVE THE ADDRESS OF THE | | | BUILDING. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND | | | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. | | | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD | | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-07-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-09 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-09 |
Time |
09:03 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-04-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-04-18 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-04-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2019-04-18 15:45:13 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ADDRESS ON PLANS, PROVIDE DETAILS. ALSO, CLEARLY | | | SHOW WHAT IS NEW WORK ON PLAN. CURRENT DRAWING IS | | | DIFFICULT TO ASCERTAIN WHAT IS NEW OR EXISTING. WPB FBC | | | 107.2.1 | | | 2. SHEET E-04 SHOW A PANEL SCHEDULE FOR PANEL | | | "LP-TEMP". WHERE IS THIS PANEL FED FROM? SAME SHEET | | | ALSO SHOW CIRCUITS FOR PUMP ROOM COMING FROM PANEL | | | "LP-PSW". PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR | | | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE | | | CIRCUITS, AND GFCI PROTECTION WHERE APPLICABLE TO | | | COMPLY WITH CODE. NEC 210.8, 210.19, 210.20, 215.5, | | | 408.4 | | | 3. SHEET E-04 SHOWS WIRING GOING TO 4 PUMP MOTORS, BUT | | | THERE IS NO INDICATION OF WIRE SIZE, CIRCUIT SIZE, OR | | | LOAD. PROVIDE DETAILS TO CONFIRM CODE COMPLIANCE. NEC | | | 210.19, 210.20, 215.5, 408.4; WPB FBC 107.2.1 | | | 4. PROVIDE MANUFACTURER SPEC SHEET FOR PUMP CONTROLLER. | | | NEC 110.3; WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2019-10-17 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-10-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-10-17 |
Time |
|
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-10-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-10-02 |
Time |
|
Sent To |
I |
|
| Notes |
| 2019-10-02 08:26:46 | REPEATED COMMENT: | | | | | | PLEASE RESPOND TO PREVIOUS COMMENT IN WRITING. | | | | | | ON SHEET M-ADF-40, 1511401, THE DETAIL FOR BACKFLOW | | | PREVENTION, NOTE 7, ITEM B SHOULD BE REVISED TO A LEAD | | | FREE MODEL (WILKINS 975XL2).- | | | | | | THERE IS NO WRITTEN RESPONSE, AND NOTES ARE MISSING | | | FROM SHEET M-ADF-40. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | | 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-09-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-09-13 |
Time |
|
Sent To |
I |
|
| Notes |
| 2019-09-13 07:53:13 | PLEASE RESPOND TO PREVIOUS COMMEN IN WRITING. | | | | | | ON SHEET M-ADF-40, 1511401, THE DETAIL FOR BACKFLOW | | | PREVENTION, NOTE 7, ITEM B SHOULD BE REVISED TO A LEAD | | | FREE MODEL (WILKINS 975XL2). | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX | | | 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-07-03 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2019-07-03 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2019-07-03 |
Time |
|
Sent To |
I |
|
| Notes |
| 2019-07-03 10:28:50 | FAILED: | | | | | | 1. AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | 2. FO THIS APPLICATION CALL OUT BACFLOW TO BE A RPPA | | | (REDUCED PRESSURE PRICIPLE ASSEMBLY). SUBMIT | | | SPECIFICATION SHEET | | | WITH REVISIONS TO PLAN M-ADF-40. DEVICE MUST BE "USC | | | APPROVED" AND "LEAD FREE". | | | | | | FEEL FREE TO E-MAIL ME SHOULD YOU REQUIRE OUR REVIEW OF | | | THE DEVICE PRIOR TO RESUBMISSION. | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-07 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-04-01 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-04-01 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2019-10-21 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-10-21 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-10-11 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2019-10-15 13:57:31 | RESUB ROUTED TO ENGINEERING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-10-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-10-02 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-09-17 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-09-13 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-09-13 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-08-01 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-07-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-05-30 |
Time |
13:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2019-05-02 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2019-03-28 |
Time |
13:06 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-08 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-08 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2019-06-21 09:01:14 | MECHANICAL PLANS SUBMITTED. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2019-04-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-04-19 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-04-19 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-10-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-10-21 |
Time |
04:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-10-21 |
Time |
03:46 |
Sent To |
ENG |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-10-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-10-01 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-10-01 |
Time |
11:47 |
Sent To |
ENG |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-08-20 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-08-20 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2019-08-20 16:05:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 54 = NATIONAL FUEL GAS CODE | | | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE | | | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 | | | NFPA 99 = HEALTH CARE FACILITIES CODE | | | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMEMTS: DENIED | | | THERE WAS NO RESPONSE TO THE FOLLOWING ORIGINAL | | | COMMENTS: | | | 1) PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION | | | CONTROL MANUAL ALL BACKFLOW PREVENTION DEVICES SHALL BE | | | LEAD FREE AND ON THE UNIV. OF SOUTHERN CALIFORNIA'S | | | FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC | | | RESEARCH LIST OF APPROVED DEVICES. NO RESPONSE NOTED IN | | | A | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PUMP. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW | | | PREVENTER. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19031168 3675 EASLEY DR | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-07-08 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-07-08 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2019-07-08 12:15:37 | 1) PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION | | | CONTROL MANUAL ALL BACKFLOW PREVENTION DEVICES SHALL BE | | | LEAD FREE AND ON THE UNIV. OF SOUTHERN CALIFORNIA'S | | | FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC | | | RESEARCH LIST OF APPROVED DEVICES. | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE PUMP.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW | | | PREVENTER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-06-05 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-06-05 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-04-29 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-04-23 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|