Plan Review Details - Permit 19031168
Plan Review Stops For Permit 19031168
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-09-23 Cont ID  
Sent By jgomez Date 2019-09-23 Time 13:36 Rev Time 0.00
Received By jgomez Date 2019-09-23 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-22 Cont ID  
Sent By jgomez Date 2019-08-22 Time 17:49 Rev Time 0.00
Received By jgomez Date 2019-08-21 Time 16:48 Sent To  
Notes
2019-08-22 18:27:32THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE;
 THE COMMENTS REGARDING THE METAL STRUCTURE WERE NOT
 ADDRESSED AT ALL. PLEASE SEE BELOW FOR COPY OF
 COMMENTS. IF THERE IS ANY QUESTION, PLEASE FEEL FREE TO
 CONTACT ME.
  
 ORIGINAL COMMENT:
 1- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED:
 A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO
 REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS
 REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY
 III.
 NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III
 AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS.
  
 B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR
 RISK CATEGORY I. COORDINATE WITH RISK CATEGORY
 SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN
 PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE
 C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE
 DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH
 ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN
 ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND
 SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE
 CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1
 FBC-BUILDING.
  
 E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)METAL ROOF PANELS SPECIFIED ON PLANS.
  
 B)METAL WALL PANELS SPECIFIED ON PLANS.
  
 C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH
 ITEM #2(A) AND #2(C) ABOVE.
 NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203
 SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED
 PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-21 Cont ID  
Sent By jgomez Date 2019-06-21 Time 13:15 Rev Time 0.00
Received By jgomez Date 2019-06-20 Time 16:58 Sent To  
Notes
2019-06-20 17:02:40SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING
 TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY
 ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS
 NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED.
 OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED
 FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE
 FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK STILL IS NO CLEAR. PLANS SUBMITTED SHOW
 ON SHEET C-YPP-02 THE CONSTRUCTION OF A CONCRETE SLAB
 FOR TEMPORARY PSW PUMPS. THIS IS OK. BUT IT IS NOT
 CLEAR WHY SUBMITTING SEPARATE ENGINEERED DRAWINGS FOR
 FOR A METAL STRUCTURE. THERE ARE NO PLANS SHOWING WHERE
 THIS STRUCTURE IS GOING TO BE INSTALLED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENTS:
 2- DESIGN CRITERIA FOR METAL STRUCTURE PLANS SUBMITTED:
 A)ENGINEER STATES RISK CATEGORY III. ENGINEER NEEDS TO
 REVISE THE ULTIMATE AND NOMINAL DESIGN WIND SPEED AS
 REQUIRED BY SEC. 1609.3 FBC-BUILDING FOR RISK CATEGORY
 III.
 NOTE: THE CITY ULTIMATE DESIGN FOR RISK CATEGORY III
 AND IV IS 180 MPH. SEE SEC. 120.1 CITY AMENDMENTS.
  
 B) GENERAL NOTE #2 STATES THAT THIS IS A BUILDING FOR
 RISK CATEGORY I. COORDINATE WITH RISK CATEGORY
 SPECIFIED ON THE DESIGN CRITERIA. COORDINATE WITH ITEM
 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) ENGINEER STATES WIND EXPOSURE "C". THE DESIGN
 PRESSURES SHOWN SEEM TO BE TO LOW FOR BUILDING EXPOSURE
 C. ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW THE
 DESIGN PRESSURES WERE CALCULATED. NOTE: COORDINATE WITH
 ITEM #2(A) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 D) ENGINEER TO SPECIFY IF THE DESIGN PRESSURES SHOWN
 ARE ULTIMATE DESIGN WIND SPEED OR NOMINAL DESIGN WIND
 SPEEDS. THE ULTIMATE WIND DESIGN WIND SPED NEEDS TO BE
 CONVERTED TO NOMINAL DESIGN WIND SPEEDS. SEC. 1609.3.1
 FBC-BUILDING.
  
 E) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL ROOF
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 F) ENGINEER OF RECORD TO CLEARLY MARK ON THE PRODUCT
 APPROVAL SUBMITTED THE FASTENING OF THE METAL WALL
 PANELS. NOTE: SEE TABLE "A" OF PRODUCT APPROVAL FOR
 MAXIMUM DESIGN PRESSURES AND COORDINATE WITH ITEMS
 #2(A) AND 2(C) ABOVE.
 SEC. 1609.1 FBC-BUILDING.
  
 3- ENGINEER OF RECORD FOR THE PROJECT TO INDICATE ON
 PLANS THE LOCATION OF THE METAL STRUCTURE. IF HE IS NOT
 DESIGNING THE METAL STRUCTURE, THEN INDICATE ON PLANS
 THAT IS A DEFERRED SUBMITTAL. DESIGNER OF RECORD TO
 REVIEW AND APPROVE IN WRITING THE METAL STRUCTURE
 SUBMITTAL PRIOR TO SUBMITAL TO THIS OFFICE AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)METAL ROOF PANELS SPECIFIED ON PLANS.
  
 B)METAL WALL PANELS SPECIFIED ON PLANS.
  
 C) ROLL UP DOORS THAT MET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. COORDINATE WITH
 ITEM #2(A) AND #2(C) ABOVE.
 NOTE: DESIGN PRESSURES FOR ROLL UP DOOR MODEL 203
 SPECIFIED BY THE ENGINEER OF RECORD ON THE APPROVED
 PRODUCT LIST DOESN'T MEET THE DESIGN PRESSURES.
  
  
 5- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
  
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-02 Cont ID  
Sent By jgomez Date 2019-05-02 Time 11:48 Rev Time 0.00
Received By jgomez Date 2019-05-02 Time 11:32 Sent To  
Notes
2019-05-02 12:01:07BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION
 SPECIFIES "INSTALLATION OF NEW BOOSTER PUMP CONNECTING
 TO EXISTING BIOSOIDS PROJECT". PLANS SUBMITTED ARE ONLY
 ELECTRICAL PLANS. THEY DON'T SHOW WHAT IS NEW A WHAT IS
 NOT. WHERE IS THE NEW PUMP GOING TO BE INSTALLED.
 OUTSIDE? INSIDE?. ARE THERE ANY SPECIFICATIONS REQUIRED
 FOR ANCHORING THE NEW PUMP FOR WIND LOADS?. PROVIDE
 FLOOR PLANS SHOWING THE COMPLETE SCOPE OF WORK. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- PLANS SUBMITTED DON'T HAVE THE ADDRESS OF THE
 BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-09 Cont ID  
Sent By jpearson Date 2019-07-09 Time 09:03 Rev Time 0.00
Received By jpearson Date 2019-07-09 Time 09:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By jpearson Date 2019-04-18 Time 15:45 Rev Time 0.00
Received By jpearson Date 2019-04-18 Time 14:34 Sent To  
Notes
2019-04-18 15:45:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ADDRESS ON PLANS, PROVIDE DETAILS. ALSO, CLEARLY
 SHOW WHAT IS NEW WORK ON PLAN. CURRENT DRAWING IS
 DIFFICULT TO ASCERTAIN WHAT IS NEW OR EXISTING. WPB FBC
 107.2.1
 2. SHEET E-04 SHOW A PANEL SCHEDULE FOR PANEL
 "LP-TEMP". WHERE IS THIS PANEL FED FROM? SAME SHEET
 ALSO SHOW CIRCUITS FOR PUMP ROOM COMING FROM PANEL
 "LP-PSW". PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND GFCI PROTECTION WHERE APPLICABLE TO
 COMPLY WITH CODE. NEC 210.8, 210.19, 210.20, 215.5,
 408.4
 3. SHEET E-04 SHOWS WIRING GOING TO 4 PUMP MOTORS, BUT
 THERE IS NO INDICATION OF WIRE SIZE, CIRCUIT SIZE, OR
 LOAD. PROVIDE DETAILS TO CONFIRM CODE COMPLIANCE. NEC
 210.19, 210.20, 215.5, 408.4; WPB FBC 107.2.1
 4. PROVIDE MANUFACTURER SPEC SHEET FOR PUMP CONTROLLER.
 NEC 110.3; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2019-10-17 Cont ID  
Sent By rrossano Date 2019-10-17 Time   Rev Time 0.00
Received By rrossano Date 2019-10-17 Time   Sent To P
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2019-10-02 Cont ID  
Sent By rrossano Date 2019-10-02 Time   Rev Time 0.00
Received By rrossano Date 2019-10-02 Time   Sent To I
Notes
2019-10-02 08:26:46REPEATED COMMENT:
  
 PLEASE RESPOND TO PREVIOUS COMMENT IN WRITING.
  
 ON SHEET M-ADF-40, 1511401, THE DETAIL FOR BACKFLOW
 PREVENTION, NOTE 7, ITEM B SHOULD BE REVISED TO A LEAD
 FREE MODEL (WILKINS 975XL2).-
  
 THERE IS NO WRITTEN RESPONSE, AND NOTES ARE MISSING
 FROM SHEET M-ADF-40.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-09-13 Cont ID  
Sent By rrossano Date 2019-09-13 Time   Rev Time 0.00
Received By rrossano Date 2019-09-13 Time   Sent To I
Notes
2019-09-13 07:53:13PLEASE RESPOND TO PREVIOUS COMMEN IN WRITING.
  
 ON SHEET M-ADF-40, 1511401, THE DETAIL FOR BACKFLOW
 PREVENTION, NOTE 7, ITEM B SHOULD BE REVISED TO A LEAD
 FREE MODEL (WILKINS 975XL2).
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By Mgonzale Date 2019-07-03 Time   Rev Time 1.00
Received By mgonzale Date 2019-07-03 Time   Sent To I
Notes
2019-07-03 10:28:50FAILED:
  
 1. AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 2. FO THIS APPLICATION CALL OUT BACFLOW TO BE A RPPA
 (REDUCED PRESSURE PRICIPLE ASSEMBLY). SUBMIT
 SPECIFICATION SHEET
 WITH REVISIONS TO PLAN M-ADF-40. DEVICE MUST BE "USC
 APPROVED" AND "LEAD FREE".
  
 FEEL FREE TO E-MAIL ME SHOULD YOU REQUIRE OUR REVIEW OF
 THE DEVICE PRIOR TO RESUBMISSION.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-07 Cont ID  
Sent By pleduc Date 2019-06-07 Time   Rev Time 0.00
Received By pleduc Date 2019-06-07 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-01 Cont ID  
Sent By scaldero Date 2019-04-01 Time 12:28 Rev Time 0.00
Received By scaldero Date 2019-04-01 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-10-21 Cont ID  
Sent By cpuell Date 2019-10-21 Time 15:29 Rev Time 0.00
Received By cpuell Date 2019-10-11 Time 13:57 Sent To  
Notes
2019-10-15 13:57:31RESUB ROUTED TO ENGINEERING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-02 Cont ID  
Sent By cpuell Date 2019-10-02 Time 10:50 Rev Time 0.00
Received By cpuell Date 2019-09-17 Time 13:59 Sent To  
Notes
2019-09-18 13:59:53B27

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-13 Cont ID  
Sent By cpuell Date 2019-09-13 Time 11:12 Rev Time 0.00
Received By cpuell Date 2019-08-01 Time 15:04 Sent To  
Notes
2019-08-02 15:05:03B27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-30 Time 13:45 Sent To  
Notes
2019-05-31 13:45:38B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-02 Cont ID  
Sent By jgomez Date 2019-05-02 Time 12:01 Rev Time 0.00
Received By jgomez Date 2019-03-28 Time 13:06 Sent To I
Notes
2019-03-29 13:07:08B21

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-07-08 Cont ID  
Sent By ccole Date 2019-07-08 Time 08:40 Rev Time 0.00
Received By ccole Date 2019-07-08 Time 07:31 Sent To  
Notes
2019-06-21 09:01:14MECHANICAL PLANS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-04-19 Cont ID  
Sent By ccole Date 2019-04-19 Time 08:30 Rev Time 0.00
Received By ccole Date 2019-04-19 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-10-21 Cont ID  
Sent By tklarge Date 2019-10-21 Time 04:48 Rev Time 0.00
Received By tklarge Date 2019-10-21 Time 03:46 Sent To ENG
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-01 Cont ID  
Sent By tklarge Date 2019-10-01 Time 12:11 Rev Time 0.00
Received By tklarge Date 2019-10-01 Time 11:47 Sent To ENG
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-20 Cont ID  
Sent By jesmith Date 2019-08-20 Time 16:05 Rev Time 0.00
Received By jesmith Date 2019-08-20 Time 16:05 Sent To  
Notes
2019-08-20 16:05:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 THERE WAS NO RESPONSE TO THE FOLLOWING ORIGINAL
 COMMENTS:
 1) PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION
 CONTROL MANUAL ALL BACKFLOW PREVENTION DEVICES SHALL BE
 LEAD FREE AND ON THE UNIV. OF SOUTHERN CALIFORNIA'S
 FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC
 RESEARCH LIST OF APPROVED DEVICES. NO RESPONSE NOTED IN
 A
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19031168 3675 EASLEY DR
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 12:15 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 12:01 Sent To  
Notes
2019-07-08 12:15:371) PER THE CITY OF WEST PALM BEACH CROSS-CONNECTION
 CONTROL MANUAL ALL BACKFLOW PREVENTION DEVICES SHALL BE
 LEAD FREE AND ON THE UNIV. OF SOUTHERN CALIFORNIA'S
 FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC
 RESEARCH LIST OF APPROVED DEVICES.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP.WPB AMEND. TO FBC SEC.
 107.2.1.
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By jroach Date 2019-06-05 Time 15:33 Rev Time 0.00
Received By jroach Date 2019-06-05 Time 15:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-29 Cont ID  
Sent By jroach Date 2019-04-29 Time 13:58 Rev Time 0.00
Received By jroach Date 2019-04-23 Time 15:46 Sent To  
Notes
***NONE***