| Plan Review Stops For Permit 19031145 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-12-17 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-17 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-09-17 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-09-17 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2019-09-17 16:41:37 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1 PLEASE PROVIDE CLEAN AND CLEAR | | | SIGNED/SEALED PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-12 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-12 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-10 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-10 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2020-01-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-15 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-15 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-17 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-17 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2019-12-17 12:35:14 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | E-2 SHOWS A NEW PANEL WITH A 2P 50A FOR BATTERY??? | | | BATTERY IS NOT CONNECTED TO THIS PANEL??? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2019-10-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-10-28 |
Time |
06:13 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-10-24 |
Time |
06:19 |
Sent To |
I |
|
| Notes |
| 2019-10-28 06:14:20 | REQUEST TO HAVE MEETING WITH OR SPEAK TO DESIGN | | | PROFESSIONAL OVER DESIGN. PLEASE CALL OR EMAIL. | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-09-17 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-09-17 |
Time |
05:55 |
Sent To |
B |
|
| Notes |
| 2019-09-17 06:17:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NEW PLANS SUBMITTED HAVE VOID WRITTEN ON THEM THEN | | | ARE WHITED OUT WITH WHITE OUT. PLANS ARE NOT READABLE. | | | PLEASE SEE REQUIREMENTS FOR PLAN SUBMITTALS BELOW: | | | | | | THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW | | | THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH | | | AMENDMENTS TO THE FBC: | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-08-12 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-08-12 |
Time |
06:14 |
Sent To |
B |
|
| Notes |
| 2019-08-12 07:07:26 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PROVIDE WRITTEN RESPONSE TO EACH PLAN REVIEW COMMENT | | | | | | 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD | | | CALCULATIONS AND PANEL SCHEDULES FOR ALL NEW PANELS, | | | ONLY LOAD CALCULATION PROVIDED WAS FOR NEW "CRITICAL | | | LOAD PANEL" AND EXISTING SERVICE, NOTHING PROVIDED FOR | | | NEW "MAIN PV PANEL" OR NEW "MAIN GENERATION PANEL" FBC | | | 107.2.1 NEC 220 | | | | | | 2. DUE TO LINE SIDE TAP RUNNING AND EGC ALONG WITH THE | | | GROUNDED CONDUCTOR TO PV AC DISCONNECT PROVIDES | | | PARALLEL PATH TO GROUND. PROVIDE CORRECTION. | | | | | | 3. NO CUT SHEETS HAVE BEEN PROVIDED FOR NEW "BACK UP | | | GATEWAY AUTOMATIC DISCONNECT" PROVIDE CUT SHEETS FOR | | | PRODUCT APPROVAL SHOWING UL LISTING. FBC 107.2.1 NEC | | | 90.7, 110.2, 110.3B | | | | | | 4. TESLA BATTER IS RATED FOR 30AMPS AND IS FEEDING | | | "MAIN GENERATION PANEL" WITH #10'S AWG BUT CRITICAL | | | LOAD PANEL IS BEING FED WITH #6'S AWG FROM "MAIN | | | GENERATION PANEL"??? PROVIDE CORRECTION/ CLARIFICATION. | | | FBC 107.2.1 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-09 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-04-09 |
Time |
17:01 |
Sent To |
E |
|
| Notes |
| 2019-04-09 17:05:47 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE LOAD CALCULATIONS FOR ALL NEW AND EXISITING | | | PANELS NEC 220, FBC 107.2.1 | | | | | | 2. PROVIDE UL OR OTHER NRTL LISTINGS FOR ALL NEW | | | EQUIPMENT ASSOCIATED WITH REVISION (TESLA BATTERY ETC). | | | NEC 90.7,110.2,110.3B | | | | | | 3. VALUE FOR WORK LOW. NEW EQUIPMENT HAS BEEN ADDED | | | WITH ZERO CHANGE IN VALUE. RAISE VALUE OR VALUE WILL BE | | | SET BY BUILDING OFFICIAL. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2019-12-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-18 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-12 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2019-12-13 14:27:22 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-10-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-10-28 |
Time |
06:16 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-10-11 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2019-10-15 13:44:40 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-09-17 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-09-11 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2019-09-12 13:41:26 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-12 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-08 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2019-08-09 15:30:32 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-10 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-25 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2019-03-26 14:51:01 | REVISION ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-09-16 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
2019-09-16 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2019-09-16 |
Time |
10:25 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-03-27 |
|
|
Cont ID |
|
| Sent By |
hdanfort |
Date |
2019-03-27 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2019-03-27 |
Time |
13:55 |
Sent To |
E |
|
| Notes |
|
|