Plan Review Details - Permit 19031145
Plan Review Stops For Permit 19031145
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-12-17 Cont ID  
Sent By pvalenti Date 2019-12-17 Time 15:41 Rev Time 0.00
Received By pvalenti Date 2019-12-17 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-09-17 Cont ID  
Sent By pvalenti Date 2019-09-17 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2019-09-17 Time 16:37 Sent To  
Notes
2019-09-17 16:41:37***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1 PLEASE PROVIDE CLEAN AND CLEAR
 SIGNED/SEALED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By pvalenti Date 2019-08-12 Time 07:39 Rev Time 0.00
Received By pvalenti Date 2019-08-12 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-10 Cont ID  
Sent By pvalenti Date 2019-04-10 Time 15:57 Rev Time 0.00
Received By pvalenti Date 2019-04-10 Time 15:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2020-01-15 Cont ID  
Sent By jleahy Date 2020-01-15 Time 15:31 Rev Time 0.00
Received By jleahy Date 2020-01-15 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2019-12-17 Cont ID  
Sent By jleahy Date 2019-12-17 Time 12:33 Rev Time 0.00
Received By jleahy Date 2019-12-17 Time 12:33 Sent To  
Notes
2019-12-17 12:35:14FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 E-2 SHOWS A NEW PANEL WITH A 2P 50A FOR BATTERY???
 BATTERY IS NOT CONNECTED TO THIS PANEL???

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-10-28 Cont ID  
Sent By fgiaquin Date 2019-10-28 Time 06:13 Rev Time 0.00
Received By fgiaquin Date 2019-10-24 Time 06:19 Sent To I
Notes
2019-10-28 06:14:20REQUEST TO HAVE MEETING WITH OR SPEAK TO DESIGN
 PROFESSIONAL OVER DESIGN. PLEASE CALL OR EMAIL.
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-09-17 Cont ID  
Sent By fgiaquin Date 2019-09-17 Time 06:17 Rev Time 0.00
Received By fgiaquin Date 2019-09-17 Time 05:55 Sent To B
Notes
2019-09-17 06:17:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEW PLANS SUBMITTED HAVE VOID WRITTEN ON THEM THEN
 ARE WHITED OUT WITH WHITE OUT. PLANS ARE NOT READABLE.
 PLEASE SEE REQUIREMENTS FOR PLAN SUBMITTALS BELOW:
  
 THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW
 THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By fgiaquin Date 2019-08-12 Time 07:07 Rev Time 0.00
Received By fgiaquin Date 2019-08-12 Time 06:14 Sent To B
Notes
2019-08-12 07:07:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PROVIDE WRITTEN RESPONSE TO EACH PLAN REVIEW COMMENT
  
 1. AS PER LAST PLAN REVIEW COMMENTS PROVIDE LOAD
 CALCULATIONS AND PANEL SCHEDULES FOR ALL NEW PANELS,
 ONLY LOAD CALCULATION PROVIDED WAS FOR NEW "CRITICAL
 LOAD PANEL" AND EXISTING SERVICE, NOTHING PROVIDED FOR
 NEW "MAIN PV PANEL" OR NEW "MAIN GENERATION PANEL" FBC
 107.2.1 NEC 220
  
 2. DUE TO LINE SIDE TAP RUNNING AND EGC ALONG WITH THE
 GROUNDED CONDUCTOR TO PV AC DISCONNECT PROVIDES
 PARALLEL PATH TO GROUND. PROVIDE CORRECTION.
  
 3. NO CUT SHEETS HAVE BEEN PROVIDED FOR NEW "BACK UP
 GATEWAY AUTOMATIC DISCONNECT" PROVIDE CUT SHEETS FOR
 PRODUCT APPROVAL SHOWING UL LISTING. FBC 107.2.1 NEC
 90.7, 110.2, 110.3B
  
 4. TESLA BATTER IS RATED FOR 30AMPS AND IS FEEDING
 "MAIN GENERATION PANEL" WITH #10'S AWG BUT CRITICAL
 LOAD PANEL IS BEING FED WITH #6'S AWG FROM "MAIN
 GENERATION PANEL"??? PROVIDE CORRECTION/ CLARIFICATION.
 FBC 107.2.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By fgiaquin Date 2019-04-09 Time 17:05 Rev Time 0.00
Received By fgiaquin Date 2019-04-09 Time 17:01 Sent To E
Notes
2019-04-09 17:05:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATIONS FOR ALL NEW AND EXISITING
 PANELS NEC 220, FBC 107.2.1
  
 2. PROVIDE UL OR OTHER NRTL LISTINGS FOR ALL NEW
 EQUIPMENT ASSOCIATED WITH REVISION (TESLA BATTERY ETC).
 NEC 90.7,110.2,110.3B
  
 3. VALUE FOR WORK LOW. NEW EQUIPMENT HAS BEEN ADDED
 WITH ZERO CHANGE IN VALUE. RAISE VALUE OR VALUE WILL BE
 SET BY BUILDING OFFICIAL.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-12-18 Cont ID  
Sent By jleahy Date 2019-12-18 Time 15:57 Rev Time 0.00
Received By jleahy Date 2019-12-12 Time 14:27 Sent To  
Notes
2019-12-13 14:27:22RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-28 Cont ID  
Sent By fgiaquin Date 2019-10-28 Time 06:16 Rev Time 0.00
Received By fgiaquin Date 2019-10-11 Time 13:44 Sent To  
Notes
2019-10-15 13:44:40RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-17 Cont ID  
Sent By pvalenti Date 2019-09-17 Time 16:42 Rev Time 0.00
Received By pvalenti Date 2019-09-11 Time 13:41 Sent To  
Notes
2019-09-12 13:41:26RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-12 Cont ID  
Sent By pvalenti Date 2019-08-12 Time 07:39 Rev Time 0.00
Received By pvalenti Date 2019-08-08 Time 15:30 Sent To  
Notes
2019-08-09 15:30:32RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-10 Cont ID  
Sent By pvalenti Date 2019-04-10 Time 15:57 Rev Time 0.00
Received By pvalenti Date 2019-03-25 Time 14:50 Sent To  
Notes
2019-03-26 14:51:01REVISION ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By hmtribou Date 2019-09-16 Time 10:25 Rev Time 0.00
Received By hmtribou Date 2019-09-16 Time 10:25 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-27 Cont ID  
Sent By hdanfort Date 2019-03-27 Time 13:55 Rev Time 0.00
Received By hmtribou Date 2019-03-27 Time 13:55 Sent To E
Notes
***NONE***