Plan Review Details - Permit 19031140
Plan Review Stops For Permit 19031140
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-02 Cont ID  
Sent By jduprey Date 2019-04-02 Time 10:40 Rev Time 0.00
Received By jduprey Date 2019-04-02 Time 09:14 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-20 Cont ID  
Sent By fgiaquin Date 2019-04-20 Time 09:37 Rev Time 0.00
Received By fgiaquin Date 2019-04-20 Time 09:30 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-03 Cont ID  
Sent By fgiaquin Date 2019-04-03 Time 18:02 Rev Time 0.00
Received By fgiaquin Date 2019-04-03 Time 17:52 Sent To I
Notes
2019-04-03 17:59:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. PROVIDE CUT SHEETS SHOWING LISTINGS OF
 MATERALS/DEVICES TO BE USED EITHER UL OR OTHER
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). FBC
 107.2.1 NEC 90.7,110.2,110.3B
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-20 Cont ID  
Sent By fgiaquin Date 2019-04-20 Time 09:37 Rev Time 0.00
Received By fgiaquin Date 2019-04-11 Time 13:56 Sent To  
Notes
2019-04-12 13:56:51RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-03 Cont ID  
Sent By fgiaquin Date 2019-04-03 Time 18:02 Rev Time 0.00
Received By fgiaquin Date 2019-03-25 Time 14:42 Sent To  
Notes
2019-03-26 14:42:37BLDG MISC 2


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved