| | FUEL GAS COMMENTS: |
| | |
| | 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| | FBC-R SEC. G2413.4.1, G2413.4.2. |
| | |
| | 2. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | |
| | 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL |
| | GAS SEC. 411.1.3.2. |
| | |
| | 4. PROVIDE DETAIL SHOWING CONNECTION AT THE GENERATOR |
| | WITH SHUT VALVE AND DRIP LEG. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 5. STEEL PIPE IS NOT APPROVED FOR DIRECT BURIAL |
| | UNDERGROUND IT SHALL BE SLEEVED PROVIDE DETAIL OF |
| | SEALED SLEEVE AROUND PIPE. PER FBC FG 404.11 , 404.11.1 |
| | |
| | 6 SEPARATE PERMITS REQUIRED FOR THE GAS AND GENERATOR. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |