Plan Review Details - Permit 19031039
Plan Review Stops For Permit 19031039
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-22 Cont ID  
Sent By thunt Date 2019-04-22 Time 08:52 Rev Time 0.00
Received By thunt Date 2019-04-18 Time 13:36 Sent To  
Notes
2019-04-19 13:36:57RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 06:24 Rev Time 0.00
Received By thunt Date 2019-03-22 Time 11:06 Sent To  
Notes
2019-03-25 11:06:57PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status N Date 2019-07-18 Cont ID  
Sent By gjohnson Date 2019-07-18 Time 16:15 Rev Time 0.00
Received By gjohnson Date 2019-07-18 Time 16:15 Sent To  
Notes
2019-07-18 16:16:42PLANS NOT REQUIRED FOR RESIDENTIAL IRRIGATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By thunt Date 2019-04-22 Time 08:51 Rev Time 0.00
Received By thunt Date 2019-04-22 Time 07:24 Sent To  
Notes
2019-04-22 08:51:57PLUMBING 2ND REVIEW**DENIED**
  
  
 1) PLANS SHALL BE DRAWN UPON SUITABLE MATERIAL.
 DRAWINGS OR NOTES PROVIDE ON PLAN SHALL NOT BE IN
 PENCIL. FBC 107.2.1
  
 2) PROVIDE RAIN SENSOR ON PLAN. FS 373.82
  
 3) ZONE #2 SHOWS ALL PIPING 3/4" RUNNING 15 HEADS.
 PROVIDE DETAIL ON HEAD G.P.M, FLOW RATE FOR 3/4" PIPING
 WITH DESIGN PRESSURE AND PRESSURE LOSS THOUGH FITTINGS.
 FBC 107.3.5
  
 4) 2ND REQUEST. YOU AGAIN HAVE LISTED CITY WATER/ PUMP
 CITY WATER. PLEASE PROVIDE WHAT THE SOURCE OF WATER IS
 FOR THIS SYSTEM. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 06:24 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 06:24 Sent To I
Notes
2019-03-26 06:24:05PLUMBING 1ST REVIEW**DENIED**
  
 1) PLANS MISSING ARCHITECT OF RECORDS WET SIGNATURE AND
 DATE. REQUIRED PER F.A.C RULE 61G1-16.005
  
 2) PLANS ARE CONFUSING. STATES ON TOP RIGHT WELL PUMP
 AND SHOWS LOCATIONS BUT ALSO CALLS OUT FOR 1" CITY
 WATER. WHICH ONE PLEASE CLARIFY. IF CITY WATER IS IT
 CONNECTED TO IT'S OWN WATER METER? FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]