 |
Plan Review Details - Permit 19031011
| Plan Review Stops For Permit 19031011 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-04-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-17 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-04-17 |
Time |
06:36 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-01 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-04-01 |
Time |
07:23 |
Sent To |
I |
|
| Notes |
| 2019-04-01 07:23:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. AS PER LAST PLAN REVIEW COMMENTS. NO ELECTRICAL PLAN | | | SUBMITTED SHOWING, CONDUIT SIZE AND TYPE FROM MCC TO | | | MOTORS, WIRE SIZE FROM MCC TO MOTORS, WIRE TYPE, ETC. | | | PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED | | | BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | 2. AS PER LAST PLAN REVIEW COMMENTS VALUE FOR LIFT | | | STATION IS LOW, VALUE WILL BE RAISED BY BUILDING | | | OFFICIAL. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-03-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-03-25 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-03-25 |
Time |
06:18 |
Sent To |
P |
|
| Notes |
| 2019-03-25 06:38:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ELECTRICAL PLAN PROVIDED. PROVIDE ELECTRICAL PLAN | | | FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN | | | PROFESSIONAL. SHOW CONDUIT SIZE, CONDUIT TYPE, WIRE | | | SIZE, MOTORS, OCP, HAZARDOUS LOCATION DOCUMENTATION, | | | ETC. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1, | | | 107.3.5 | | | | | | 2, WORK HAS ALREADY BEEN COMPLETED IN THE FIELD WITH NO | | | INSPECTIONS. LABELS ON EQUIPMENT AND EMAILS FROM | | | CONTRACTOR STATE THAT IT IS A CLASS 1 DIVISION 1 | | | HAZARDOUS LOCATION. A DESIGN PROFESSIONAL MUST | | | DETERMINE WHETHER IT IS A CLASS LOCATION OR NOT AND | | | MUST PROVIDE SIGNED AND SEALED DOCUMENTION. NEC 500.4 | | | NEC 107.2.1 | | | | | | 3. VALUE FOR PROJECT LOW. RAISE VALUE OR VALUE WILL BE | | | SET BY BUILDING OFFICIAL. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-04-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-17 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-04-02 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2019-04-03 15:13:20 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-04-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-04-01 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-03-26 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2019-03-27 15:39:24 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-03-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-03-25 |
Time |
06:43 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-03-21 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2019-03-22 10:58:00 | ELEC <5K |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |