| 2019-04-11 12:59:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19031010 |
| | 4/11/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHOW THE FIRE LINE RUN FROM THE POINT OF CONNECTION |
| | TO THE BUILDING- SECTION 107.2.1 WPB. |
| | |
| | 2) PROVIDE SUBMITTALS FOR THE UNDERGROUND PIPING, PIPE |
| | FITTINGS, AND JOINT RESTRAINT SYSTEM. PLEASE NOTE THAT |
| | MATERIAL DATA SHEETS SHALL BE PROVIDED TO THE ON-SITE |
| | INSPECTOR TO INDICATE CORRECT TORQUE WRENCH SETTINGS. |
| | |
| | 3) THE PLAN SHALL BE SIGNED AND SEALED BY THE ENGINEER |
| | WHO PREPARED THE DRAWING. E;LCTRONIC SIGNATURES AND |
| | SEALS ARE NOT ACCEPTABLE TO CERTIFY PAPER PLANS SECTION |
| | 61G15-23,002- 23.005 FAC. |
| | |
| | 4) A BACKFLOW PREVENTER SHALL BE PROVIDED AND THE |
| | LOCATION SHOWN ON THE PLAN, HOWEVER IT MUST BE |
| | SUBMITTED UNDER SEPARATE PERMIT- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |
| | . |