Plan Review Details - Permit 19030985
Plan Review Stops For Permit 19030985
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By cthroop Date 2019-04-19 Time 16:10 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 10:51 Sent To  
Notes
2019-04-19 16:12:58BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. VALUE
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR THE PROPSED ROOFING SYSTEM.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 3. CHANGE APPLICABLE CODES IN ADA BLOCK TO FBC 6TH
 EDITION (2017).
  
 4. PLEASE CLARIFY NOTE 29A ON PLAN PAGE A-0.0.03
 "CONTRACTOR MUST COMPLY WITH SECTION 717 OF THE FBC
 2014".
  
 5. PROVIDE A UNITY OF TITLE PER BUILDING SETBACKS BLOCK
 ON PLAN PAGE A-0.0.02.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By jleahy Date 2019-04-16 Time 08:21 Rev Time 0.00
Received By jleahy Date 2019-04-16 Time 08:21 Sent To  
Notes
2019-04-16 08:22:12FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) DISCONNECT REQUIRED FOR SEPARATE STRUCTURE
  
 225.30 NUMBER OF SUPPLIES
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR
 FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING
 MEANS SHALL BE
 SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN
 225.30(A) THROUGH (E). FOR THE PURPOSE OF THIS SECTION,
 A MULTIWIRE
 BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE CIRCUIT.
 WHERE A BRANCH CIRCUIT OR FEEDER ORIGINATES IN THESE
 ADDITIONAL
 BUILDINGS OR OTHER STRUCTURES, ONLY ONE FEEDER OR
 BRANCH CIRCUIT
 SHALL BE PERMITTED TO SUPPLY POWER BACK TO THE ORIGINAL
 BUILDING
 OR STRUCTURE, UNLESS PERMITTED IN 225.30(A) THROUGH
 (E).
  
  
 2) SEPARATE GROUNDING ELECTRODE SYSTEM REQUIRED.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED
 BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE
 OR GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE
 WI TH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL
 BE CON NECTED IN ACCORDANCE WITH 250.32(B) OR (C).
 WHERE THERE
 IS NO EXISTING GROUNDING ELECTRODE, THE GROUNDING
 ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 07:52 Rev Time 0.00
Received By shill Date 2019-04-30 Time 07:52 Sent To  
Notes
2019-04-30 07:53:02CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By scaldero Date 2019-03-26 Time 10:43 Rev Time 0.00
Received By scaldero Date 2019-03-26 Time 10:34 Sent To  
Notes
2019-03-26 10:43:55PERMIT # 19030985
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 07:14 Rev Time 0.00
Received By shill Date 2019-03-25 Time 14:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 07:13 Rev Time 0.00
Received By shill Date 2019-05-13 Time 07:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By cthroop Date 2019-04-19 Time 16:13 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 15:09 Sent To  
Notes
2019-04-19 16:13:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR THE PROPSED ROOFING SYSTEM.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By cthroop Date 2019-04-19 Time 16:13 Rev Time 0.00
Received By cthroop Date 2019-04-19 Time 10:51 Sent To  
Notes
2019-04-19 16:14:26BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SIGNATURE AND SEAL ON GEOTECHNICAL SOILS REPORT IS
 INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 THE SUBMITTED DOCUMENT IS SIGNED AND SEALED AS A PAPER
 DOCUMENT, THERE IS NO ELECTRONIC SIGNATURE TO THIS
 DOCUMENT. THE ENGINEER HAS 2 OPTIONS, EITHER COMPLY
 WITH FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SUBMIT 2 ORIGINAL PAPER DOCUMENT SIGNED
 AND SEALED.
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By jroach Date 2019-05-09 Time 16:17 Rev Time 0.00
Received By jroach Date 2019-05-09 Time 16:17 Sent To  
Notes
2019-05-09 16:17:38PROVISOS:
  
 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE
 ?WEDDING GAZEBO.? SEPARATE PERMITS REQUIRED FOR
 SURROUNDING SITE WORK, FENCING, LANDSCAPING,
 IRRIGATION, ETC.
  
 2. THE BANYAN CAY RESIDENTIAL/COMMERCIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS AND DESIGN GUIDELINES, AS OUTLINED IN
 RESOLUTION NO. 307-17, APPROVED ON NOVEMBER 20, 2017,
 AND AS MAY BE AMENDED. QUESTIONS/COMMENTS, PLEASE
 CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved