Plan Review Details - Permit 19030966
Plan Review Stops For Permit 19030966
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-30 Time 09:25 Rev Time 0.00
Received By dbattles Date 2019-04-30 Time 08:22 Sent To  
Notes
2019-04-30 09:29:29107.3.5 FBC[AMENDED] NO ADDITIONAL COMMENTS AT THIS
 TIME.
 BUILDING WILL NEED TO REVIEW CHANGES MADE TO SATIFY
 OTHER REVIEW COMMENTS.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By jpearson Date 2019-04-09 Time 14:13 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 14:10 Sent To  
Notes
2019-04-09 14:12:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE CORRECTION FOR ENGINEERS SIGNATURE. PER FAC
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-30 Time 09:29 Rev Time 0.00
Received By dbattles Date 2019-03-20 Time 13:06 Sent To  
Notes
2019-04-08 15:01:06ROUTED FROM ZONING TO PERMIT LIBRARIAN 4/8/2019 EL
2019-03-22 13:06:26B16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-11 Cont ID  
Sent By ccole Date 2019-04-11 Time 12:37 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 12:16 Sent To  
Notes
2019-04-11 12:42:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030966
 4/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 61G15-23.002 FAC: THE ASHRAE-90
 2013 COMPLIANCE DATA REPORT FOR THE WALK-IN FREEZER
 SHALL BE SIGNED AND SELAED BY THE ENGINEER WHO
 POREPARED THE DOCUMENT- RANDY HERBERT.
  
 2) INDICATE HOW THE OUTDOOR WALK-IN FREEZER WILL BE
 PROTECTED FROM DAMAGE SUCH AS VEHICLE IMPACT- SECTION
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By aaponte Date 2019-04-08 Time 15:00 Rev Time 0.00
Received By elevesqu Date 2019-04-08 Time 12:44 Sent To  
Notes
2019-04-08 15:00:49PLEASE SUBMIT SURVEY OF PROPERTY AND SHOW EXACT
 LOCATION OF PROPOSED COOLER WITH DIMENSIONS FOR
 SETBACKS.
  
 STAND ALONE ITEMS WILL NEED TO BE SCREENED BY AN
 ENCLOSURE MADE OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY OR COMPARABLE MATERIAL. WALLS SHALL
 BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT 2-FOOT
 INTERVALS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]