| 2019-03-26 11:25:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 0.0 - THERE ARE INDICATIONS OF A 30% |
| | REDUCTION FOR FUNITURE IN THE OCCUPANCY LOAD |
| | CALCULATIONS. |
| | |
| | UNDER WHAT FLORIDA FIRE PREVENTION CODE REFERNECE ARE |
| | YOU CITING FOR THIS REDUCTION? |
| | |
| | PLEASE PROVIDE SPECIFIC CODE(S) OR CORRECT/REMOVE. |
| | |
| | |
| | |
| | 2) SHEET A 0.0 - THERE IS ONLY ONE EXIT FROM THE |
| | PROPOSED FLOOR PLAN. THE EXIT LEADING INTO THE EXISTING |
| | SPACE DOES NOT MEET THE REQUIRMENT OF A SEPARATE EXIT. |
| | |
| | PER NFPA 101, CH 16, NEW DAYCARE |
| | |
| | 16.2.4 NUMBER OF MEANS OF EGRESS. |
| | 16.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE |
| | WITH SECTION 7.4. |
| | 16.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN |
| | ACCORDANCE |
| | WITH BOTH OF THE FOLLOWING CRITERIA: |
| | (1) THEY SHALL BE PROVIDED ON EVERY STORY. |
| | (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY |
| | STORY AND |
| | MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL BE |
| | PERMITTED |
| | TO BE COMMON FOR THE DISTANCE PERMITTED AS COMMON PATH |
| | OF TRAVEL BY 16.2.5.3. |
| | |
| | 16.2.5 ARRANGEMENT OF MEANS OF EGRESS. SEE ALSO |
| | 16.1.6.2. |
| | 16.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH |
| | SECTION 7.5. |
| | |
| | 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 7.5.1.3.1 |
| | THROUGH 7.5.1.3.7. |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 0.0 - THERE IS AN INDICATION OF A DEAD END |
| | CORRIDOR THAT APPEARS TO EXCEED THE REQUIREMENT. |
| | |
| | 16.2.5.2 NO DEAD-END CORRIDOR SHALL EXCEED 20 FT (6100 |
| | MM), |
| | OTHER THAN IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.7, IN WHICH CASE DEAD-END CORRIDORS SHALL NOT |
| | EXCEED |
| | 50 FT (15 M). |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY/CLARIFY. |
| | |
| | |
| | |
| | 4) SHEET A 0.0 - THERE IS AN INDICATION OF A CORRIDOR |
| | LLEADING TO AN EXIT THAT DOES NOT APPEAR TO MEET THE |
| | REQUIRMENT. |
| | |
| | 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE |
| | CONSTRUCTED OF |
| | WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE |
| | RATING IN |
| | ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED |
| | BY ANY OF |
| | THE FOLLOWING: |
| | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| | SPACES |
| | NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN |
| | ONE |
| | DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR |
| | EXIT |
| | ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. |
| | (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7, |
| | CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| | PROVIDED THAT |
| | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION |
| | 8.4. |
| | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| | 1-HOUR FIRE |
| | RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR |
| | WALLS |
| | SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR |
| | CEILING. |
| | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES |
| | BY WALLS |
| | HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 8.3. |
| | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: |
| | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.7. |
| | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| | FORM |
| | SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 5) SHEET A 4.0 - THERE IS AN INDICATION OF DOOR # 2 AS |
| | NOT HAVING A FIRE RESISTIVE RATING. THIS DOOR IS |
| | LOCATED IN A 2 HOUR WALL. |
| | |
| | PLEASE REVIEW AND CORRECT/PROVIDE A 2 HOUR RATING FOR |
| | THIS DOOR. |
| | |
| | |
| | |
| | 6) SHEET A 4.0 - THE DOORS ALONG THE CORRIDOR ARE |
| | REQUIRED TO HAVE AN 1 HOUR FIRE RESISTIVE RATING PER # |
| | 4 ABOVE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 7) SHEET A 0.0 - THERE ARE INDICATIONS OF WINDOWS FOR |
| | RESCUE FROM THE ROOMS. |
| | |
| | THE FLOOR PLAN INDICATES ONLY ONE EXIT AND IT IS AN |
| | INDIRECT PATH AS IT PASSES THRU THE FRONT ROOM AREA. |
| | |
| | 16.2.11.1 WINDOWS FOR RESCUE. |
| | 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO |
| | CLIENT |
| | OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS |
| | THAN ONE |
| | OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH |
| | ALL OF THE |
| | FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2: |
| | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE |
| | USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT |
| | LESS THAN |
| | 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, |
| | AND 5.7 |
| | FT2 (0.5 M2) IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | IN. (1120 |
| | MM) ABOVE THE FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A WIDTH |
| | AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7 |
| | FT2 (0.5 |
| | M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510 |
| | MM), TO |
| | PASS FULLY THROUGH THE OPENING. |
| | 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT |
| | APPLY TO |
| | EITHER OF THE FOLLOWING: |
| | (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7 |
| | (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO AN EXIT |
| | OR DIRECTLY TO THE OUTSIDE OF THE BUILDING |
| | |
| | |
| | |
| | 8) SHEET A 1.0 - DOOR E AT THE FRONT ROOM/CORRIDOR |
| | LOCATION IS NOT INDICATED WITH ANY EXIT HARWARE ON THE |
| | DOOR SCHEDULE |
| | |
| | PLEASE PROVIDE THE HARDWARE AND LOCK/LATCH TYPE FOR |
| | THIS DOOR IN COMPLIANCE WITH THE CODE. |
| | |
| | |
| | |
| | 9) SHEET A 4.0 - NOTE # 2 INDICATES DOOR STOPS ON ALL |
| | DOORS. |
| | |
| | THERE SHALL NOT BE DOOR STOPS ON ANY FIRE RATED DOOR. |
| | |
| | FIRE RATED DOORS SHALL HAVE DOOR CLOSERS. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 10) SHEET A 4.0 - BATHROOM DOORS 7 & 8 ARE INDICATED AS |
| | HAVING PRIVACY LOCKS |
| | |
| | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE |
| | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| | OUTSIDE |
| | BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE |
| | TO THE STAFF. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | NARRATIVE OF COMPLIANCE. |
| | |
| | |
| | |
| | 11) SHEET E 1 - THERE ARE NO INDICATIONS OF A FIRE |
| | ALARM. MORE THAN ONE ROOM IS INDICATED AND A FIRE ALARM |
| | IS REQUIRED. |
| | |
| | 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN |
| | DAY-CARE |
| | OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| | OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| | EXTERIOR |
| | EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE |
| | PROVIDED |
| | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.6. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 12) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 13) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |