2019-04-26 12:34:41****CORRECTIONS****
 W.P.B. PERMIT: 19030940
 REVIEWED: APRIL 26, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) PLEASE REVIEW EGRESS FROM CARE ROOM 104 AND THE
 CORRIDOR LEADING TO EXIT DISCHARGE. THESE COMMENTS ARE
 IN PARALLEL WITH FIRE AND THE MOST RESTRIVTIVE WILL
 APPLY.
  
 466.8 FBC[B] CORRIDORS. EVERY INTERIOR CORRIDOR SHALL
 BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING. EXCEPTIONS:
 A. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTIONS 901.6 AND 903.3.1.1 CORRIDOR WALLS SHALL
 NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710.
 B. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
 C. LAVATORIES IN UNSPRINKLERED BUILDINGS SHALL NOT BE
 REQUIRED TO BE SEPARATED FROM CORRIDORS, PROVIDED THAT
 THEY ARE SEPARATED FROM ALL OTHER SPACES BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 709.
 D. LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS, PROVIDED THE BUILDING IS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND
 903.3.1.1.
  
 1020.1 FBC[B] CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1020.1.
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. (SEE
 1020 FOR EXCEPTIONS)
  
 1020.6 FBC[B] CORRIDOR CONTINUITY.
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF
 EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR
 TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT
 ACCESS STAIRWAYS OR RAMPS, THE FIRE-RESISTANCE RATING
 SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR
 RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON
 THE ADJACENT FLOOR LEADING TO THE EXIT. EXCEPTIONS:
 A. FOYERS, LOBBIES OR RECEPTION ROOMS CONSTRUCTED AS
 REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS
 INTERVENING ROOMS.
 B. ENCLOSED ELEVATOR LOBBIES AS PERMITTED BY ITEM 1 OF
 SECTION 1016.2 SHALL NOT BE CONSTRUED AS INTERVENING
 ROOMS.
  
 2) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE.
 - PLEASE SHOW ACCESSIBLE ROUTE TO EXISTING DOOR THAT
 PROVIDES ACCESS TO NEW AREAS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By jpearson Date 2019-06-24 Time 08:39 Rev Time 0.00
Received By jpearson Date 2019-06-24 Time 08:39 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By jpearson Date 2019-04-16 Time 09:38 Rev Time 0.00
Received By jpearson Date 2019-04-16 Time 08:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-05 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By pleduc Date 2019-03-26 Time   Rev Time 0.00
Received By pleduc Date 2019-03-26 Time 10:48 Sent To  
Notes
2019-03-26 11:25:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 0.0 - THERE ARE INDICATIONS OF A 30%
 REDUCTION FOR FUNITURE IN THE OCCUPANCY LOAD
 CALCULATIONS.
  
 UNDER WHAT FLORIDA FIRE PREVENTION CODE REFERNECE ARE
 YOU CITING FOR THIS REDUCTION?
  
 PLEASE PROVIDE SPECIFIC CODE(S) OR CORRECT/REMOVE.
  
  
  
 2) SHEET A 0.0 - THERE IS ONLY ONE EXIT FROM THE
 PROPOSED FLOOR PLAN. THE EXIT LEADING INTO THE EXISTING
 SPACE DOES NOT MEET THE REQUIRMENT OF A SEPARATE EXIT.
  
 PER NFPA 101, CH 16, NEW DAYCARE
  
 16.2.4 NUMBER OF MEANS OF EGRESS.
 16.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4.
 16.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN
 ACCORDANCE
 WITH BOTH OF THE FOLLOWING CRITERIA:
 (1) THEY SHALL BE PROVIDED ON EVERY STORY.
 (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY
 STORY AND
 MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL BE
 PERMITTED
 TO BE COMMON FOR THE DISTANCE PERMITTED AS COMMON PATH
 OF TRAVEL BY 16.2.5.3.
  
 16.2.5 ARRANGEMENT OF MEANS OF EGRESS. SEE ALSO
 16.1.6.2.
 16.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 0.0 - THERE IS AN INDICATION OF A DEAD END
 CORRIDOR THAT APPEARS TO EXCEED THE REQUIREMENT.
  
 16.2.5.2 NO DEAD-END CORRIDOR SHALL EXCEED 20 FT (6100
 MM),
 OTHER THAN IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7, IN WHICH CASE DEAD-END CORRIDORS SHALL NOT
 EXCEED
 50 FT (15 M).
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY/CLARIFY.
  
  
  
 4) SHEET A 0.0 - THERE IS AN INDICATION OF A CORRIDOR
 LLEADING TO AN EXIT THAT DOES NOT APPEAR TO MEET THE
 REQUIRMENT.
  
 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE
 CONSTRUCTED OF
 WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE
 RATING IN
 ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED
 BY ANY OF
 THE FOLLOWING:
 (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL
 SPACES
 NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN
 ONE
 DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR
 EXIT
 ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3.
 (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7,
 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION
 8.4.
 (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE
 RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR
 WALLS
 SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR
 CEILING.
 (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES
 BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3.
 (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.7.
 (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS
 FORM
 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 5) SHEET A 4.0 - THERE IS AN INDICATION OF DOOR # 2 AS
 NOT HAVING A FIRE RESISTIVE RATING. THIS DOOR IS
 LOCATED IN A 2 HOUR WALL.
  
 PLEASE REVIEW AND CORRECT/PROVIDE A 2 HOUR RATING FOR
 THIS DOOR.
  
  
  
 6) SHEET A 4.0 - THE DOORS ALONG THE CORRIDOR ARE
 REQUIRED TO HAVE AN 1 HOUR FIRE RESISTIVE RATING PER #
 4 ABOVE.
  
 PLEASE REVIEW AND CORRECT.
  
  
 7) SHEET A 0.0 - THERE ARE INDICATIONS OF WINDOWS FOR
 RESCUE FROM THE ROOMS.
  
 THE FLOOR PLAN INDICATES ONLY ONE EXIT AND IT IS AN
 INDIRECT PATH AS IT PASSES THRU THE FRONT ROOM AREA.
  
 16.2.11.1 WINDOWS FOR RESCUE.
 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT
 OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS
 THAN ONE
 OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH
 ALL OF THE
 FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE
 USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN
 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT,
 AND 5.7
 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN. (1120
 MM) ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH
 AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7
 FT2 (0.5
 M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510
 MM), TO
 PASS FULLY THROUGH THE OPENING.
 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT
 APPLY TO
 EITHER OF THE FOLLOWING:
 (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7
 (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO AN EXIT
 OR DIRECTLY TO THE OUTSIDE OF THE BUILDING
  
  
  
 8) SHEET A 1.0 - DOOR E AT THE FRONT ROOM/CORRIDOR
 LOCATION IS NOT INDICATED WITH ANY EXIT HARWARE ON THE
 DOOR SCHEDULE
  
 PLEASE PROVIDE THE HARDWARE AND LOCK/LATCH TYPE FOR
 THIS DOOR IN COMPLIANCE WITH THE CODE.
  
  
  
 9) SHEET A 4.0 - NOTE # 2 INDICATES DOOR STOPS ON ALL
 DOORS.
  
 THERE SHALL NOT BE DOOR STOPS ON ANY FIRE RATED DOOR.
  
 FIRE RATED DOORS SHALL HAVE DOOR CLOSERS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 10) SHEET A 4.0 - BATHROOM DOORS 7 & 8 ARE INDICATED AS
 HAVING PRIVACY LOCKS
  
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE
 BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE
 TO THE STAFF.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE OF COMPLIANCE.
  
  
  
 11) SHEET E 1 - THERE ARE NO INDICATIONS OF A FIRE
 ALARM. MORE THAN ONE ROOM IS INDICATED AND A FIRE ALARM
 IS REQUIRED.
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE
 OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR
 OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN
 EXTERIOR
 EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE
 PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION
 9.6.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 12) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 13) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-30 Time 13:57 Sent To  
Notes
2019-05-31 13:57:20B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-26 Cont ID  
Sent By dbattles Date 2019-04-26 Time 12:35 Rev Time 0.00
Received By dbattles Date 2019-03-20 Time 14:42 Sent To  
Notes
2019-03-21 14:42:57B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By cthroop Date 2019-06-26 Time 16:33 Rev Time 0.00
Received By cthroop Date 2019-06-26 Time 16:33 Sent To  
Notes
2019-06-26 16:33:46MU-2019-019849-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By dbattles Date 2019-04-26 Time 12:35 Rev Time 0.00
Received By dbattles Date 2019-04-26 Time 08:42 Sent To  
Notes
2019-04-26 12:37:12109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 REVIEW NEEDED FOR CHANGE OF OCCUPANCY.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-12 Cont ID  
Sent By ccole Date 2019-06-12 Time 16:34 Rev Time 0.00
Received By ccole Date 2019-06-12 Time 15:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-11 Cont ID  
Sent By ccole Date 2019-04-11 Time 09:21 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By jesmith Date 2019-06-11 Time 14:14 Rev Time 0.00
Received By jesmith Date 2019-06-11 Time 13:32 Sent To  
Notes
2019-06-11 14:14:46APPROVED WITH PROVISO
 1. PROVIDE SPECS FOR FILTROL 160 LINT
 INTERCEPTOR/FILTER. SPEC SHALL BE IN PLACE FOR FINAL
 INSPECTION.
 2. THE SHUT OFF VALVES AT THE CLOTHES WASHER SHALL BE
 ACCESSIBLE PER FBC PL 603.2 AS WELL AS THE FULL OPEN
 VALVES IN THE CEILING ABOVE SERVICING THE DOWN FEED
 PIPES TO NTHE CLOTHES WASHER.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-12 Cont ID  
Sent By tklarge Date 2019-04-12 Time 11:37 Rev Time 0.00
Received By tklarge Date 2019-04-10 Time 05:45 Sent To  
Notes
2019-04-12 10:31:341) SHT. A-1.0 - THE DOOR FOR TOILET ROOMS #108 & #109
 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY OR THE WATER CLOSET. 2017 FBC-ACCESS. SEC.
 603.2.3.
 2) DRINKING FOUNTAINS ARE REQUIRED IN THIS SPACE PER
 2017 FBC-PLUMBING TABLE 403.1 & 410.3. SHOW THE
 LOCATION OF THE REQUIRED DRINKING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND ALSO ON THE PLUMBING PLANS
 AND WATER AND SANITARY RISERS. 2017 FBC-PLUMBING TABLE
 403.1 & WPB AMEND. TO FBC 107.2.1.
 3) A SERVICE SINK IS REQUIRED IN THIS SPACE PER 2017
 FBC-PLUMBING TABLE 403.1. SHOW THE LOCATION OF THE
 SERVICE SINK ON THE ARCHITECTURAL FLOOR PLAN AND
 PLUMBING PLAN AND SANITARY AND WATER RISERS.
 4) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINE PER 2017 FBC-PLUMBING SEC.1003.6.
 5) SHT. A-4.0 - DETAIL #3 - ELEVATION - "A" - THE
 TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7
 INCHES AND A MAXIMUM OF 9 INCHES TO THE CENTER OF THE
 DISPENSER FROM THE FRONT OF THE TOILET BOWL.2017
 FBC-ACCES. SEC.604.7.
 6) SHT. P-0 - THE WASHING MACHINE SHALL BE INSTALLED ON
 A MINIMUM 3 INCH STACK. SHOW THIS ON THE PLAN. 2017
 FBC-PLUMBING SEC.406.2.
 7) THE WATER SUPPLY VALVES AT THE WASHING MACHINE BOX
 SHALL BE ACCESSIBLE PER FBC-PLUMBING SEC.606.3.
 8) TEMPERED WATER IS REQUIRED AT THE LAVATORIES PER
 FBC-PLUMBING SEC.416.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 12:19 Sent To  
Notes
2019-06-13 12:23:58 
 PAUL GREILICH, AICP, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-04-02 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-01 Time 16:26 Sent To  
Notes
2019-04-02 11:40:36PLEASE INCLUDE A SURVEY OR OVERALL SITE PLAN INDICATING
 SETBACKS. IF ALL WORK IS TO BE COMPLETED WITHIN THE
 EXSITING BUILDING FOOTPRINT, INCLUDE A NOTE INDICATING
 THIS ON THE SITE PLAN.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443