Plan Review Details - Permit 19030921
Plan Review Stops For Permit 19030921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 08:29 Rev Time 0.00
Received By shill Date 2019-05-06 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By shill Date 2019-04-05 Time 05:43 Rev Time 0.00
Received By shill Date 2019-04-05 Time 05:43 Sent To  
Notes
2019-04-05 05:52:33****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THERE IS AN EXPIRED MECHANICAL PERMIT AT THIS
 LOCATION, 09040436; PLEASE COORDINATE WITH THE
 CONTRACTOR (SERVICE EXPERTS LLC, 561-744-2700) TO
 RESOLVE PRIOR TO FINAL INSPECTION.
  
 2. NO STRUCTURAL INFORMATION WAS PROVIDED FOR THE GLASS
 SHOWER ENCLOSURE. SUBJECT TO FIELD INSPECTOR'S
 DISCRETION, A REVISION MAY BE REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-23 Cont ID  
Sent By jpearson Date 2019-04-23 Time 10:09 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 07:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By jleahy Date 2019-04-05 Time 08:06 Rev Time 0.00
Received By jleahy Date 2019-04-05 Time 08:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 08:29 Rev Time 0.00
Received By shill Date 2019-04-08 Time 15:04 Sent To  
Notes
2019-04-09 15:05:07R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-05 Cont ID  
Sent By jleahy Date 2019-04-05 Time 08:06 Rev Time 0.00
Received By jleahy Date 2019-03-20 Time 13:52 Sent To  
Notes
2019-04-05 05:58:044/5 TO JL DESK
  
  
2019-03-21 13:52:33R05

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By thunt Date 2019-04-15 Time 16:32 Rev Time 0.00
Received By thunt Date 2019-04-15 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By thunt Date 2019-04-02 Time 14:56 Rev Time 0.00
Received By thunt Date 2019-04-02 Time 14:56 Sent To  
Notes
2019-04-02 14:56:13PLUMBING 1ST REVIEW**DENEIED**
  
 1) PROVIDE A SANITARY RISER ISOMETRIC DRAWING. FBC
 107.3.5
  
 2) IS THE 3 PIECE SHOWER DRAIN MADE BY KBRS FOR THERE
 SYSTEM? IF NOT PROVIDE PRODUCT SUPPORT DOCUMENTS THAT
 ALLOW THE USE OF A LIQUID LINERS ON THE MANUFACTURES
 DRAIN ASSEMBLY. FBC 107.2.1
  
 3) PERSON DESIGNING PLANS SHALL SIGN AND DATE TAKING
 RESPONSIBILITY. F.S 471
  
 4) PROVIDE SHOWER VALVE MANUFACTURE MANUALS SHOWING
 THEY ARE ASSE 1016 APPROVED BEING PRESSURE BALANCED,
 THERMOSTATIC OR A COMBINATION OF BOTH AND HAVE A LIMIT
 STOP OF 120F. FBC P 417
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  