| 2019-04-03 10:08:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. REVISION SHOWS A RECEPTACLE OUTLET IN THE POWDER |
| | BATH THAT IS NOT GFCI PROTECTED. PROVIDE CORRECTION. |
| | NEC 210.8; FBC RE E3902 |
| | 2. REVISION SHOWS A CHANDELIER IN THE MASTER WALK IN |
| | CLOSET. PER CODE, LIGHTING WITH OPEN OR PARTIALLY |
| | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE |
| | CORRECTION. NEC 410.16; FBC RE E4003.12 |
| | 3. REVISION SHOWS THE ADDITION OF SUB-PANEL D. WHAT IS |
| | THE LOCATION OF THIS PANEL? PROVIDE LOCATION FOR |
| | CONFIRMATION OF CODE COMPLIANCE. WPB FBC 107.2.1 |
| | 4. RISER DIAGRAM SHOWS TOO MANY WIRES IN FEED TO |
| | SUB-PANEL B. WHAT IS THE ADDITIONAL WIRE FOR? PROVIDE |
| | CLARIFICATION AND CORRECTIONS AS NEEDED. WPB FBC |
| | 107.2.1 |
| | 5. RISER SHOWS THE ADDITON OF SUB-PANEL D, BUT THE LOAD |
| | CALCULATION HAS NOT BEEN UPDATED TO REFLECT THIS |
| | INFORMATION. PROVIDE CORRECTION. NEC 220; FBC RE |
| | E3602.2 |
| | 6. THE 2ND FLOOR BALCONY HAS BEEN CHANGED TO INCLUDE A |
| | STORAGE AREA. RECEPTACLE OUTLETS IN A STORAGE AREA |
| | REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8; |
| | FBC RE E3902 |
| | 7. REVISION SHOWS THE SMOKE/CO ALARM IN MASTER FED FROM |
| | A DIFFERENT CIRCUIT THAN OTHER ALARMS. CODE REQUIRES |
| | THAT ALL ALARMS ARE INTERCONNECTED. PROVIDE CORRECTION. |
| | FBC RE R314.4 |
| | 8. REVISION SHOWS THREE BATHROOMS ON CIRCUIT B-2 THAT |
| | FEEDS ALL LIGHTING AND RECEPTACLES IN THE BATHROOMS. A |
| | MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| | 9. COMMENT FOR VALUE REMOVED PER STEVE KENNEDY. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |