| 2019-03-20 06:42:37 | PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE |
| | REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL |
| | PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE |
| | RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) VALUE OF JOB SEEMS LOW. PLEASE PROVIDE A SIGNED |
| | CONTRACT FOR THIS JOB.109.3 BUILDING PERMIT VALUATIONS. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATIONOF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | |
| | 2) PERSON DRAWING PLANS SHALL SIGN AND DATE.FBC 107.1 |
| | |
| | 3) AAV WOULD NOT BE PERMITTED AS THIS IS A SEPERATE |
| | BUILDING DRAIN CONNECTING TO THE SEWER. PER FBC-P 904.1 |
| | THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE |
| | NOT LESS THEN ONE VENT PIPIE THAT EXTEND TO THE |
| | OUTDOORS. |
| | |
| | 4) PLANS DO NOT INDICATE IF THESE SINKS ARE NEW OR |
| | EXISTING. WHERE IS THE HOT AND COLD WATER COMING FROM? |
| | FBC 107.1 |
| | |
| | |