Plan Review Details - Permit 19030841
Plan Review Stops For Permit 19030841
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-23 Cont ID  
Sent By thunt Date 2019-04-23 Time 07:12 Rev Time 0.00
Received By thunt Date 2019-04-23 Time 07:12 Sent To  
Notes
2019-04-23 07:13:43VALUE CHANGED FROM $2300.00 TO $10361.96 TO MATCH
 SUBMITTED PROPOSAL TOTAL COST OF JOB. TLH

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-20 Cont ID  
Sent By thunt Date 2019-03-20 Time 07:04 Rev Time 0.00
Received By thunt Date 2019-03-20 Time 07:04 Sent To I
Notes
2019-03-20 07:04:04GAS 1ST REVIEW**DENIED**
  
  
  
 1) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408
  
 3) VALUE SEEMS LOW. VALUE SHALL INCLUDE ALL COST TO
 INCLUDE THE COST OF THE 2 NEW BBQ GRILL. PROVIDE A
 SIGNED CONTRACT. 109.3 BUILDING PERMIT VALUATIONS. IF,
 IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 ELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE.
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-23 Cont ID  
Sent By thunt Date 2019-04-23 Time 07:13 Rev Time 0.00
Received By thunt Date 2019-04-19 Time 13:11 Sent To  
Notes
2019-04-22 13:11:22RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-20 Cont ID  
Sent By thunt Date 2019-03-20 Time 07:04 Rev Time 0.00
Received By thunt Date 2019-03-18 Time 12:51 Sent To  
Notes
2019-03-19 12:51:59PLUMB<5K