Plan Review Details - Permit 19030813
Plan Review Stops For Permit 19030813
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By jduprey Date 2019-03-25 Time 11:30 Rev Time 0.00
Received By jduprey Date 2019-03-25 Time 11:28 Sent To  
Notes
2019-03-25 11:45:22BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLEASE SUBMITT DESIGN DRAWINGS TO COMPLY WITH FBC
 107.2. THE EXTERIOR WALLS ARE SUBJECT TO WINDLOADS. WE
 HIGLY RECOMMEND GET A DESIGN FROM A REGISTER FLORIDA
 STATE ENGINEER.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By jpearson Date 2019-04-02 Time 12:44 Rev Time 0.00
Received By jpearson Date 2019-04-02 Time 12:44 Sent To  
Notes
2019-04-02 12:44:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE DETAILS OF
 EXISTING ELECTRICAL FOR THIS SPACE, AND DETAIL ANY
 CHANGES REQUIRED PER CODE. WPB FBC 107.2.1, 107.3.5; FS
 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By aborngra Date 2019-03-19 Time 16:27 Rev Time 0.00
Received By aborngra Date 2019-03-19 Time 16:23 Sent To PC
Notes
2019-03-19 16:26:57THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. A CERTIFICATE OF APPROPRIATENESS APPLICATION IS
 REQUIRED TO BE SUBMITTED. THE CASE MAY BE HEARD BY THE
 HISTORIC PRESERVATION BOARD.
  
 A CERTIFICATE OF APPROPRIATENESS IS A SEPARATE PROCESS
 FROM THE BUILDING PERMIT PROCESS. PLEASE VISIT - HTTP:/
 /WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/PLANNING/FORM
 S TO OBTAIN A COPY OF THE CERTIFICATE OF
 APPROPRIATENESS APPLICATION. PLEASE INCLUDE ALL
 INFORMATION REQUIRED UNDER "ADDITIONS: VISIBLE FROM THE
 STREET AND 10% OR LESS..." ON PAGE 2. A $40.00
 APPLICATION FEE WILL ALSO BE REQUIRED.
  
 PLEASE CONTACT STAFF TO DISCUSS PROPOSED ALTERATIONS.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-25 Cont ID  
Sent By jduprey Date 2019-03-25 Time 11:45 Rev Time 0.00
Received By jduprey Date 2019-03-18 Time 14:46 Sent To  
Notes
2019-03-19 14:46:35ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By aborngra Date 2019-03-19 Time 16:23 Rev Time 0.00
Received By aborngra Date 2019-03-19 Time 16:26 Sent To B
Notes
2019-03-19 16:26:34THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. A CERTIFICATE OF APPROPRIATENESS APPLICATION IS
 REQUIRED TO BE SUBMITTED. THE CASE MAY BE HEARD BY THE
 HISTORIC PRESERVATION BOARD.
  
 A CERTIFICATE OF APPROPRIATENESS IS A SEPARATE PROCESS
 FROM THE BUILDING PERMIT PROCESS. PLEASE VISIT - HTTP:/
 /WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/PLANNING/FORM
 S TO OBTAIN A COPY OF THE CERTIFICATE OF
 APPROPRIATENESS APPLICATION. PLEASE INCLUDE ALL
 INFORMATION REQUIRED UNDER "ADDITIONS: VISIBLE FROM THE
 STREET AND 10% OR LESS..." ON PAGE 2. A $40.00
 APPLICATION FEE WILL ALSO BE REQUIRED.
  
 PLEASE CONTACT STAFF TO DISCUSS PROPOSED ALTERATIONS.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  