Plan Review Details - Permit 19030784
| Plan Review Stops For Permit 19030784 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-24 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-24 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2019-06-24 07:52:45 | PROVISO: SUBMIT DOOR PRODUCT APPROVAL | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-08 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-05-08 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2019-05-08 07:02:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | COMMENTS FROM FIRST REVIEW: | | | | | | 1. FBC 107, PLAN IS NOT EASILY LEGIBLE AND WILL NOT BE | | | READABLE AFTER SCANNED DUE TO DRAWING ON DARK GRID | | | PAPER. PROVIDE A LEGIBLE PLAN. | | | | | | 2ND REVIEW, NOT ADDRESSED. | | | | | | 2. FBC 107, SCOPE OF WORK PROPOSED (OR DONE WITHOUT | | | PERMIT) IS NOT CLEAR. PROVIDE AN EXISTING PLAN, DEMO | | | PLAN, PROPOSED NEW PLAN, TO CLARIFY SCOPE. | | | | | | 2ND REVIEW, NOT ADDRESSED. ONLY ONE PLAN WAS PROVIDED - | | | PROVIDE AN EXISTING PLAN (THIS MEANS THE LEGALLY | | | PERMITTED CONDITIONS), DEMO PLAN (ITEMS DEMOLISHED | | | WITHOUT PERMIT), PROPOSED NEW PLAN TO CLARIFY SCOPE. | | | THE PLAN SHOULD ALSO CLARIFY WHERE IN THE HOUSE THIS | | | ROOM IS LOCATED. | | | | | | 3. FBC R 301, PROVIDE PRODUCT APPROVAL FOR THE EXTERIOR | | | DOOR. | | | | | | A PRODUCT APPROVAL WAS PROVIDED, BUT THE PLAN DOES NOT | | | SHOW A DOOR REPLACEMENT. | | | | | | NEW COMMENT: | | | | | | 4. ZACH LUCIO, PRECISION RENOVATIONS PROVIDED A | | | RESPONSE LETTER AND INDICATED THAT THEY WOULD COMPLETE | | | THE WORK. PROVIDE LICENSE INFORMATION FOR THIS | | | INDIVIDUAL, FS489. | | | | | | 5. FBC 109, PROVIDE THE COMPLETE VALUE FOR ALL NEW | | | WORK. THE CONTRACT SHOWS A VALUE OF $17,472 TO COMPLETE | | | WORK (BUT NOT CLEAR IF THAT PERSON IS LICENSED, SO | | | VALUE IS LIKELY LOW AS THAT COMPANY LIKELY DOES NOT | | | HAVE WORKERS COMP, GENERAL LIABILITY, ETC.). THE MARKET | | | VALUE FOR ALL WORK IS REQUIRED TO BE PROVIDED (THE | | | AMOUNT THAT A LICENSED CONTRACTOR WOULD CHARGE FOR THE | | | WORK INCLUDING MATERIALS, LABOR, OVERHEAD, PROFIT - | | | THIS SHOULD INCLUDE MATERIALS PROVIDED BY OWNER). | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-04 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-04 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2019-04-04 06:26:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, PLAN IS NOT EASILY LEGIBLE AND WILL NOT BE | | | READABLE AFTER SCANNED DUE TO DRAWING ON DARK GRID | | | PAPER. PROVIDE A LEGIBLE PLAN. | | | | | | 2. FBC 107, SCOPE OF WORK PROPOSED (OR DONE WITHOUT | | | PERMIT) IS NOT CLEAR. PROVIDE AN EXISTING PLAN, DEMO | | | PLAN, PROPOSED NEW PLAN, TO CLARIFY SCOPE. | | | | | | 3. FBC R 301, PROVIDE PRODUCT APPROVAL FOR THE EXTERIOR | | | DOOR. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-17 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-17 |
Time |
15:15 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-06-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-22 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-22 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2019-06-22 15:21:31 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. IT APPEARS | | | THAT THE SCOPE OF WORK CHANGED AND EXCLUDED THE | | | ELECTRICAL WORK. THE ELECTRICAL WORK PERFORMED ON SITE | | | HAS BEEN RED TAGGED AND REQUIRES A PLAN AND PERMIT. | | | PROVIDE ELECTRICAL PLAN FOR REVIEW FOR THE ELECTRICAL | | | PERMIT APPLICATION SUBMITTED AS AN ELECTRICAL | | | SUB-PERMIT FOR THIS JOB. WPB FBC 105.1, 107.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-06-22 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-04-30 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-04-30 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2019-06-22 15:17:43 | CHANGED TO FAIL, SEE 3RD REVIEW. JP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-03-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-03-28 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-03-28 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2019-03-28 09:47:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 210.8 REQUIRES AN OUTLET WITHIN 3' OF THE SINK. | | | | | | SWITCH LOCATION(S) NOT SHOWN FOR NEW LIGHTS AND FAN IN | | | BATHROOM. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-06-19 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-06-19 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-06-19 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2019-04-10 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2019-04-10 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-07-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-07-15 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2019-07-16 14:20:21 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-24 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-11 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-08 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-26 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-04-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-04-11 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-03-20 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-06-19 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-06-19 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-06-19 |
Time |
17:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-30 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-30 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2019-04-30 10:23:30 | PLUMBING 2ND REVIEW**DENIED** | | | | | | FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN | | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | | REVIEW. | | | | | | | | | 1) ***ANSWERED WITH NEW COMMENT*I UNDERSTAND THAT | | | PRECISION RENOVATIONS IS KNOW TAKING OVER THE ENTIRE | | | PROJECT PER THE SIGNED CONTRACT SUBMITTED. A CHANGE OF | | | CONTRACTOR FORM IS REQUIRED FOR ALL TRADES. | | | | | | 2) 2ND REQUEST: PROVIDE EXISTING FLOOR PLAN AS PER CITY | | | RECORDS UNDER PERMIT # 17030482 AND INSPECTORS PHOTOS | | | THERE IS SIGNIFICANT CHANGE TO THE FLOOR PLAN. FBC | | | 107.3.5. OWNER PURCHASED HOME ON 7/16/18, YOU CONTRACT | | | LIST YOUR FIRST SITE VISIT AS 10/1/18. THE FIELD | | | INSPECTOR FOUND WORKERS ON-SITE WORKING. ANY AND ALL | | | WORK UNPERMITTED WORK IS THE RESPONSIBILITY OF THE | | | CURRENT OWNER. PROVIDE AN EXISTING FLOOR PLAN AND A | | | PROPOSED FLOOR PLAN.FBC 107.3.5 | | | | | | 3) PROVIDE A COMPLETE SANITARY RISER ISOMETRIC SHOWING | | | ALL NEW WORK. FBC 107.3.5 | | | (A) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND | | | DRAWN UPON SUITABLE MATERIAL. RISER ISOMETRIC IS IN | | | PENCIL.PENCIL IS NOT PERMITTED. FBC 107.2.1 | | | (B) CONSTRUCTION DOCUMENTS SHALL BE SIGNED BY THE | | | PERSON TAKING RESPONSIBILITY F.S 471, 481, 489 | | | | | | 4) PROVIDE SHOWER PAN DETAIL AND PRODUCT BEING USED. | | | PROVIDE DRAWING OF PAN SHOWING PRE-PITCH @ 2% AND SHOW | | | CURB HEIGHT. FBC 107.2.1 | | | | | | 5) 2ND REQUEST:EXPOSE ALL WORK REQUIRING INSPECTION. IT | | | SHALL BE THE DUTY OF THE PERMIT APPLICANT TO CAUSE THE | | | WORK TO REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | | PURPOSES. WPB AMEND TO THE FBC 110.1 | | | (A)PLEASE PROVIDE A NARRATIVE ON HOW YOU INTENT TO | | | EXPOSE ALL COVERED WORK TO ALLOW THE CITY'S INSPECTION | | | STAFF TO PROPERLY PERFORM THE REQUIRED INSPECTIONS FBC | | | 110.1. | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-03 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-26 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-26 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2019-03-26 12:05:30 | PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) VALUE OF JOB SEEMS LOW WHEN COMPARED TO ENTIRE SCOPE | | | OF WORK. PROVIDE AN ACCURATE VALUATION OF ALL WORK AND | | | COST. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE | | | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION | | | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING | | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST | | | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS | | | PUBLISHED BY INTERNATIONAL (1)CODE CONGRESS. FINAL | | | BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING | | | OFFICIAL. | | | | | | 2) PROVIDE EXISTING FLOOR PLAN AS PER CITY RECORDS | | | UNDER PERMIT # 17030482 AND INSPECTORS PHOTOS THERE IS | | | SIGNIFICANT CHANGE TO THE FLOOR PLAN. FBC 107.3.5 | | | | | | 3) PROVIDE A COMPLETE SANITARY RISER ISOMETRIC SHOWING | | | ALL NEW WORK. FBC 107.3.5 | | | | | | 4) PROVIDE SHOWER PAN DETAIL AND PRODUCT BEING USED. | | | FBC 107.2.1 | | | | | | 5) EXPOSE ALL WORK REQUIRING INSPECTION. IT SHALL BE | | | THE DUTY OF THE PERMIT APPLICANT TO CAUSE THE WORK TO | | | REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES. | | | WPB AMEND TO THE FBC 110.1 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
|