Plan Review Details - Permit 19030749
Plan Review Stops For Permit 19030749
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-03 Cont ID  
Sent By fgiaquin Date 2019-04-03 Time 17:50 Rev Time 0.00
Received By fgiaquin Date 2019-04-03 Time 17:15 Sent To I
Notes
2019-04-03 17:50:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEVERAL DEVICES IN SUBMITTAL PACKET ARE NOT LISTED
 IN THE U.S. BY UL OR ANY OTHER NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL). PROVIDE CUT SHEETS SHOWING
 LISTED DEVICES. FBC 107.2.1 NEC 90.7.110.2, 110.3B
  
 INFORMATIONAL NOTE: CE IS NOT AN ACCEPTED NRTL IN THE
 U.S. CE IS A CANADIAN/EUROPEAN LISTING
  
 2. ALTRONIX POWER SUPPLY IS TO BE HARD WIRED PER
 MANUFACTURES INSTALLATION INSTRUCTIONS. NEC 110.3B
 ELECTRICAL PERMIT WILL BE REQUIRED BY LICENSED
 ELECTRICIAN FOR ALL 120V CIRCUITS AND CONNECTIONS TO
 NEW POWER SUPPLIES. F.S. 489.505 #7
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 4. SEPARATE LOW VOLTAGE AND ELECTRICAL PERMIT REQUIRED
 FOR EACH BUILDING WHERE WORK IS TO BE PERFORMED. ONE
 PLAN STATING "TYPICAL" FOR BUIDLINGS 1-20 WILL NOT
 SUFFICE. SUBMIT PLANS AND PERMIT APPLICATIONS WITH
 PROPER ADDRESSES FOR EACH BUILDING. FBC 107. F.S. 553
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-03 Cont ID  
Sent By fgiaquin Date 2019-04-03 Time 17:51 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
2019-03-18 14:10:13ROUTED TO ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved