Plan Review Details - Permit 19030681
Plan Review Stops For Permit 19030681
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 08:24 Rev Time 0.00
Received By jduprey Date 2019-04-30 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-03-28 Cont ID  
Sent By jduprey Date 2019-03-28 Time 09:22 Rev Time 0.00
Received By jduprey Date 2019-03-28 Time 08:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2019-04-09 Cont ID  
Sent By jpearson Date 2019-04-09 Time 09:51 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 09:17 Sent To  
Notes
2019-04-09 09:51:49NO ELECTRICAL SHEETS SUBMITTED FOR REVISION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-25 Cont ID  
Sent By bwoods Date 2019-03-25 Time 13:44 Rev Time 0.00
Received By bwoods Date 2019-03-25 Time 13:44 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 08:24 Rev Time 0.00
Received By jduprey Date 2019-04-17 Time 15:16 Sent To  
Notes
2019-04-18 15:17:05RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-14 Time 11:00 Sent To  
Notes
2019-03-15 11:00:36C02

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-29 Cont ID  
Sent By tklarge Date 2019-04-29 Time 11:15 Rev Time 0.00
Received By tklarge Date 2019-04-29 Time 11:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By gjohnson Date 2019-04-09 Time 07:46 Rev Time 0.00
Received By tklarge Date 2019-04-08 Time 10:12 Sent To  
Notes
2019-04-08 10:15:521) THE NARRATIVE FOR SHT.A-1.5 STATES "ROOF DRAIN
 RELOCATION" BUT I DO NOT SEE ANY ROOF DRAINS ON THE
 PLAN. CLARIFY.
 2) SHT. A-6.5.1 & A-6.5.2 - DETAIL "A" - A 30 INCH BY
 48 INCH CLEAR FLOOR SPACE IS REQUIRED OUTSIDE THE SWING
 OF THE DOOR PER THE FAIR HOUSING DESIGN MANUAL. CLEARLY
 SHOW THIS CLEAR FLOOR SPACE ON THE DETAIL.
 3) SHT. A-9.1 - THERE ARE TWO FIRESTOP DETAILS THAT DO
 NOT SHOW ANY SYSTEM NUMBER AND ONE DOES NOT HAVE ANY F
 RATING ON THE DETAIL. SUBMIT THE REQUIRED INFORMATION.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A-9.2 - SUPPLY THE SYSTEM NUMBER FOR THE 2 HOUR
 FIRESTOP SYSTEM DETAIL. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. A-9.3 - THERE ARE NO SYSTEM NUMBERS ON ANY OF
 THE FIRESTOP DETAILS. SUPPLY ALL THE REQUIRED
 INFORMATION. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  