Plan Review Details - Permit 19030671
Plan Review Stops For Permit 19030671
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-02 Cont ID  
Sent By jwitmer Date 2019-04-02 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2019-04-02 Time 10:10 Sent To  
Notes
2019-04-02 10:59:27BUILDING PROVISO:
 CONSTRUCTION TRAILER WILL NEED STAIRS, LANDING AND
 HANDRAIL
 TO COMPLY WITH THE 2017 FBC-BUILDING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By jpearson Date 2019-05-08 Time 07:42 Rev Time 0.00
Received By jpearson Date 2019-05-08 Time 07:42 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-02 Cont ID  
Sent By jpearson Date 2019-05-02 Time 07:59 Rev Time 0.00
Received By jpearson Date 2019-05-02 Time 07:59 Sent To I
Notes
2019-05-02 07:59:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FYI, I DO NOT NEED
 THE RISER FOR THE PROJECT BEING BUILT, ONLY FOR THE
 TEMPORARY SERVICE. PROVIDE CORRECTION. WPB FBC 107.1,
 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By jpearson Date 2019-04-08 Time 13:24 Rev Time 0.00
Received By jpearson Date 2019-04-08 Time 12:50 Sent To I
Notes
2019-04-08 13:24:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM FOR TEMP SERVICE, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By scaldero Date 2019-04-16 Time 10:14 Rev Time 0.00
Received By scaldero Date 2019-04-16 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By scaldero Date 2019-03-18 Time 09:44 Rev Time 0.00
Received By scaldero Date 2019-03-18 Time 09:37 Sent To  
Notes
2019-03-18 09:44:35PERMIT # 19030671
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) ADDRESS OF PROJECT NOT PROVIDED IN THE PLAN
 TITLEBLOCK INFORMATION OR ANYWHERE ELSE ON THE
 SUBMITTED PLAN SHEETS.
  
 2) A SITE PLAN WAS NOT PROVIDED WITH THIS SUBMISSION.
  
 3) TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-05-08 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-06 Time 13:22 Sent To  
Notes
2019-05-07 13:22:23RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-05-02 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-09 Time 15:52 Sent To  
Notes
2019-04-10 15:52:38B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-08 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-14 Time 10:30 Sent To  
Notes
2019-03-15 10:30:38B20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-04-02 Cont ID  
Sent By jwitmer Date 2019-04-02 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2019-04-02 Time 10:59 Sent To  
Notes
2019-04-02 11:00:35SELF CONTAINED UNIT STATE APPROVED PLANS. JW
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-04-02 Cont ID  
Sent By jwitmer Date 2019-04-02 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2019-04-02 Time 11:00 Sent To  
Notes
2019-04-02 11:01:25NO PLUMBING IN CONSTRUCTION TRAILER, STATE APPROVED
 PLAN. JW

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-22 Cont ID  
Sent By awooten Date 2019-04-22 Time   Rev Time 0.00
Received By awooten Date 2019-04-22 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By awotten Date 2019-03-28 Time   Rev Time  
Received By awooten Date 2019-03-28 Time   Sent To  
Notes
2019-03-28 10:16:22**********************************ZONING REVIEW
 FAILED****************************
  
 PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 CONSTRUCTION TRAILER, ALL SETBACKS AND SURROUNDINGS ON
 PROPERTY.
  
 ADDITIONAL COMMENTS MAY RESULT FROM FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]