Plan Review Details - Permit 19030631
Plan Review Stops For Permit 19030631
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-01 Cont ID  
Sent By pvalenti Date 2019-05-01 Time 15:37 Rev Time 0.00
Received By pvalenti Date 2019-05-01 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By jleahy Date 2019-04-25 Time 15:37 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 15:37 Sent To  
Notes
2019-04-25 15:42:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CONTRACT COPY STATES NO OPTIONS DECK, LIGHT, DIAMOND
 BLUE GUNITE NOT INCLUDED WITH VALUE AND ANY OTHER
 OPTION INCLUDED SHALL BE INCLUDED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By jleahy Date 2019-03-28 Time 08:18 Rev Time 0.00
Received By jleahy Date 2019-03-28 Time 08:16 Sent To  
Notes
2019-03-28 08:21:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 POOL PANEL ?
  
 WHAT SIZE WIRE TO POOL PANEL, WHAT SIZE POOL PANEL?
  
 VALUE FOR WORK TO LOW PLEASE SUBMIT A SIGNED CONTRACT
 FOR POOL.
  
 SUBMIT SPECS FOR POOL LIGHT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-01 Cont ID  
Sent By pvalenti Date 2019-05-01 Time 15:40 Rev Time 0.00
Received By pvalenti Date 2019-04-19 Time 13:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 14:16 Rev Time 0.00
Received By pvalenti Date 2019-03-14 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 11:59 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 11:51 Sent To  
Notes
2019-04-24 11:59:37NO VAC LINE SHOWN ON PLAN. REVISION REQUIRED IF VAC
 LINE IS INSTALLED

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 13:14 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 12:42 Sent To  
Notes
2019-04-05 13:14:04PLUMBING 1ST REVIEW**DENIED**
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
  
 2) PROVIDE MAIN DRAIN DETAIL SHOWINF G.P.M AND THAT
 THEY COMPLY WITH V.G.B. FBC R 4501.6.6, 4501.21.3
  
 3) VALUE SEEMS LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-23 Cont ID  
Sent By jroach Date 2019-04-23 Time 13:36 Rev Time 0.00
Received By jroach Date 2019-04-23 Time 13:36 Sent To  
Notes
2019-04-23 13:37:02PROVISOS
  
 1. POOL EQUIPMENT SHALL BE AT LEAST ONE (1) FOOT FROM
 THE SIDE PROPERTY LINE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-27 Cont ID  
Sent By jroach Date 2019-03-27 Time 09:40 Rev Time 0.00
Received By jroach Date 2019-03-27 Time 09:40 Sent To  
Notes
2019-03-27 09:41:09PROVISOS
  
 1. POOL EQUIPMENT SHALL BE AT LEAST ONE (1) FOOT FROM
 THE SIDE PROPERTY LINE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  