Plan Review Details - Permit 19030628
Plan Review Stops For Permit 19030628
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By jduprey Date 2019-05-17 Time 14:13 Rev Time 0.00
Received By jduprey Date 2019-05-17 Time 14:03 Sent To  
Notes
2019-05-17 14:13:07PROVISO
  
 PLEASE PROVIDE THE DEFFERED SUBMITTALS APPROVED BY THE
 DESIGNER OF RECORD. FBC 107.3.4; FBC 107.3.4.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 16:43 Rev Time 0.00
Received By cthroop Date 2019-04-05 Time 09:54 Sent To  
Notes
2019-04-10 17:01:24BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE WAS ADJUSTED FROM $42,500 TO $54,249 BASED ON
 THE ICC BUILDING VALUATION DATA PUBLISHED FEBRUARY
 2019.
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 3. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 4. ROOFING PERMIT REQUIRED. FBC 105.
  
 5. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. PROVIDE PRODUCT APPROVALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR AND
 MECHANICAL C/U TIE DOWN SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By ppetty Date 2019-04-30 Time 12:52 Rev Time 0.00
Received By ppetty Date 2019-04-30 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By jpearson Date 2019-04-04 Time 15:11 Rev Time 0.00
Received By jpearson Date 2019-04-04 Time 13:24 Sent To  
Notes
2019-04-04 15:11:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 14:25 Sent To  
Notes
2019-04-25 14:31:25ALL THE MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR NATURAL GAS TANKLESS WATER
 HEATER AND REGULATORS INCLUDING SHALL BE ON JOBSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. FAILURE TO COMPLY WILL RESULT IN A FAILED
 INSPECTION AND FEE'S
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 12:38 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 12:38 Sent To  
Notes
2019-04-01 12:38:57GAS 1ST REVIEW**DENIED**
  
 1) PROVIDE TANKLESS WATER HEATER COMPLETE INSTALLATION
 MANUAL. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 2) PROVIDE DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 4) PROVIDE SHUT OFF VALVE AND SEDIMENT TRAP AT THE
 TANKLESS. FBC G 409.5.1, 408.4
  
 5) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 6) SIZING TABLE CALLED OUT 402.4(2) ON P-003 LIST MAX
 BTU @ 20' AS 118,000 BTU'S. YOUR PROPOSED 1/2" SCH 40
 METAL PIPE WOULD BE UNDERSIZED FOR 150000 BTU'S. TOTAL
 MUST INCLUDE THE VERTICAL PIPING IN DISTANCE.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-03 Cont ID  
Sent By mcruz Date 2019-06-03 Time 15:56 Rev Time 0.00
Received By mcruz Date 2019-04-17 Time 15:23 Sent To PC
Notes
2019-04-18 15:23:33R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 17:05 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 15:08 Sent To  
Notes
2019-03-14 15:08:18R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By jduprey Date 2019-05-17 Time 14:05 Rev Time 0.00
Received By jduprey Date 2019-05-17 Time 14:04 Sent To  
Notes
2019-05-17 14:05:07MU-2019-011572-0000
 $180.65 PAID

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 17:01 Rev Time 0.00
Received By cthroop Date 2019-04-05 Time 09:54 Sent To  
Notes
2019-04-10 17:02:35IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 07:09 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 07:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 17:05 Rev Time 0.00
Received By cthroop Date 2019-04-05 Time 09:54 Sent To  
Notes
2019-04-10 17:34:07MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. PROVIDE MECHANICAL EQUIPMENT SPECIFICATIONS.
 RE403.7HEATING AND COOLING EQUIPMENT (MANDATORY).
 RE403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
 3. MECHANICAL EQUIPMENT SCHEDULE SPECIFIES COMFORT AIR
 OR EQUIVALENT. IF EQUIPMENT IS NOT COMFORT AIR, A
 REVISION TO THESE PLANS WILL BE REQUIRED COMPLYING WITH
 NOTE #2 ABOVE.
  
 4. PROVIDE PRODUCT APPROVAL FOR C/U TIE DOWN PER NOTE
 ON PLAN PAGE M-001.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE MECH. C/U TIE DOWN SUBMITTALS.
  
 5. AIR HANDLER ON PLAN PAGE M-002 IS MISLABLED. SHOULD
 BE LABLED AHU-1.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE STATEMENT ON PLAN FOR TAMPER PROOF LINE PORT
 CAPS.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 14:24 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 09:01 Sent To  
Notes
2019-04-25 14:25:35APPROVED BY TIM HUNT ON 4/1/19

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 12:46 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 12:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-05-17 Cont ID  
Sent By jduprey Date 2019-05-17 Time 14:05 Rev Time 0.00
Received By jduprey Date 2019-05-17 Time 14:05 Sent To  
Notes
2019-05-17 14:06:33PROVISO
  
 1. ROOFING PERMIT REQUIRED. FBC 105
  
 2. PROVIDE PRODUCT APPROVALS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-04-05 Time 09:55 Sent To  
Notes
2019-04-10 17:05:10BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED. FBC 105
  
 2. PROVIDE PRODUCT APPROVALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By mcruz Date 2019-06-03 Time 15:56 Rev Time 0.00
Received By mcruz Date 2019-06-03 Time 15:53 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By mcruz Date 2019-03-26 Time 15:16 Rev Time 0.00
Received By mcruz Date 2019-03-26 Time 14:41 Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy