| 2019-04-01 14:20:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET T 1 - THERE ARE INDICATIONS OF FIRE SPRINKLER |
| | AND FIRE ALARM NOTES WITH WORK UNDER SEPARATE SHOP |
| | DRAWINGS; HOWEVER, NOTHING ABOUT MAINTAINING EITHER |
| | SYSTEMS WHILE UNDER DEMO & CONSTRUCTION. |
| | |
| | THE FS AND FA SYSTEMS SHALL REMAIN FUNCTIONAL AND BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION. |
| | |
| | PLEASE ENSURE AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 2) SHEETS A 1 & A 3 - DOOR 01 SWINGS OUT INTO THE EXIT |
| | CORRIDOR WHICH DOES NOT APPEAR TO ENCROACH INTO THE |
| | REQUIRED EGRESS WIDTH: HOWEVER, THE DOOR SWINGS AT 90'. |
| | |
| | PER NFPA 101 THE DOOR IS REQUIRED TO SWING 180' |
| | |
| | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, |
| | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, |
| | UNLESS BOTH |
| | OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING |
| | BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF |
| | 7.2.1.4.3.2. |
| | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS |
| | SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE |
| | REQUIRED WIDTH |
| | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, |
| | UNLESS THE DOOR |
| | LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE |
| | AND IS NOT |
| | REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE |
| | DIRECTION OF |
| | EGRESS TRAVEL. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 02 |
| | HARDWARE AS HAVING A KEY. THIS DOOR IS INDICATED AS AN |
| | EXIT DOOR. |
| | |
| | PER NFPA 101 CH 38 & 7 |
| | |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 4) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 01 |
| | HARDWARE AS HAVING A KEY AND DEADBOLT. THIS DOOR IS |
| | INDICATED AS AN EXIT DOOR. |
| | |
| | PER NFPA 101 CH 38 & 7 |
| | |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 5) SHEET LS 1 & A 4 - DOOR 04 IS INDICATED AS AN EXIT |
| | THAT IS LEADING TO AN AREA AS FUTURE EXPANSION. |
| | |
| | HOW WILL THIS EXIT BE CONTROLLED AND MAINTAINED AND |
| | FUNCTION AS AN EXIT? |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |