Plan Review Details - Permit 19030580
Plan Review Stops For Permit 19030580
Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-04-17 Cont ID  
Sent By rrossano Date 2019-04-17 Time   Rev Time 0.00
Received By rrossano Date 2019-04-17 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-04-03 Cont ID  
Sent By rrossano Date 2019-04-03 Time   Rev Time 0.00
Received By rrossano Date 2019-04-03 Time   Sent To I
Notes
2019-04-03 07:33:49PLEASE ADDRESS FIRE COMMENTS.
  
 PLEASE PROVIDE WATER, SEWER, STORMWATER
 ELEVATIONS/SEPARATIONS AT CONFLICT POINTS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By rrossano Date 2019-03-18 Time   Rev Time  
Received By rrossano Date 2019-03-18 Time   Sent To I
Notes
2019-03-18 06:42:39PLEASE SUBMIT PLANS.
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-04-18 Cont ID  
Sent By scaldero Date 2019-04-18 Time 15:14 Rev Time 0.00
Received By scaldero Date 2019-04-18 Time 15:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-17 Cont ID  
Sent By scaldero Date 2019-04-17 Time 14:37 Rev Time 0.00
Received By scaldero Date 2019-04-17 Time 14:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-03-25 Cont ID  
Sent By scaldero Date 2019-03-25 Time 08:57 Rev Time 0.00
Received By scaldero Date 2019-03-25 Time 08:18 Sent To  
Notes
2019-03-25 08:57:31PERMIT # 19030580
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 2) SHOP DRAWINGS WERE SUBMITTED FOR A DOUBLE CHECK
 VALVE ASSEMBLY HOWEVER THE INSTALLATION LOCATION FOR
 THIS ASSEMBLY IS NOT IDENTIFIED ON ANY OF THE DRAWINGS
 PROVIDED. PLEASE MARK THE LOCATION OF THE DDCV TO
 ENSURE COMPLIANCE WITH THE
 REQUIREMENTS OF NFPA 24.
  
 3) PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO
 PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS
 SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 4) JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 5) CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 6) ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 7) FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1,
 THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 8) HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT
 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING
 PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT
 PRESSURE +/-5 PSI FOR 2 HOURS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By sathomas Date 2019-03-15 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-03-15 Time 00:00 Sent To M
Notes
2019-03-15 10:47:51NO PLANS SUBMITTED IN PACKET.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-18 Cont ID  
Sent By lmarchan Date 2019-04-18 Time 16:42 Rev Time 0.00
Received By lmarchan Date 2019-04-18 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-18 Cont ID  
Sent By shill Date 2019-04-18 Time 10:24 Rev Time 0.00
Received By shill Date 2019-04-11 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-21 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-18 Cont ID  
Sent By cpuell Date 2019-03-18 Time 09:04 Rev Time 0.00
Received By cpuell Date 2019-03-13 Time 14:15 Sent To  
Notes
2019-03-14 14:15:12ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-18 Cont ID  
Sent By ccole Date 2019-04-18 Time 08:31 Rev Time 0.00
Received By ccole Date 2019-04-18 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-03 Cont ID  
Sent By ccole Date 2019-04-03 Time 17:05 Rev Time 0.00
Received By ccole Date 2019-04-03 Time 17:05 Sent To I
Notes
2019-04-03 17:25:55 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030580
 4/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER. REQUIREMENTS FOR BACKFLOW PREVENTER
 PERMITTING CAN BE FOUND UNDER "FORMS" ON THE CITY OF
 WEST PALM BEACH WEB SITE. THE FORM IS TITLED "BACKFLOW
 PREVENTION DEVICE PERMIT REQUIREMENTS". FOLLOW THE
 LINKS TO DEVELOPMENT SERVICES TO FIND FORMS.
  
 2) PLEASE PROVIDE SUBMITTALS FOR THE UNDERGROUND
 PIPING, PIPE FITTINGS, AND JOINT RESTRAINT SYSTEM .
 PLEASE NOTE THAT MATERIAL DATA SHEETS SHALL BE PROVIDED
 TO THE ON-SITE INSPECTOR TO INDICATE CORRECT TORQUE
 WRENCH SETTINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By cmontell Date 2019-03-15 Time 13:34 Rev Time 0.00
Received By cmontell Date 2019-03-15 Time 13:33 Sent To ENG
Notes
2019-03-15 13:33:55MECHANICAL PLAN REVIEW FAIL
  
 1 NO PLANS
  
 CHRIS MONTELLO
 8056733

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-04-18 Cont ID  
Sent By shill Date 2019-04-18 Time 15:08 Rev Time 0.00
Received By shill Date 2019-04-18 Time 15:08 Sent To  
Notes
2019-04-18 15:09:28PROVISO: ENGINEER TO COMPLY WITH FAC61G15-23.004
 EMAIL TO ENGINEER SENT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By shill Date 2019-04-18 Time 10:19 Rev Time 0.00
Received By shill Date 2019-04-18 Time 05:46 Sent To  
Notes
2019-04-18 05:50:30SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENT FROM FIRST REVIEW:
  
 1. CIVIL PAGES ARE DIGITALLY SIGNED BY BRITT L.
 STEPHENS. SEE FS471, FAC61G15-23.002; A SEAL AND
 PRINTED LICENSE NUMBER IS REQUIRED. AN IMAGE OF A SEAL
 IS ACCEPTABLE TO SATISFY BOTH REQUIREMENTS.
  
 SECOND REVIEW:
  
 IT IS NOT CLEAR IF THE COMMENT WAS PROPERLY CONVEYED TO
 THE ENGINEER AS THE REPONSE NARRATIVE STATES THAT THIS
 IS COMMENT #2 FOR ENGINEERING. IT IS ALSO NOT CLEAR IF
 THE ENGINEER DISAGREES WITH THE COMMENT AS THE RESPONSE
 STATES "PLEASE SEE THE ATTACHED PLANS WITH REQUESTED
 SEAL." OF THE 13 PAGES SIGNED BY THE ENGINEER, ONLY TWO
 NEW PAGES WERE UPLOADED, ALL PAGES ARE DIGITALLY SIGNED
 BUT LACK A SEAL.
  
 PLEASE SEE FAC61G15-23.004 FOR LANGUAGE REQUIRED TO BE
 INCLUDED IN THE DIGITAL SIGNATURE.
  
 AS DISCUSSED WITH BILL DUFFY AND DAVID PELLEGRI, THIS
 ISSUE WILL NOT DELAY ISSUANCE OF THIS PERMIT, BUT
 ENGINEER IS TO COMPLY IN THE FUTURE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By shill Date 2019-04-02 Time 18:24 Rev Time 0.00
Received By shill Date 2019-04-02 Time 18:24 Sent To  
Notes
2019-04-02 18:26:23SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CIVIL PAGES ARE DIGITALLY SIGNED BY BRITT L.
 STEPHENS. SEE FS471, FAC61G15-23.002; A SEAL AND
 PRINTED LICENSE NUMBER IS REQUIRED. AN IMAGE OF A SEAL
 IS ACCEPTABLE TO SATISFY BOTH REQUIREMENTS.
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-04-18 Cont ID  
Sent By rcaranci Date 2019-04-18 Time 16:16 Rev Time 0.00
Received By rcaranci Date 2019-04-18 Time 16:15 Sent To  
Notes
2019-04-18 16:17:08VERSION 3 OF DRAWING C-600 PASSED ZONING REVIEW.
 STAMPED BY MARGARITA CRUZ.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-04-18 Cont ID  
Sent By rcaranci Date 2019-04-18 Time 16:15 Rev Time 0.00
Received By rcaranci Date 2019-04-18 Time 16:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-17 Cont ID  
Sent By rcaranci Date 2019-04-17 Time 13:52 Rev Time 0.00
Received By rcaranci Date 2019-04-17 Time 13:52 Sent To  
Notes
2019-04-17 13:54:20THE CONFLICT HAS NOT BEEN CORRECTED. THERE ARE 3 DATE
 PALMS, TWO THAT ARE RELOCATED. THIS WAS A CONDITION OF
 APPROVAL THAT THE 2 PALMS BE PLACED BACK CLOSE TO THEIR
 ORIGINAL POSITIONS AFTER THE BUILDING WAS CONSTRUCTED,
 AND THE THIRD PALM WAS TO REMAIN IN PLACE. THE
 LOCATIONS OF THE WATER AND FIRE LINES NEED TO BE
 ADJUSTED. PLEASE WORK WITH THE LANDSCAPE ARCHITECT TO
 RESOLVE THE PROBLEM.
 ALSO NOTE THAT A SEPARATE PERMIT IS NEEDED FOR
 LANDSCAPING.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By eschneid Date 2019-03-22 Time 10:59 Rev Time 0.25
Received By eschneid Date 2019-03-22 Time 10:59 Sent To  
Notes
2019-03-22 11:03:19FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE PROPOSED NEW FIRE SERVICE AND WATER SERVICE
 LINES APPEAR TO BE IN DIRECT CONFLICT WITH TWO REQUIRED
 PALMS. PROVIDE A PLAN SHOWING THE LINES AND THE PALMS
 WITH ADEQUATE SEPARATION FROM THE PROPOSED AND EXISTING
 UTILITIES IN THE AREA. COORDINATE WITH YOUR THE
 LANDSCAPE ARCHITECT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]