Plan Review Details - Permit 19030548
Plan Review Stops For Permit 19030548
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-06-19 Cont ID  
Sent By fgiaquin Date 2019-06-19 Time 07:15 Rev Time 0.00
Received By fgiaquin Date 2019-06-19 Time 07:11 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-04-23 Cont ID  
Sent By fgiaquin Date 2019-04-23 Time 17:01 Rev Time 0.00
Received By fgiaquin Date 2019-04-23 Time 16:53 Sent To M
Notes
2019-04-23 17:01:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-21 Cont ID  
Sent By fgiaquin Date 2019-03-21 Time 06:31 Rev Time 0.00
Received By fgiaquin Date 2019-03-21 Time 06:04 Sent To M
Notes
2019-03-21 06:31:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS SUBMITTED ARE FROM INTEGRATED SECURITY SYSTEMS
 (ISS). PERMIT APPLICATION IS FROM MCFARLAND ELECTRICAL
 SERVICES. ISS IS NOT SHOWN TO BE A DBA OF MCFARLAND
 ELECTRICAL SERVICES. PLEASE EXPLAIN AND PROVIDE
 VERIFICATION FOR WHO IS EXACTLY PERFORMING THE WORK.
 FBC 107.2.1
  
 2. DIGITAL SIGNATURES ARE NOT VALID ON PHYSICALLY
 TRANSMITTED DOCUMENTS. PLEASE SEE REQUIREMENTS BELOW
 FOR SIGNATURES AND SEALS FROM DESIGN PROFESSIONALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By fgiaquin Date 2019-03-21 Time 05:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-06-10 Cont ID  
Sent By pleduc Date 2019-06-10 Time   Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 13:27 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By pleduc Date 2019-04-16 Time   Rev Time 0.00
Received By pleduc Date 2019-04-16 Time 09:56 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-14 Cont ID  
Sent By pleduc Date 2019-03-14 Time   Rev Time 0.00
Received By pleduc Date 2019-03-14 Time 12:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-19 Cont ID  
Sent By hmoser Date 2019-06-19 Time 15:43 Rev Time 0.00
Received By hmoser Date 2019-06-07 Time 10:55 Sent To  
Notes
2019-06-10 10:55:53RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-24 Cont ID  
Sent By cmontell Date 2019-04-24 Time 14:02 Rev Time 0.00
Received By cmontell Date 2019-04-24 Time 14:02 Sent To  
Notes
2019-04-12 16:04:24RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-06 Cont ID  
Sent By cmontell Date 2019-04-06 Time 06:48 Rev Time 0.00
Received By cmontell Date 2019-04-06 Time 06:48 Sent To  
Notes
2019-03-13 11:18:45ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-19 Cont ID  
Sent By hmoser Date 2019-06-19 Time 15:42 Rev Time 0.00
Received By hmoser Date 2019-06-19 Time 15:42 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By cmontell Date 2019-04-24 Time 14:01 Rev Time 0.00
Received By cmontell Date 2019-04-24 Time 14:01 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-06 Cont ID  
Sent By cmontell Date 2019-04-06 Time 06:47 Rev Time 0.00
Received By cmontell Date 2019-04-06 Time 06:45 Sent To I
Notes
2019-04-06 06:47:43MECHANICAL PLAN REVIEW FAIL
  
 1 - SEE ELECTRICAL COMMENTS
  
 CHRIS MONTELLO
 805-6733