| 2019-04-22 14:18:53 | PLUMBING 2ND REVIEW**DENIED** |
| | |
| | 1) PROVIDE PLAN SHOWING EXISTING POOL IS EITHER ALREADY |
| | COMPLYING WITH OR THAT YOUR PLAN ON MODIFICATION TO |
| | MAKE IT COMPLY WITH THE FOLLOWING SECTIONS:FBC 454.1 |
| | |
| | 454.1.10.1.1 THE LIP OF THE GUTTER MUST BE LEVELED TO |
| | WITHIN 1/4 INCH (6.4 MM) BETWEEN THE HIGHEST AND LOWEST |
| | POINT AND THE DOWNWARD SLOPE FROM THE LIP TO THE DRAIN |
| | MUST BE MAINTAINED AS ORIGINALLY DESIGNED OR INCREASED, |
| | BUT SHALL NOT EXCEED NEW CONSTRUCTION STANDARDS. |
| | |
| | 454.1.10.1.2 TILE STEP MARKINGS MUST BE INSTALLED |
| | MEETING THE REQUIREMENTS OF SECTION 454.1.2.5.3. |
| | |
| | 454.1.10.1.3 WHERE APPLICABLE THE SLOPE BREAK MARKING |
| | MUST BE INSTALLED MEETING THE REQUIREMENTS OF SECTION |
| | 454.1.2.2.3.2 AND SAFETY LINE MUST BE INSTALLED 2 FEET |
| | (610 MM) BEFORE THE MARKING. |
| | |
| | 454.1.10.1.4 DEPTH MARKERS AND NO DIVING MARKERS MUST |
| | BE INSTALLED IN ACCORDANCE WITH SECTION 454.1.2.3. |
| | |
| | 454.1.10.1.5 THE POOL LADDER MUST HAVE A 3 TO 6 INCH |
| | (76 TO 152 MM) CLEARANCE FROM THE POOL WALL. NEW CROSS |
| | BRACED LADDER(S) SHALL BE INSTALLED IN PLACE OF NON |
| | CROSS-BRACED LADDER(S) IN CONFORMANCE WITH SECTION |
| | 454.1.2.5.1 DURING A POOL RESURFACING. |
| | |
| | 454.1.10.1.6 SHOULD RESURFACING WORKS AFFECT THE STEP |
| | RISER HEIGHTS, NO RISER SHALL EXCEED 10 INCHES (254 MM) |
| | FOR POOLS AND 12 INCHES (305 MM) FOR SPAS, AND THE |
| | INTERMEDIATE RISERS SHALL BE MADE UNIFORM. |
| | |
| | 454.1.10.1.7 STEP TREADS THAT PROTRUDE FROM THE POOL |
| | WALL SHALL BE REMOVED AND REPLACED WITH A CROSS-BRACED |
| | LADDER OR RECONSTRUCTED TO MEET THE REQUIREMENTS OF |
| | SECTIONS 454.1.2.5.1 OR 454.1.2.5.2. |
| | |
| | 2) PROVIDE MANUFACTURES INSTALLATION MANUALS FOR THE |
| | NEW POOL PUMP, HEAT PUMP, SALT SYSTEM FBC 107.2.1 |
| | |
| | 3) PROVIDE PIPING ISOMETRIC DRAWING FOR THE NEW SALT |
| | SYSTEM, HEAT PUMP. FBC 107.2.1 |
| | |
| | 4) NO INSTALLATION MANUAL PROVIDE FOR THE MAIN DRAIN |
| | COVERS., FBC 107.2.1 |
| | |
| | |
| | |