Plan Review Details - Permit 19030476
Plan Review Stops For Permit 19030476
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By cthroop Date 2019-03-12 Time 07:00 Rev Time 0.00
Received By cthroop Date 2019-03-12 Time 06:57 Sent To  
Notes
2019-03-12 07:06:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 **ADDITIONAL REQUIREMENTS PER ROBERT BROWN, BUILDING
 OFFICIAL, CITY OF WEST PALM BEACH
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 GENERAL BUILDING CODE REQUIREMENTS FOR TEMPORARY
 MEMBRANE STRUCTURES
  
 APPLICANTION CHECKLIST
 ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS,
 GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS
 * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS
 PRIOR TO EVENT
 1. PERMIT APPLICATION
 A. PROVIDE EVENT FUNCTION
  B. ADDRESS OF EVENT
  C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS
 D. OWNER AND CONTRACTOR INFO.
  E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER
  F. SPECIFY DATES OF INSTALLATION AND REMOVAL
 2. SITE PLAN
  A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE?
  B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER
 FBC CHPT. 6, SEC. 602
  C. PROVIDE SQUARE FOOTAGE
  D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT
  E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT
 ENTRANCE
  F. IDENTIFY MEANS OF EGRESS PER CHPT. 10
  G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE
 RESTROOMS
  H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500
 FEET OF TENT
 2. FOUNDATION/TIE DOWN
  A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT
  B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL
 MOVEMENT
 3. CONFORMANCE PER SECTION 3103.1.1
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT
 C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN
 REQUIRED.
  2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
  A) STATE OCCUPANT LOAD.
  B) IDENTIFY MEANS OF EGRESS.
  C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO
 EXIT.
  D) PROVIDE FLOOR LAYOUT OF EVENT.
  D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE
 PLAN
  E. LIGHT 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
  F. VENTILATION 1) OPEN SIDES ? N/A
  2) CLOSED SIDES ? PER SEC. 1203
  G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES
 ON SITE PLAN
  2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By scaldero Date 2019-03-12 Time 09:15 Rev Time 0.00
Received By scaldero Date 2019-03-12 Time 08:52 Sent To  
Notes
2019-03-12 09:15:12PERMIT #19030476
 FIRE REVIEW COMMENTS
  
 FAIL COMMENTS:
  
 1) THE OCCUPANT LOAD FOR THE 40 X 100 TENT SHALL COMPLY
 WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101:
 CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY
 USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15
 SQ FT/PERSON.
 BASED ON THE INFORMATION PROVIDED AND THE SEATING
 ARRANGEMENT THAT INDICATES 120 PERSONS, THE OCCUPANT
 LOAD IS BEING EXCEEDED FOR THIS SIZE TENT.
  
 2) 1)SEATING SHALL BE ARRANGED IN A MANNER THAT
 COMPLIES WITH THE AISLE AND AISLEWAY REQUIREMENTS AS
 LISTED UNDER NFPA 101: 12.2.5 (ARRANGEMENT OF MEANS OF
 EGRESS).
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-01 Cont ID  
Sent By shill Date 2019-03-12 Time 07:33 Rev Time 0.00
Received By shill Date 2019-03-11 Time 16:30 Sent To  
Notes
***NONE***