| Plan Review Stops For Permit 19030461 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-03 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-03 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-10 |
Time |
06:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-10 |
Time |
06:13 |
Sent To |
|
|
| Notes |
| 2019-04-10 06:15:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE TENANT SPACE NUMBER AND NAME ON THE | | | APPLICATION, FBC 107. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-03 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-03 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2019-06-03 13:35:47 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING 2ND PLAN REVIEW | | | | | | APPROVED WITH PROVISO: | | | | | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | | BE USED. | | | | | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-16 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-16 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2019-04-16 13:46:52 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING PLAN REVIEW DENIED: | | | | | | FBC B 107 : | | | | | | 1. THE PLANS INCLUDING MATERIAL SUBMITTALS NEED TO HAVE | | | CITY PLACE APPROVAL STAMP PRIOR TO BUILDING REVIEW. | | | | | | NOTE: WELDING PROCEDURE SPECIFICATION AND WELDER | | | QUALIFICATION RECORDS WILL BE REQUIRED ON SITE AT TIME | | | OF INSPECTION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-28 |
Time |
12:44 |
Sent To |
B |
|
| Notes |
| 2019-05-28 12:47:05 | 5/28/19 | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THE EXISITNG FIRE SPRINKLER COVERAGE SHALL BE | | | EXENDED TO BELOW THE PROPOSED CANOPY, AS WELL AS, | | | REMAIN PROPOER COVERAGE ON TOP OF THE CANOPY. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | 2) ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE | | | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-04-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-11 |
Time |
14:16 |
Sent To |
B |
|
| Notes |
| 2019-04-11 14:22:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO INDICATIONS OF AN EXISTING FIRE | | | SPRINKLER SYSTEM OVER THE BAR AREA. | | | | | | THE PROPOSED CANOPY WOULD OBSTRUCT THE EXISTING FIRE | | | SPRINKLER COVERAGE. ADDITIONALL FIRE SPRINKLERS WOUD | | | NEED TO BE EXTENDED TO UNDER THE PROPOSED THROUGH | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE EXISTING FIRE SPRINKLER | | | LOCATION DETAILS AND PROVIDE AN APPLICABLE NOTE . | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-03 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-09 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2019-05-09 16:18:30 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-04-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-16 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-11 |
Time |
11:19 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-05-24 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2019-05-24 |
Time |
15:26 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2019-05-24 |
Time |
15:25 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-16 |
Time |
13:48 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2019-04-09 |
Time |
11:36 |
Sent To |
FIRE |
|
| Notes |
| 2019-04-09 11:54:17 | FAILED | | | | | | 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED | | | ON THE PLANS. | | | | | | 2) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS | | | SHALL BE A SUNBRELLA 100% SOLUTION DYED ACRYLIC OR | | | SUNBRELLA FIRESIST 100% SOLUTION DYED MODACRYLIC | | | MATERIAL (OR EQUIVALENT APPROVED BY CITYPLACE RETAIL IN | | | WRITING). IF CITYPLACE RETAIL APPROVES AN EQUIVALENT | | | MATERIAL, IT MUST BE PROVIDED IN WRITING ON THEIR | | | LETTER HEAD. | | | | | | 3) WHAT IS HAPPENING TO THE FANS ABOVE THE BAR? THE AIR | | | CIRCULATION AND COOLING PROVIDED BY THE FANS IS VERY | | | IMPORTANT DURING THE SUMMER MONTHS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] | | | |
|
|