| 2019-03-28 17:18:14 | RESIDENTIAL (R3) REVISION BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| | |
| | |
| | 1- BUILDING REVIEW WAS APPROVED ON 01/09/18 WITH |
| | PROVISO TO ALLOW CONTRACTOR TO START CONSTRUCTION AND |
| | PROVIDE THE REQUIRED INFORMATION PRIOR TO INSPECTIONS. |
| | PROVISO ITEMS ARE NOT ADDRESSED. SEE COPY OF PROVISO |
| | BELOW. SHEET A-4 SUBMITTED DOESN'T PROVIDE THE REQUIRED |
| | FASTENING INFORMATION . ALSO, THE INFORMATION FOR THE |
| | FLAT ROOF WAS NOT SUBMITTED. NEED TO PROVIDE ALL THE |
| | REQUIRED INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | |
| | (NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO |
| | AVOID CONFLICTS/DELAYS) |
| | |
| | 1- PROVIDE COMPLETE DETAILS/SPECS FOR INSTALLATION OF: |
| | A) ALL METAL LOUVERS. B) ALL BAHAMA SHUTTERS. C) |
| | COLONIAL SHUTTERS. D) ALUMINUM TRELLIS. |
| | 2- PROVIDE PRODUCT APPROVAL FOR: A)FLAT ROOF AND |
| | IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. B)BALCONIES |
| | UNDERLAYMENT DESIGNED TO RECEIVE TILE/STONE. AND, |
| | IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. |
| | 3- DESIGNER OF RECORD TO APPROVE IN WRITING ABOVE |
| | PRODUCT APPROVALS. |