Plan Review Details - Permit 19030441
Plan Review Stops For Permit 19030441
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-14 Cont ID  
Sent By pvalenti Date 2019-05-14 Time 15:31 Rev Time 0.00
Received By pvalenti Date 2019-05-14 Time 15:31 Sent To  
Notes
2019-05-14 15:42:08***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD PLAN REVIEW DENIED:
 PLEASE READ THE NOTES LISTED BELOW AND ADDRESS AS
 REQUIRED. IT IS HELPFUL TO RESPOND IN AN ITEM BY ITEM
 FORMAT.
  
 FBC B 107. THE SUBMITTED PLANS ARE MISSING NECESSARY
 INFORMATION, SUCH AS:
 1.SITE BUILT REQUIREMENTS:
 A. PROVIDE FOUNDATION PLAN ? FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B. PROVIDE BUILDING PLANS:
 1. FLOOR: LIVE LOADS, CONNECTION DETAILS, FOUNDATION
 DETAILS, & COMPACTION REQUIREMENTS.
 2. WALLS: WIND LOADS, BRACING, AND CONNECTION DETAILS.
 PLEASE CLARIFY: THE PROPOSED BATHROOM APPEARS TO BE
 COVERING UP AN EXISTING WINDOW AND THE EXISTING REAR
 WALL APPEARD TO SHOW A NEW SLIDING GLASS DOOR.
 3. ROOF FRAMING: DEAD LOADS, WIND LOADS, UPLIFT
 CAPACITIES; RAFTER SPACING IS QUESTIONABLE CONSIDERING
 SPAN AND TYPICAL GRADES, ROOF FRAMING TO WALL
 CONNECTIONS,
 C. WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D. PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS.
 E. PROVIDE SITE PLAN WITH SETBACKS FROM PROPERTY LINES.
 2. ROOFING:
 A. ROOFING SUB?PERMIT IS REQUIRED:
 B. PROVIDE ALL RELATED PRODUCT APPROVALS AND IDENTIFY
 SYSTEMS TO BE USED.
 C. PROVIDE DESIGN WIND LOADS FOR ZONE 1, 2, & 3.
 D. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ZONES 2 &
 3 PER RAS 117 OR FM LPDS 1?52.
 3. SEPERATE PERMITS REQUIRED:
 A. ELECTRIC
 B. PLUMBING
 4. VALUATION:
 THE VALUATION OF THIS PERMIT APPLICATION APPEARS TO BE
 VERY LOW IN COMPARISON TO SOURCES SUCH AS THE ICC
 BUILDING VALUATION DATA. PLEASE RE?EVALUATE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-04 Cont ID  
Sent By pvalenti Date 2019-04-04 Time 16:23 Rev Time 0.00
Received By pvalenti Date 2019-04-04 Time 16:23 Sent To P
Notes
2019-04-04 17:33:35***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND PLAN REVIEW DENIED:
 R301.1APPLICATION.
 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF, SHALL
 BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING
 DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW
 LOADS, WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY
 THIS CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER OF ALL
 LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION. BUILDINGS
 AND STRUCTURES CONSTRUCTED AS PRESCRIBED BY THIS CODE
 ARE DEEMED TO COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION.
  
 FBC B 107. THE SUBMITTED PLANS ARE MISSING NECESSARY
 INFORMATION, SUCH AS:
  
 1.SITE BUILT REQUIREMENTS:
 A. PROVIDE FOUNDATION PLAN ? FOOTINGS/SLAB ON
 GRADE/REINFORCING
 B. PROVIDE BUILDING PLANS:
 1. FLOOR: LIVE LOADS, CONNECTION DETAILS, FOUNDATION
 DETAILS, & COMPACTION REQUIREMENTS.
 2. WALLS: WIND LOADS, BRACING, AND CONNECTION DETAILS.
 PLEASE CLARIFY: THE PROPOSED BATHROOM APPEARS TO BE
 COVERING UP AN EXISTING WINDOW AND THE EXISTING REAR
 WALL APPEARD TO SHOW A NEW SLIDING GLASS DOOR.
 3. ROOF FRAMING: DEAD LOADS, WIND LOADS, UPLIFT
 CAPACITIES; RAFTER SPACING IS QUESTIONABLE CONSIDERING
 SPAN AND TYPICAL GRADES, ROOF FRAMING TO WALL
 CONNECTIONS,
 C. WINDOW AND/OR DOOR SCHEDULE WITH ROUGH OPENINGS AND
 DESIGN WIND LOADS.
 D. PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS AND/OR
 DOORS.
 E. PROVIDE SITE PLAN WITH SETBACKS FROM PROPERTY LINES.
  
 2. ROOFING:
 A. ROOFING SUB-PERMIT IS REQUIRED:
 B. PROVIDE ALL RELATED PRODUCT APPROVALS AND IDENTIFY
 SYSTEMS TO BE USED.
 C. PROVIDE DESIGN WIND LOADS FOR ZONE 1, 2, & 3.
 D. PROVIDE SIGNED AND SEALED CALCULATIONS FOR ZONES 2 &
 3 PER RAS 117 OR FM LPDS 1-52.
  
 3. SEPERATE PERMITS REQUIRED:
 A. ELECTRIC
 B. PLUMBING
  
 4. VALUATION:
 THE VALUATION OF THIS PERMIT APPLICATION APPEARS TO BE
 VERY LOW IN COMPARISON TO SOURCES SUCH AS THE ICC
 BUILDING VALUATION DATA. PLEASE RE-EVALUATE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By pvalenti Date 2019-03-13 Time 09:20 Rev Time 0.00
Received By pvalenti Date 2019-03-13 Time 09:20 Sent To  
Notes
2019-03-13 09:22:40****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC B 107. PLEASE PROVIDE MORE DETAILED INFORMATION ON
 THE WORK THAT WILL BE COVERED UNDER THIS PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By jleahy Date 2019-05-14 Time 08:58 Rev Time 0.00
Received By jleahy Date 2019-05-14 Time 08:58 Sent To B
Notes
2019-05-14 09:01:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW WHERE LIGHTS, SWITCHES, AND OUTLETS WILL
 GO IN THE ADDITION ON A FLOOR PLAN.
  
 ANY OTHER WORK TO BE ALSO SHOWN ON FLOOR PLAN

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By jleahy Date 2019-04-05 Time 17:14 Rev Time 0.00
Received By jleahy Date 2019-04-05 Time 17:14 Sent To  
Notes
2019-04-05 17:15:25NO ELECTRIC SHOWN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-14 Cont ID  
Sent By thunt Date 2019-05-14 Time 15:56 Rev Time 0.00
Received By thunt Date 2019-05-10 Time 12:57 Sent To  
Notes
2019-05-13 12:58:08RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-05 Cont ID  
Sent By jleahy Date 2019-04-05 Time 17:15 Rev Time 0.00
Received By jleahy Date 2019-04-04 Time 13:44 Sent To  
Notes
2019-04-04 13:44:49RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-13 Cont ID  
Sent By pvalenti Date 2019-03-13 Time 09:22 Rev Time 0.00
Received By pvalenti Date 2019-03-11 Time 11:36 Sent To  
Notes
2019-03-12 11:36:58BLDG - $5000

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By thunt Date 2019-05-14 Time 15:55 Rev Time 0.00
Received By thunt Date 2019-05-14 Time 15:55 Sent To  
Notes
2019-05-14 15:55:43PLUMBING 2ND REVIEW**DENIED**PLUMBING SUB PERMIT
 REQUIRED**FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION
 OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 ****NOT ADDRESSED AT ALL****A PLUMBING REVIEW COULD NOT
 BE PERFORMED DUE TO LACE OF INFORMATION. PROVIDE A
 COMPLETE PLAN SHOWING WHERE PLUMBING FIXTURE WILL BE
 LOCATED, DIMENSION OF ROOMS, SANITARY RISER ISOMETRIC
 DRAWING, AND LIST THE COMPLETE SCOPE OF WORK FOR THIS
 PROJECT. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 11:54 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 11:54 Sent To E
Notes
2019-04-05 11:54:43PLUMBING 1ST REVIEW**DENIED**PLUMBING SUB PERMIT
 REQUIRED**
  
 A PLUMBING REVIEW COULD NOT BE PERFORMED DUE TO LACE OF
 INFORMATION. PROVIDE A COMPLETE PLAN SHOWING WHERE
 PLUMBING FIXTURE WILL BE LOCATED, DIMENSION OF ROOMS,
 SANITARY RISER ISOMETRIC DRAWING, AND LIST THE COMPLETE
 SCOPE OF WORK FOR THIS PROJECT. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  