Plan Review Details - Permit 19030437
Plan Review Stops For Permit 19030437
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2019-03-28 Cont ID  
Sent By rrossano Date 2019-03-28 Time   Rev Time  
Received By rrossano Date 2019-03-28 Time   Sent To I
Notes
2019-03-28 11:59:39PASSED WITH PROVISO:
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. MORE INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-14 Cont ID  
Sent By scaldero Date 2019-03-14 Time 10:25 Rev Time 0.00
Received By scaldero Date 2019-03-14 Time 09:24 Sent To  
Notes
2019-03-14 10:25:53PERMIT # 19030437
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) CUT SHEETS / MANUFACTURER'S SPECS SHALL BE PROVIDED
 TO THE FIRE INSPECTOR AT THE TIME OF INSPECTION AND
 SHALL BE MADE READILLY AVAILABLE ON-SITE AT ALL TIMES.
 FAILURE TO PROVIDE THESE DOCUMENTS WILL RESULT IN A
 FAILED INSPECTION.
  
 2) JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 3) CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 4) ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 5) FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1,
 THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR?S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 6) HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT
 200 PSI OR 50 PSI IN EXCESS OF THE SYSTEM WORKING
 PRESSURE, WHICHEVER IS GREATER, AND SHALL MAINTAIN THAT
 PRESSURE +/-5 PSI FOR 2 HOURS.
  
 7) THIS IS A CONDITIONAL APPROVAL. COMPLIANCE WITH THE
 ABOVE CONDITIONS WILL BE VERIFIED AT THE TIME OF
 INSPECTION. FAILURE TO MEET THE CONDITIONS WILL RESULT
 IN A FAILED INSPECTION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-01 Cont ID  
Sent By shill Date 2019-03-28 Time 07:34 Rev Time 0.00
Received By shill Date 2019-03-13 Time 12:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2019-03-18 Time   Rev Time 0.00
Received By ccole Date 2019-03-18 Time 12:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 16:12 Rev Time 0.00
Received By shill Date 2019-03-22 Time 16:12 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved