Plan Review Details - Permit 19030354
Plan Review Stops For Permit 19030354
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-18 Cont ID  
Sent By shill Date 2019-11-18 Time 14:28 Rev Time 0.00
Received By shill Date 2019-11-18 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 13:57 Rev Time 0.00
Received By shill Date 2019-10-11 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:11 Rev Time 0.00
Received By shill Date 2019-05-13 Time 08:10 Sent To  
Notes
2019-05-13 08:12:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, THE PRODUCT APPROVALS IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 2. FS471, THE ROOF PLAN IS TO BE CONSISTENT WITH DESIGN
 CRITERIA SPECIFIED BY SEOR. SEOR TO REVIEW PLAN PRIOR
 TO SUBMITTAL.
  
 3. FBC B 1609, THE DESIGN PRESSURES SPECIFIED BY THE
 ROOF ENGINEER FOR ENHANCED FASTENING FOR ZONES 1 AND 2
 EXCEED THE DESIGN PRESSURES SPECIFIED BY SEOR SO ARE
 ACCEPTABLE (-86.18, -135.27).
  
 HOWEVER, ZONE 3 FOR THIS SUBMITTAL ( -135.27) IS LESS
 THAN -180.84 PSF SPECIFIED ON SHEETS S0-01 AND S0-05.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 13:57 Rev Time 0.00
Received By shill Date 2019-10-07 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:28 Rev Time 0.00
Received By shill Date 2019-04-18 Time 09:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-11-18 Cont ID  
Sent By shill Date 2019-11-18 Time 14:28 Rev Time 0.00
Received By shill Date 2019-11-18 Time 14:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-11-13 Cont ID  
Sent By shill Date 2019-11-13 Time 06:53 Rev Time 0.00
Received By shill Date 2019-11-13 Time 06:53 Sent To  
Notes
2019-11-13 06:53:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE THE DOCUMENT NAMED ROOF & DECK INSULATION
 PRODUCT DATA. THE DESIGN PRESSURES USE ZONE 2 PRESSURES
 FOR ZONE 3, 3' PARAPET. THE ENGINEERING SUBMITTED HAS A
 1' PARAPET, WITH HIGHER ZONE 3 PRESSURES. IF USING
 THESE PRESSURES, PROVIDE A ROOF PLAN SHOWING PARAPET
 HEIGHTS. TYPICALLY STAIR AND ELEVATOR SHAFTS DO NOT
 HAVE A 3' PARAPET EVEN IF THE REST OF THE ROOF HAS A 3'
 PARAPET; A PLAN WILL DOCUMENT THE CONDITIONS FOR THIS
 STRUCTURE.
  
 2. SEE THE DOCUMENT NAMED REVISED TOP ROOFING PRODUCT
 DATA. THE DESIGN PRESSURES ARE CONSISTENT WITH THE
 PAPER ENGINEERING SUBMITTED. THIS DOCUMENT AND THE
 DOCUMENT REFERENCED IN COMMENT #1 WERE UPLOADED THE
 SAME DAY. IT IS NOT CLEAR WHY TWO DIFFERENT ROOF
 SUBMITTALS WERE SUBMITTED.
  
 3. SEE ROOF & DECK INSULATION PRODUCT DATA UPLOADED
 4/18/19. THIS DOCUMENT THE SAME ENGINEERING AS COMMENT
 #1.
  
 4. THE DOCUMENT THERMOPLASTIC-POLYOLEFIN ROOFING
 PRODUCT DATA HAS TWO DIFFERENT PRODUCT APPROVALS; A
 FLORIDA STATE PRODUCT APPROVAL WHICH INDICATES THE
 ASSEMBLY PROPOSED AND ALSO INCLUDES A MIAMIDADE WHICH
 APPEARS TO BE THE SAME PRODUCT. AS THERE MAY BE
 CONFLICTS BETWEEN THE TWO, ONLY ONE PRODUCT APPROVAL
 CAN BE PROPOSED.
  
 5. DUE TO THE DUPLICATION OF DOCUMENTS AND INCONSITENCY
 BETWEEN THE DOCUMENTS, PLEASE REMOVE ALL DOCUMENTS
 WHICH ARE NOT REQUIRED TO BE IN THE SUBMITTAL. IT'S
 SUGGESTED THAT THE ENGINEERING ALONG WITH THE PRODUCT
 APPROVAL BE ONE DOCUMENT, ROOF DRAWINGS SPECIFIC TO
 THIS PRODUCT BE A SECOND DOCUMENT, THEN GENERIC DETAILS
 AND SPEC SHEETS CAN EITHER BE OMITTED OR SUBMITTED AS
 ONE DOCUMENT.
  
  
  
  
2019-11-04 14:49:35HARD COPIES ROUTED TO SHILL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 13:51 Rev Time 0.00
Received By shill Date 2019-10-11 Time 13:51 Sent To  
Notes
2019-10-11 13:52:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FS471, ENGINEERING IS NOT DIGITALLY SIGNED. IF
 ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, ONE PAPER
 ORIGINAL IS TO BE SUBMITTED TO THE BUILDING DIVISION,
 WITH A SUBMITTAL FORM, DESCRIPTION "SIGNATURE
 DOCUMENTS" AFTER ALL REVIEWS HAVE PASSED.
  
 ALTERNATIVELY, DIGITALLY SIGNED ENGINEERING CAN BE SENT
 TO ME VIA EMAIL ([email protected], CC [email protected],
 SUBMITTAL NUMBER AND "SIGNATURE DOCUMENTS" IN THE
 SUBJECT LINE).
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By shill Date 2019-05-13 Time 08:27 Rev Time 0.00
Received By shill Date 2019-05-13 Time 08:27 Sent To  
Notes
2019-05-13 08:28:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FS471, ENGINEERING IS NOT DIGITALLY SIGNED. IF
 ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, ONE PAPER
 ORIGINAL IS TO BE SUBMITTED TO THE BUILDING DIVISION,
 WITH A SUBMITTAL FORM, DESCRIPTION "SIGNATURE
 DOCUMENTS" AFTER ALL REVIEWS HAVE PASSED.
  
  