Plan Review Details - Permit 19030267
Plan Review Stops For Permit 19030267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By jduprey Date 2019-05-21 Time 12:20 Rev Time 0.00
Received By jduprey Date 2019-05-21 Time 09:38 Sent To  
Notes
2019-05-21 12:21:17PROVISO
  
 SEPARATE ROOF PERMIT REQUIRED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-29 Cont ID  
Sent By cthroop Date 2019-03-29 Time 12:57 Rev Time 0.00
Received By cthroop Date 2019-03-28 Time 14:45 Sent To  
Notes
2019-03-29 13:08:19BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED SCOPE OF WORK INCLUDES THE REMOVAL OF THE
 BOTTOM CORD OF EXISTING TRUSSES IN THE LOFT AREA AND
 BOTH BEDROOMS.
 2. AN EVALUATION OF THIS PROPOSED WORK NEEDS TO BE
 PERFORMED BY A FLORIDA LICENSED PROFESSIONAL ENGINEER.
 THIS REPORT TO INCLUDE A SHORING PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE THE MANUFACTURERS INSTALLATION INSTRUCTIONS
 FOR THE PROPOSED SPRAYED INSULATION. IDENTIFY WHICH
 PRODUCT WILL BE USED TO OBTAIN THE REQUIRED R-20.
  
 4. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 5. PROVIDE DESIGN PRESSURES OF ALL EXTERIOR WINDOW AND
 DOOR OPENINGS.
  
 6. ARCHITECT'S SIGNATURE IS A COPY.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 7. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLIONS SUBMITTALS.
  
 8. PLAN PAGE A-3 STATES EXTERIOR FRAMED WALLS SHALL
 HAVE FIBERGLASS 5.5 BATT INSULATION. THE EXTERIOR WALL
 SECTION ON PLAN PAGE A-9 STATES THE INSULATION SHALL BE
 SPRAY APPLIED. PLEASE CLARIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By jpearson Date 2019-05-30 Time 08:10 Rev Time 0.00
Received By jpearson Date 2019-05-30 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By jpearson Date 2019-03-25 Time 12:49 Rev Time 0.00
Received By jpearson Date 2019-03-25 Time 10:47 Sent To  
Notes
2019-03-25 12:49:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE
 INCLUDED IN THE CONDUIT FROM THE METER TO THE MAIN
 PANEL. PROVIDE CORRECTION. NEC 250.6; FBC RE E3610.4
 3. RISER DIAGRAM SHOWS THREE 4/0 CONDUCTORS IN A 1 1/2
 INCH CONDUIT. THIS CONDUIT IS UNDERSIZED FOR THE WIRE
 SIZE. PROVIDE CORRECTION. NEC CHAPTER 9 TABLES,
 INFORMATIVE ANNEX C
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 5. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 7. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY (DECK) ACCESSIBLE FROM THE
 DWELLING UNIT. NEC 210.52(E)(3); FBC RE E3901.7
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 9. RISER DIAGRAM SHOWS THE ELECTRCAL PANELS AS MAIN
 BREAKER PANELS, BUT THE PANEL SHCEDULES SHOW THEM AS
 MAIN LUG ONLY PANELS. CORRECT DISCREPANCY. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-05-29 Cont ID  
Sent By fmittner Date 2019-05-29 Time 11:30 Rev Time 0.00
Received By fmittner Date 2019-05-29 Time 11:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:52 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 13:09 Rev Time 0.00
Received By cthroop Date 2019-05-06 Time 13:30 Sent To  
Notes
2019-06-03 06:50:016/3 TO CT DESK
  
  
2019-05-07 13:30:15R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-29 Cont ID  
Sent By cthroop Date 2019-03-29 Time 12:53 Rev Time 0.00
Received By cthroop Date 2019-03-07 Time 13:10 Sent To  
Notes
2019-03-08 13:10:10R25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 13:09 Rev Time 0.00
Received By cthroop Date 2019-06-04 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-03-27 Cont ID  
Sent By hmoser Date 2019-03-27 Time 09:23 Rev Time 0.00
Received By hmoser Date 2019-03-27 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By gjohnson Date 2019-05-13 Time 10:03 Rev Time 0.00
Received By gjohnson Date 2019-05-13 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By thunt Date 2019-03-25 Time 15:34 Rev Time 0.00
Received By thunt Date 2019-03-25 Time 15:03 Sent To  
Notes
2019-03-25 15:34:45PLUMBING 1ST REVIEW**DENIED**
  
 1) PLANS SHALL BE WET SIGNED AND DATED BY THE DESIGN
 PROFESSIONAL. THESE ARE COPIES (PIXELATED). 61G15-23
  
 2) PROVIDE A PROPER WET VENT FOR THE POWER BATHROOM
 TOILET. TOILET CANNOT BE VENTED BY 2ND FLOOR BATHROOMS.
 FBC-PLB 912.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CALVIN, GIORDANO & ASSOCIATES INC
 561-248-2703
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By jduprey Date 2019-05-21 Time 12:20 Rev Time 0.00
Received By jduprey Date 2019-05-21 Time 12:20 Sent To  
Notes
2019-05-21 12:21:41PROVISO
  
 SEPARATE ROOF PERMIT REQUIRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-03-29 Cont ID  
Sent By cthroop Date 2019-03-29 Time 12:54 Rev Time 0.00
Received By cthroop Date 2019-03-29 Time 10:17 Sent To  
Notes
2019-03-29 12:57:43BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE PROPOSED SCOPE OF WORK TO REMOVE THE
 BOTTOM CORD OF THE EXISTING TRUSSES, AN EVALUATION OF
 THE TRUSS SYSTEM NEEDS TO BE PERFORMED BY A FLORIDA
 LICENSED PROFESSIONAL ENGINEER.
  
 SEE ADDITIONAL COMMENTS UNDER BUILDING REVIEW.
  
 2. ROOF COVERING PRODUCTS ARE APPROVED.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-29 Cont ID  
Sent By fmittner Date 2019-05-29 Time 11:30 Rev Time 0.00
Received By fmittner Date 2019-05-29 Time 11:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:52 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:52 Sent To  
Notes
2019-03-22 15:54:08LANDSCAPE PERMIT NEEDS TO BE SUBMITTED SEPERATELY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved