Plan Review Details - Permit 19030266
Plan Review Stops For Permit 19030266
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By jduprey Date 2019-05-24 Time 10:27 Rev Time 0.00
Received By jduprey Date 2019-05-24 Time 10:27 Sent To  
Notes
2019-05-24 10:29:20PER MICHAEL ORIO THIS PARCEL WITH THE PCN:
 74434327280000200 WILL HAVE THE ADDRESS OF 295 AUSTIN
 LN.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By jgomez Date 2019-04-04 Time 09:03 Rev Time 0.00
Received By jgomez Date 2019-04-04 Time 08:59 Sent To  
Notes
2019-04-04 09:03:47ACCORDING TO ZONING REVIEW COMMENTS THE LOT NEEDS TO BE
 SPLIT AND NEW PCN AND ADDRESS IS REQUIRED. PLEASE
 CONTACT MIKE ORIO TO COORDINATE NEW ADDRESS. SEE MIKE'S
 INFORMATION BELOW:
  
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040
 E-MAIL: [email protected]
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
 ZONING COMMENTS:
 LOT NEEDS TO BE SPLIT AND THIS NEW CONSTRUCTION APPLY
 UNDER NEW PCN AND ADDRESS. LANDSCAPE PERMIT TO BE
 SUBMITTED SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-03 Cont ID  
Sent By jduprey Date 2019-06-03 Time 08:52 Rev Time 0.00
Received By jduprey Date 2019-06-03 Time 08:47 Sent To  
Notes
2019-06-03 08:52:15***PROVISO***
  
 1. PROVIDE WOOD TRUSS SHOP DRAWINGS TO THE FIELD
 INSPECTOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By jduprey Date 2019-05-24 Time 10:17 Rev Time 0.00
Received By jduprey Date 2019-05-24 Time 10:16 Sent To  
Notes
2019-05-24 10:17:32***PROVISO***
  
 1. PROVIDE WOOD TRUSS SHOP DRAWINGS TO THE FIELD
 INSPECTOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By jgomez Date 2019-04-05 Time 16:15 Rev Time 0.00
Received By jgomez Date 2019-04-05 Time 09:06 Sent To  
Notes
2019-04-05 16:16:34NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 2- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL
  
 3- PLANS SUBMITTED HAVE A COPY OF THE ARCHITECT'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE ARCHITECT'S ORIGINAL
 SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS AS REQUIRED BY 61G1-16.003 FAC.
  
 4- IT LOOKS LIKE SECOND FLOOR BEDROOM WINDOWS DON'T
 COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE OPENINGS
 SEC. R310.2.1 FBC-RESIDENTIAL. WINDOW SCHEDULE SPECIFY
 5'-0" HIGH WINDOWS. TYPICALLY, 5-0" HIGH WINDOWS DON'T
 PROVIDE THE 24" CLEAR OPENING HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT SPECIFIED WINDOW
 SIZE PROVIDES 24" CLEAR OPENING AND MIN. TOTAL CLEAR
 OPENING OF 5.7S.F.
 NOTE: VISIT THE WEBSITE FOR WINDOWS PRODUCT APPROVAL
 SUBMITTED (CGI WINDOWS AND DOORS) FOR WINDOW SIZES THAT
 COMPLY WITH ALL THE EGRESS REQUIREMENTS AND REVISE
 WINDOW SCHEDULE AS REQUIRED.
  
 5- WINDOWS AND DOORS DESIGN PRESSURES:
 A)DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET S-2
 DON'T MATCH THE DESIGN PRESSURES SHOWN ON SHEET A-6.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) DESIGN PRESSURES SHOWN ON SHEET S-2 SPECIFY THAT
 DESIGN PRESSURES ARE BASED ON A TRIBUTARY AREA OF 20
 S.F.. THERE ARE SOME OPENINGS THAT ARE LESS THAN 20 S.
 F. THE DESIGN PRESSURES NEED TO BE CALCULATED BASED ON
 THE ACTUAL TRIBUTARY AREA (AND MEAN ROOF HEIGHT). IF
 INTERPOLATING , THEN THE DESIGN PRESSURES FOR THE LOWER
 EFFECTIVE AREA SHALL BE USED. SEE FOOTNOTES ON TABLE
 R301.2(2) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- SIZE OF WATER CLOSET DOOR IN THE MASTER BATHROOM
 DOESN'T COMPLY WITH SEC. R320 FBC-RESIDENTIAL. NEED
 DOOR THAT PROVIDES 29" CLEAR OPENING. REVISE AS
 REQUIRED.
  
 7- SPECIFY SIZE OF ATTIC ACCESS ABOVE GARAGE AND MASTER
 BEDROOM HALLWAY. AND, SPECIFY LOCATION AND SIZE OF
 ATTIC ACCESS ON THE SECOND FLOOR AS REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL.
  
 8- ROOF SPRAY FOAM INSULATION:
 A) CLARIFY IF HOUSE IS DESIGNED AS HAVING A VENTED OR
 UNVENTED ROOF VENTILATION. SEC. 107.2.1 CITY AMENDMENTS
 AND SEC. R806 FBC-RESIDENTIAL. INSULATION
 SPECIFICATIONS SON SHEET A-2 CALL FOR R20 SPRAY FOAM
 INSULATION, WHILE SPECIFICATIONS ON BUILDING SECTIONS
 ON SHEET A-7 AND A-8 CALL FOR R30 BATT INSULATION.
 REVISE AS REQUIRED TO MATCH. NOTE: IF DESIGNING
 UNVENTED ATTIC, THEN SOFFIT VENTILATION NEEDS TO BE
 REVISED N THE THE WALL SECTIONS AS WELL.
  
 B) IF HOUSE IS DESIGNED WITH UNVENTED ROOF, THEN
 PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE
 SPECIFIED SPRAY FOAM TO VERIFY COMPLIANCE WITH SEC.
 R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 9- SPECIFY CARBON MONOXIDE ALARM WITHIN 10 FEET OF ALL
 SLEEPING ROOMS ON THE SECOND FLOOR AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 10- STAIR SECTION ON SHEET A-7:
 A)PROVIDE DETAIL/SPECIFICATIONS FOR STAIRWAY
 FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 B) CLARIFY TREAD SIZE. STAIR CALCULATIONS CALL FOR 10"
 TREAD WHILE STAIR SECTION CALLS FOR 11" TREAD. REVISE
 AS REQUIRED TO MATCH. SEC. R311.7.5.2 FBC-RESIDENTIAL.
  
 11- PROVIDE SPECIFICATIONS FOR CEILING DWELLING-GARAGE
 SEPARATION SHOWING COMPLIANCE WITH TABLE R302.6
 FBC-RESIDENTIAL.
  
 12- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE TRELLIS OUTSIDE THE GREAT ROOM
 AREA. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 13- TYPICAL ROOF NOTE SHOWN ON ALL WALL SECTIONS ON
 SHEET A-7 AND A-8: ARCHITECT IS SPECIFYING TO INSTALL
 ROOF TILES WITH 2-10D NAILS. ROOF TILE NOA 18-0829.05
 SUBMITTED HAVE DIFFERENT MOMENT OF RESISTANCE VALUES.
 ARCHITECT TO SPECIFY THE CALCULATED ROOF TILE MOMENT OF
 RESISTANCE AND CLEARLY IDENTIFY WHICH 10D NAILS FROM
 NOA SUBMITTED ARE REQUIRED TO MEET THE CALCULATED
 MOMENT OF RESISTANCE. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SEE RAS 127 FOR PROCEDURE TO DETERMINE THE MOMENT
 OF RESISTANCE.
  
 14- ALL WALL SECTIONS NEED TO SPECIFY 7/8" MIN. STUCCO
 THICKNESS NOT 5/8" THICKNESS AS REQUIRED BY TABLE
 R702.1(1). REVISE SPECIFICATIONS ON ALL WALL SECTIONS
 AS REQUIRED.
  
 15- NEED FOOTINGS PLACED NOT LESS THAN 12 INCHES BELOW
 FINISHED GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE ALL WALL SECTIONS AS REQUIRED.
 CLEARLY SPECIFY THE MIN. FOOTING DEPTH.
  
 16- SHEET S-1:
 A)LOWER ROOF FRAMING PLAN: THERE ARE SOME CONNECTORS
 THAT ARE NOT SHOWN ON THE CONNECTOR SCHEDULE ON SHEET
 S-2. CLEARLY IDENTIFY CUSTOM CONNECTORS FOR ALL
 STRUCTURAL FRAMING MEMBERS THAT ARE NOT SHOWN ON THE
 CONNECTOR SCHEDULE. FOR EXAMPLE WHERE IS CONNECTOR "X",
 "XX", ETC. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DETAILS SHOWN ON SHEET S-3 AND
 S-4.
  
 B) CLEARLY SPECIFY THE TOP AND BOTTOM CONNECTORS OF ALL
 STEEL AND WOOD COLUMNS. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DETAILS SHOWN ON SHEET S-3 AND
 S-4.
  
 C) CLARIFY WHY THE STEEL COLUMNS SHOWN ON THE
 FOUNDATION PLAN ARE CALLED S/C 2 AND ON LOWER ROOF
 FRAMING PLAN ARE CALLED S/C 1?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 17- SHEET S-2: REVISE THE ROOF TRUSSES TOP CHORD DEAD
 LOAD SPECIFIED UNDER THE ROOF FRAMING NOTES.
 A 5 PSF DEAD LOAD DOESN'T SEEM TO BE CORRECT IF
 INSTALLING CONCRETE ROOF TILES. REVISE AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 18-ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER'S NAME AND BUILDER'S NAME .
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE
 1 OF 5 AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE WITH PLANS AND PRODUCT
 APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 C) REVISE INSULATION R-VALUE SPECIFIED ON FLOOR OVER
 OTHER SPACE ON ITEM #8(B) TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D) REVISE NUMBER OF OCCUPANTS SHOWN ON SPACES
 INFORMATION ON PAGE 2 OF 5 IS INCORRECT. WHY THERE ARE
 "0" OCCUPANTS IN A FOUR BEDROOM HOUSE?. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. FOR EXAMPLE: SLIDING GLASS DOORS DON'T
 HAVE A 5'-0" OVERHANG DEPTH, THERE IS A TRELLIS NOT A
 ROOF ON THE EXTERIOR SIDE OF THESE DOORS. REVISE AS
 REQUIRED. WINDOW #1 ON PAGE 3 OF 5 FACING NORTH DON'T
 HAVE A 15FT OVERHANG DEPTH. NOTE: SEE EXTERIOR
 ELEVATIONS AND CHECK/REVISE OVERHANG DEPTH AND
 SEPARATION OF ALL WINDOWS/DOORS AS REQUIRED TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
 19- SURVEY SUBMITTED CAN NOT BE USED FOR CONSTRUCTION.
 SEE SURVEY NOTES ON SURVEY SUBMITTED. PROVIDE SURVEY
 SUITABLE FOR CONSTRUCTION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 20- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A)PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) 6" HARDI-PLANK SIDING AND 4" HARDI-TRIM AS SHOWN ON
 PLANS.
  
 21- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 22- WINDOW MULLIONS NOA 17-1018.07 SUBMITTED: REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 23- ENTRY DOORS SHOWN ON FIRST FLOOR PLAN DON'T MATCH
 DOOR SPECIFIED ON THE DOOR SCHEDULE AND DOOR SHOWN ON
 THE EXTERIOR ELEVATION. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-23 Cont ID  
Sent By jleahy Date 2019-05-23 Time 16:19 Rev Time 0.00
Received By jleahy Date 2019-05-23 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By jleahy Date 2019-03-28 Time 10:29 Rev Time 0.00
Received By jleahy Date 2019-03-28 Time 10:29 Sent To  
Notes
2019-03-28 10:42:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1)SECOND FLOOR CO MISSING AT BEDROOMS
  
 R315.1CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR
 ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
 2) SECOND FLOOR SMOKE ALARMS LOOK TO BE TO CLOSE TO THE
 FANS
  
 R314.3LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE
 ATTICS. IN DWELLINGS OR DWELLING UNITS WITH SPLIT
 LEVELS AND WITHOUT AN INTERVENING DOOR BETWEEN THE
 ADJACENT LEVELS, A SMOKE ALARM INSTALLED
 ON THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A
 BATHTUB OR SHOWER UNLESS THIS WOULD PREVENT PLACEMENT
 OF A SMOKE ALARM REQUIRED BY SECTION R314.3.
  
 3) RISER DIAGRAM AND PANEL SCHEDULE DO NOT HAVE SAME
 WIRE SIZES FOR SUB-PANEL
  
 PANEL SCHEDULE SHOWS #2 RISER SHOW 1/0
  
 PLEASE SPECIFY WIRE TYPE ON RISER (CU. OR AL)
  
 4) PANEL "A" SHOWS 150 AMPERE BUSS WITH A 200 AMPERE
 MAIN
 SPECIFY MAIN SIZE FOR PANEL "A"

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By fmittner Date 2019-05-21 Time 13:24 Rev Time 0.00
Received By fmittner Date 2019-05-21 Time 13:24 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:55 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-03 Cont ID  
Sent By jduprey Date 2019-06-03 Time 08:52 Rev Time 0.00
Received By jduprey Date 2019-05-29 Time 11:26 Sent To  
Notes
2019-05-29 12:42:26TO TKL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-28 Cont ID  
Sent By shill Date 2019-05-25 Time 06:33 Rev Time 0.00
Received By shill Date 2019-05-06 Time 13:34 Sent To  
Notes
2019-05-24 10:43:555/24 TO C.MONTELLO DESK
  
  
2019-05-07 13:34:56R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-05 Cont ID  
Sent By jgomez Date 2019-04-05 Time 16:18 Rev Time 0.00
Received By jgomez Date 2019-03-07 Time 13:11 Sent To I
Notes
2019-03-08 13:11:53R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By jgomez Date 2019-06-04 Time 12:11 Rev Time 0.00
Received By jgomez Date 2019-06-04 Time 12:06 Sent To  
Notes
2019-06-04 12:11:52$10,003.08 PAID. MU-2019-017153.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-06-03 Cont ID  
Sent By jduprey Date 2019-06-03 Time 08:51 Rev Time 0.00
Received By jduprey Date 2019-06-03 Time 08:51 Sent To  
Notes
2019-06-03 08:51:36IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By jgomez Date 2019-04-05 Time 16:18 Rev Time 0.00
Received By jgomez Date 2019-04-05 Time 16:17 Sent To  
Notes
2019-04-05 16:18:14IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 05:52 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 05:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-02 Cont ID  
Sent By hmoser Date 2019-04-02 Time 14:11 Rev Time 0.00
Received By hmoser Date 2019-04-02 Time 10:59 Sent To  
Notes
2019-04-02 14:11:27PASS PROVISO
 REFER TO SECTION M1602.3 BALANCED RETURN AIR
 (MASTER BEDROOM) 2017 FBC RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-30 Cont ID  
Sent By tklarge Date 2019-05-30 Time 14:52 Rev Time 0.00
Received By tklarge Date 2019-05-30 Time 14:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-23 Cont ID  
Sent By tklarge Date 2019-05-23 Time 09:34 Rev Time 0.00
Received By tklarge Date 2019-05-22 Time 08:49 Sent To  
Notes
2019-05-23 09:34:251) SUBMIT NEW ENERGY CALCULATIONS. THE CALCULATIONS
 STILL SHOW THE EF RATING OF THE WATER HEATER AS .86.
 WATER HEATERS UP TO 55 GALS. SHALL HAVE AN EF RATING OF
 .95. 2ND REQUEST.
 2) THE WATER CLOSET IN THE POWDER ROOM IS NOT SHOWN ON
 THE SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE TUB AND WATER CLOSET IN THE MASTER BATH ARE NOT
 VENTED. 2017 FBC-RES. SEC. P3101.2, P3101.2.1.
 4) THE SHOWER IN THE MASTER BATH IS NOT SHOWN ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS TO
 THE 2ND FLOOR. 2017 FBC-RES. SEC.P3005.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By lcrespo Date 2019-03-25 Time 08:15 Rev Time 0.00
Received By lcrespo Date 2019-03-25 Time 08:14 Sent To  
Notes
2019-03-25 08:16:0203/25/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY
 FORM R405-2017 IS SHOWING THE E.F AS .92. AS OF APRIL
 16, 2015, ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO
 BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN
 THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012.
 2. PLEASE SHOW TEMPERING DEVICE FOR ROMAN TUB AND
 LOCATION IF DOES NOT HAVE A INTEGRAL ONE, 2017 FBC
 R2713.3 BATHTUB AND WHIRLPOOL BATHTUB VALVES. HOT WATER
 SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL BE
 LIMITED TO A TEMPERATURE OF NOT GREATER THAN 120?F
 (49?C) BY A WATER TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH
 PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.4.
 3. PLEASE SHOW BUILDING CLEAN OUT ON ISOMETRIC DIAGRAM
 ON PAGE A-7, WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By jgomez Date 2019-04-05 Time 16:16 Rev Time 0.00
Received By jgomez Date 2019-04-05 Time 16:16 Sent To  
Notes
2019-04-05 16:17:36EAGLE CONCRETE FLAT TILE NOA 18-0829.05

Review Stop Z ZONING
Rev No 3 Status P Date 2019-06-03 Cont ID  
Sent By fmittner Date 2019-06-03 Time 16:27 Rev Time 0.00
Received By fmittner Date 2019-06-03 Time 16:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-21 Cont ID  
Sent By fmittner Date 2019-05-21 Time 13:24 Rev Time 0.00
Received By fmittner Date 2019-05-21 Time 13:24 Sent To  
Notes
2019-05-21 13:25:18SEE COMMENTS FROM FIRST REVIEW

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:55 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:55 Sent To  
Notes
2019-03-22 15:55:50LOT NEEDS TO BE SPL;IT AND THIS NEW CONSTRUCTION APPLIE
 DUNDER NEW PCN AND ADDRESS. LANDSCAPE PERMIT TO BE
 SUBMITTED SEPERATELY.