Plan Review Details - Permit 19030152
Plan Review Stops For Permit 19030152
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By cthroop Date 2019-03-07 Time 12:58 Rev Time 0.00
Received By cthroop Date 2019-03-07 Time 12:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 10:11 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 09:52 Sent To  
Notes
2019-03-06 10:36:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN CALCULATIONS ARE GENERIC.
 2. IDENTIFY STRUCTURE THESE DESIGN PARAMETERS APPLY TO.
 3. PROVIDE ORIGINAL SIGNATURE AND SEAL OF DESIGNER OF
 RECORD ON DESIGN CALCULATIONS.
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-06 Cont ID  
Sent By scaldero Date 2019-03-06 Time 08:38 Rev Time 0.00
Received By scaldero Date 2019-03-06 Time 08:11 Sent To  
Notes
2019-03-06 08:38:32PERMIT #19030152
 FIRE REVIEW COMMENTS
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 6) A FIRE INSPECTION WILL BE CONDUCTED AFTER THE TENT
 IS ERECTED.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 10:12 Rev Time 0.00
Received By cthroop Date 2019-03-05 Time 10:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 10:12 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 10:09 Sent To  
Notes
2019-03-06 10:22:46NO NOTES
  
  
  