Plan Review Details - Permit 19030147
Plan Review Stops For Permit 19030147
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By dbattles Date 2019-06-20 Time 16:31 Rev Time 0.00
Received By dbattles Date 2019-06-17 Time 07:50 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By dbattles Date 2019-05-14 Time 12:59 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 12:59 Sent To  
Notes
2019-05-14 13:02:11319 FBC[R] ADDRESSING IS NEEDED FOR THIS BUILDING. THE
 PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN
 ASSIGNED TO THE BUILDING.
 PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR
 BY E-MAIL [email protected]
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:20 Rev Time 0.00
Received By dbattles Date 2019-08-26 Time 10:12 Sent To  
Notes
2019-08-27 11:39:27PROVISOS:
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
 TILT UP TEMPORARY BRACING BY ENGINEER
 ROOM DIVIDER IN EVENT ROOM
 HANDRAILS AND GUARDRAILS
 FLOOR UNDERLAYMENT/SOUNDPROOFING
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By dbattles Date 2019-06-20 Time 16:31 Rev Time 0.00
Received By dbattles Date 2019-06-17 Time 07:50 Sent To  
Notes
2019-06-24 07:36:11BUILDING REVIEW COMMENTS
 W.P.B. PERMIT: 19030147
 2 ND REVIEW: JUNE 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 42) 1011.12 FBC[B]
 - ROOF HATCH OK SINCE NO MECHANICAL ACCESS.
 1011.12.2 FBC[B] PLEASE DIMENSION THE ROOF HATCH TO
 SHOW IT IS 16 SQ. FT MINIMUM.
  
 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF
 EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE
 MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP
 R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1)
 AND 1006.3.2(2).
 - WINDOWS DON?T NEED TO OPERATE FOR EGRESS, BUT PLEASE
 REVIEW FOR VENTILATION
 1203.5 NATURAL VENTILATION.
 IS ALL THE VENTILATION MECHANICAL?
  
 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION
 RATING EQUAL TO THE SHAFT ENCLOSURE.
 -NEW COMMENT-TYPICALLY YOU WOULD USE TABLE 716.5 TO
 SPECIFY FIRE RATING OF DOOR, BUT FOR THE CHUTE
 DISCHARGE ROOM 713.13.4 REQUIRES THE DOOR TO EQUAL THE
 FIRE PROTECTION RATING OF THE SHAFT (2 HOURS).
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 10:40 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 09:15 Sent To  
Notes
2019-05-17 10:42:57****CORRECTIONS****
 W.P.B. PERMIT: 19030147
 REVIEWED: MAY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 2) 1603.1 FBC[B] GENERAL. CONSTRUCTION DOCUMENTS SHALL
 SHOW THE SIZE, SECTION AND RELATIVE LOCATIONS OF
 STRUCTURAL MEMBERS WITH FLOOR LEVELS, COLUMN CENTERS
 AND OFFSETS DIMENSIONED. THE DESIGN LOADS AND OTHER
 INFORMATION PERTINENT TO THE STRUCTURAL DESIGN REQUIRED
 BY SECTIONS 1603.1.1 THROUGH 1603.1.8 SHALL BE
 INDICATED ON THE CONSTRUCTION DOCUMENTS. EXCEPTION:
 CONSTRUCTION DOCUMENTS FOR BUILDINGS CONSTRUCTED IN
 ACCORDANCE WITH THE CONVENTIONAL LIGHT-FRAME
 CONSTRUCTION PROVISIONS OF SECTION 2308 (SEE 1603.1 FOR
 LIGHT STEEL FRAME EXCEPTION AND REQUIREMENTS)
 - PLEASE ADD STRUCTURAL DESIGN CALCULATIONS TO
 SUPPORTING DOCUMENTS FOLDER IN PROJECTDOX.
  
 3) C103.1.1.1.2 FBC[ENERGY] COMMERCIAL AND
 MULTIPLE-FAMILY RESIDENTIAL.DESIGN PROFESSIONALS
 RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF
 LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS
 AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF
 THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND
 PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 - ENERGY CALCULATIONS TO BE SIGNED BY THE PREPARER.
  
 4) C103.1.1.2 FBC[ENERGY] CODE COMPLIANCE
 CERTIFICATION. THE BUILDING?S OWNER, THE OWNER?S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION.
 - ENERGY CALCULATIONS TO BE SIGNED BY APPROPRIATE PARTY
 AS OUTLINED IN C103.1.1.2.
  
 5) C103.3 ENERGY CALCULATIONS.
 - VERIFY PROJECT DATA ON ENERGY CALCULATIONS PAGE 2.
 CONDITIONED AREA AND NON CONDITIONED AREA ARE THE SAME,
 THE NUMBER OF STORIES SHOWS 1.
  
 6) C103.3 ENERGY CALCULATIONS.
 - UNDER SECTION FOR DOORS THERE ARE NO ENTRIES FOR THE
 DOORS. DOORS SHOULD BE INCLUDED WITH THE OVERHANGS
 PROVIDED.
  
 7) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS.
 - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT ROOF
 ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE R-30.
  
 9) C103.2 INFORMATION ON CONSTRUCTION DOCUMENTS.
 - DRAWINGS SHOULD SHOW DESIGN R-VALUE AT WALL THERMAL
 ENVELOPE ESTABLISHED BY ENERGY CALCULATIONS. THEY STATE
 R-13. PROVIDE CUT SHEET TO SHOW RIDIG BOARD PANEL THAT
 CAN PROVIDE R VALUE NEEDED AFTER ALL OTHER ENVELOPE
 COMPONANTS ARE INCLUDED.
  
 10) GENERAL COMMENT
 - IF POSSIBLE CAN THE DOTTED GRIDLINES BE TURNED OFF
 FOR FLOOR PLANS ON SHEETA2.1 AND A2.2. THIS IS JUST A
 REQUEST TO MAKE DRAWINGS MORE READABLE. WITH FIRE WALLS
 USING DASH DOT LINE TYPE IT WOULD HELP CLARIFY THE
 SEPARATIONS.
  
 FAIRHOUSING REVIEW BEGIN: COMMENTS 11-24
 GENERAL COMMENT
 - IT LOOKS LIKE FLORIDA ACCESSIBLITY CODE WAS APPLIED
 TO THIS PROJECT INSTEAD OF FAIRHOUSING GUIDELINES. THE
 COMMON AREAS USING FLORIDA ACCESSIBILITY WOULD MEET OR
 EXCEED FAIRHOUSING GUIDELINES, BUT THE RESIDENT ROOMS
 WILL FALL SHORT OF MEETING REQUIREMENTS 6 AND 7 BECAUSE
 THEY APPLY TO ALL ROOMS. WITH FAIRHOUSING BEING APPLIED
 THE ADA SUITES WOULD NOT NEED TO BE PROVIDED, BUT THE
 FOLLOWING FAIRHOUSING REQUIREMENTS WOULD APPLY TO ALL
 DWELLING UNITS.
  
 11) 1986 ANSI [A117.1] IF A DESIGNER OR BUILDER CHOOSES
 TO FOLLOW AN ACCESSIBILITY STANDARD OTHER THAN THE 1986
 ANSI A117.1 STANDARD, OR A MORE RECENT VERSION OF THE
 ANSI A117.1, SUCH AS THE 1992 CABO/ANSI, THAT CARE BE
 TAKEN TO ENSURE THE STANDARD USED IS AT LEAST
 EQUIVALENT TO OR STRICTER THAN THE 1986 ANSI A117.1
 STANDARD.
 - WHAT STANDARD IS BEING APPLIED FOR COMPLIANCE WITH
 FAIR HOUSING? YOU CAN USE GUIDELINES THAT FALL WITHIN
 THE SAFE HARBOR FOR COMPLIANCE?
  
 12) REQUIREMENT 1 - PROVIDE AT LEAST ONE ACCESSIBLE
 ROUTE TO BUILDING ENTERANCE. WALKS THAT ARE PART OF
 ACCESSIBLE ROUTES BECOME RAMPS WHEN THEIR SLOPE EXCEEDS
 5% (1 IN 20). HANDRAILS ARE NOT REQUIRED ON WALKS WITH
 SLOPES BETWEEN 0% AND 5%, BUT THEY ARE REQUIRED ON
 THOSE STEEPER THAN 5% AND UP TO 8.33% (1 IN 12)
 - PROVIDE CIVIL PLANS TO VERIFY SLOPES THAT WILL OCCUR
 ON THE ACCESSIBLE PATH. PROVIDE SITE PLAN TO SHOW THE
 ACCESSIBLE PATH FROM PARKING OR OTHER PUBLIC ACCESS
 POINTS SUCH AS BUS STOP OR DROP OFF ZONE.
  
 13) REQUIREMENT 1 - PARKING
 - PROVIDE SITE PLAN WITH PARKING, IF PROVIDED, REVIEW
 OF PARKING WILL BE DONE BASED ON SITE PLAN AND
 GUIDELINES BEING USED FOR FAIR HOUSING.
  
 14) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND
 COMMON USE AREAS
 - IF AMENITIES ARE PROVIDED OUTSIDE OF BUILDING FOR THE
 USERS OF THIS BUILDING, THEN PLEASE SHOW ACCESSIBLE
 PATHS TO THE AMENITIES.
  
 15) IS THERE A MAILROOM?
 - IF SO PLEASE SHOW HOW REACH RANGES ARE ACHIEVED FOR
 MAILBOXES.
  
 16) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON
 SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED
 TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT
 GRASPING OR TWISTING.
 - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS
 TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE
 UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR
 SCHEDULE.
  
 17) ONCE INSIDE THE DWELLING UNIT HARDWARE NO LONGER
 APPLIES, BUT CLEAR SPACE ON ALL DOORS REQUIRE 32 INCHES
 NOMINAL CLEAR SPACE.
 - CHECK DOORS INSIDE DWELLING UNITS LABELED E, F, P, Q,
 V, U, EE AND FF AS THEY WOULD NOT PROVIDE THE NOMINAL
 CLEARANCE REQUIRED.
  
 18) REQUIREMENT 4 - ACCESSIBLE ROUTE INTO AND THROUGH
 THE DWELLING UNIT.
 - THEY LOOK OK SINCE ALL FURNITURE IS USABLE AND IF
 DOORS PROVIDE 32 INCH NOMINAL THAN ACCESS WILL BE
 PROVIDED. ALSO, REQUIREMENT 6 WILL HELP ACHIEVE
 ACCESSIBLE ROUTE.
  
 19) REQUIREMENT 5 - LIGHT SWITCHES, OUTLETS,
 THERMOSTATS AND OTHE CONTROLS IN ACCESSIBLE LOCATIONS.
 - THIS CAN BE HANDLED WITH NOTES TO STATE MAXIMUM AND
 MINIMUM HEIGHTS THAT COMPLY WITH THE GUIDELINES BEING
 FOLLOWED. THE NOTES CAN BE IN A FAIRHOUSING OVERVIEW,
 BUT SHOULD ALSO BE ON APPROPRIATE M OR ESHEETS SO THEY
 DON'T GET OVERLOOKED BY THE SPECIFIC TRADES.
  
 20) REQUIREMENT 6 - REINFORCED WALLS FOR GRAB BARS
 - BARS ONLY NEED TO BE INSTALLED IN THE PUBLIC OR
 COMMON USE AREAS. ALL OF THE DWELLING UNITS ONLY NEED
 BLOCKING INSTALLED. SHEET A2.3 SHOWS THE BLOCKING AT
 TOILET AND WILL WORK. PLEASE ADD BLOCKING AT SHOWER
 BECAUSE I ONLY SEE CONTROL ZONE AND THAT WILL BE
 COVERED IN REQUIREMENT 7.
  
 21) REQUIREMENT 7 - USABLE KITCHENS.
 - I ONLY SEE ONE KITCHEN IN UNIT S101. PLEASE SHOW
 CLEAR FLOOR SPACE AT COOKTOP,REFRIDGERATOR AND SINK.
 THE CLEAR SPACE SHOULD BE CENTERED ON THE APPLIANCE.THE
 SINK DOESN'T APPEAR THAT IT WOULD WORK, SO THIS MAY
 NEED TO BE RE-WORKED. ALSO, CHECK
  
 22) REQUIREMENT 7 - COMMON LAUNDRY ROOMS.
 - SHOW CLEAR FLOOR SPACE AT WASHER AND DRYER IN LAUNDRY
 ROOM 118 AND LAUNDRY ROOMS ON FLOORS 2-4. THE CLEAR
 SPACE SHOULD BE CENTERED ON THE APPLIANCES.
  
 23) REQUIREMENT 7 - USABLE BATHROOMS.
 - IN DWELLING UNITS CONTAINING MORE THAN ONE BATHROOM,
 IF SPECIFICATION A IS SELECTED AS THE BASIS FOR
 DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING
 UNIT ALSO MUST COMPLY WITH THE A SPECIFICATIONS. IF
 SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE REQUIREMENTS ALL
 BATHROOMS AS DEFINED IN THE GUIDELINES MUST:
  
 24) REQUIREMENT 7 - USABLE BATHROOMS.
 - STATE IF THE BATHROOMS IN DWELLING UNITS ARE
 SPECIFICATION A OR B. COMPARTMETALIZED BATHROOMS WILL
 BE CONSIDERED ONE BATHROOM AND BOTH AREAS WILL NEED TO
 SHOW CLEAR SPACE, 32 INCH NOMINAL OPENING, SWITH/OUTLET
 HEIGHTS AND BLOCKING IN WALLS. SHOWERS NEED MINIMUM
 30X48 AND THE SPACE NEEDS TO BE PARALLEL TO THE FIXTURE
 AND FLUSH WITH THE CONTROL WALL. CLEAR SPACE AT SINKS
 NEEDS TO BE CENTERED WITH FIXTURE.
  
 FAIRHOUSING REVIEW END
  
 25) 1606.2 FBC[B] DESIGN DEAD LOAD. FOR PURPOSES OF
 DESIGN, THE ACTUAL WEIGHTS OF MATERIALS OF CONSTRUCTION
 AND FIXED SERVICE EQUIPMENT SHALL BE USED. IN THE
 ABSENCE OF DEFINITE INFORMATION, VALUES USED SHALL BE
 SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL.
 - PLEASE PROVIDE DEAD LOAD DATA. STRUCTURAL CALCULATION
 S WERE REQUESTED IN OTHER COMMENT, SO NO RESPONSE
 NEEDED IF THEY ARE BEING SUPPLIED IN THE SUPPORTING
 DOCUMENTS FOLDER.
  
 26) 1604.3.1 FBC[B] DEFLECTIONS. THE DEFLECTIONS OF
 STRUCTURAL MEMBERS SHALL NOT EXCEED THE MORE
 RESTRICTIVE OF THE LIMITATIONS OF SECTIONS 1604.3.2
 THROUGH 1604.3.5 OR THAT PERMITTED BY TABLE 1604.3.
 - ARE THERE STRUCTURAL CALCULATIONS THAT SHOW
 DEFLECTIONS. IF SO PLEASE UPLOAD THEM TO SUPPORTING
 DOCUMENTS, OR INDICATE WHERE THE PLANS HAVE DEFLECTION
 LIMITS.
  
 27)
 28)
 29)
 30)
 COMMENTS 27-30 WERE A MISTKAE ON MY PART AND DO NOT
 APPLY. YOUR AREA, CONSTRUCTION TYPE AND SPRINKLERS TYPE
 WILL WORK FOR PROPOSED AREAS.
  
 31) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - BUILDING DATA SHEET A0.1 STATES .5 SLEEPING UNITS AND
 ,5 COORIDOR. THAT IS CORRECT, BUT THE LINE USED ON LIFE
 SAFETY PLAN MATCHES 1 HOUR DASH DOT IN TABLE. IF .5 IS
 BEING USED THE LINE MAY NEED TO BE CHANGED.
  
 32) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - VERIFY WALL TYPES ON FLOOR PLANS. SHEET A2.2 SUITES
 S-06 AND S-06 CALL FOR FS.2/FS. THIS TYPE DOESN'T MATCH
 CONDITION ON SHEET A7.1. ALSO, EXTERIOR WALLS HAVE NO
 WALL TYPE ASSIGNED.
  
 33) TABLE 1020.1 AND 708.3 EXCEPTIONS
 - PLEASE REVIEW ALL WALL TYPES ARE AS INTENDED PER
 DESIGN. I ONLY SEE SOME DESCREPENCY BETWEEN WALL TYPES
 CALLED OUT ON A0.1, FLOOR PLANS AND GRAPHIC DEPICTIONS
 ON LIFE SAFETY. THEY ARE NOT NECESSARILY NON COMPLIANT.
 I WILL NOT COMMENT ANY WALL THAT EXCEEDS CODE ON THE
 NEXT REVIEW.
  
 34) 602.1 FBC[B] WHERE REQUIRED TO HAVE A
 FIRERESISTANCE RATING BY TABLE 601, BUILDING ELEMENTS
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 703.2
  
 35) 602.1 FBC[B] EXTERIOR WALLS SHALL HAVE A
 FIRE-RESISTANCE RATING NOT LESS THAN THAT SPECIFIED IN
 TABLE 602. WHERE REQUIRED TO HAVE A FIRERESISTANCE
 RATING BY TABLE 601, BUILDING ELEMENTS SHALL COMPLY
 WITH THE APPLICABLE PROVISIONS OF SECTION 703.2.
 - (SEE TABLE 601 FOR FIRE-RESISTANCE RATING
 REQUIREMENTS) REVIEW EXTERIOR WALL FOR IIIB .THE
 BUILDING DATA PROVIDED ON SHEET A0.1. SHOWS ZERO HOURS
 EXTERIOR, BUT TABLE 601 CALLS FOR 2 HOURS. IF TABLE 602
 CALLS FOR ZERO TABLE 601 STILL APPLIES.
  
 36) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
 - SHOW OCCUPANT LOAD PER FLOOR AT 200 PER OCCUPANT AND
 FIRST FLOOR BASED ON THE RESIDENT AREA AND PUBLIC ARES
 SEPARATELY. I CALCULATE 65 AT FLOOR 4, 3 AND 2. YOU DO
 NOT HAVE TO ADD OCCUPANT LOAD FROM ABOVE ON EXIT STAIRS
 (SEE 1005.3.1 STAIRWAYS)WHERE STAIRWAYS SERVE MORE THAN
 ONE STORY, ONLY THE OCCUPANT LOAD OF EACH STORY
 CONSIDERED INDIVIDUALLY SHALL BE USED IN CALCULATING
 THE REQUIRED CAPACITY OF THE STAIRWAYS SERVING THAT
 STORY. IF YOU DO THAN LOSING ONE EXIT WOULD DECREASE
 YOUR REQUIRED CAPACITY BY MORE THAN HALF(1005.5)
  
 37) 1005.1 FBC[B] GENERAL. ALL PORTIONS OF THE MEANS OF
 EGRESS SYSTEM SHALL BE SIZED IN ACCORDANCE WITH THIS
 SECTION.
 - THE FIRST FLOOR SHOULD BE 200 PER OCCUPANT AT
 DWELLING AREAS, BUT COMMON ARES MAY USE DIFFERENT
 NUMBER. FOR EXAMPLE BUSINESS AREA MAY BE 100. ALSO, THE
 COMMON AREAS (MULTI PURPOSE, EVENT, GREAT ROOM AND
 LOBBY) NEED TO BE ASSIGNED OCCUPANT LOADS BASED ON THE
 USE OF THE SPACE. CHECK DOOR SWING OF DOOR 25 BASED ON
 OCCUPANT LOAD IF GREATER THAN 50.
  
 38) 1004.3 FBC[B] POSTING OF OCCUPANT LOAD. EVERY ROOM
 OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE THE
 OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR THE OWNER?S AUTHORIZED
 AGENT.
  
 39) 1005.7.1 FBC[B] DOORS. DOORS, WHEN FULLY OPENED,
 SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7
 INCHES (178 MM). DOORS IN ANY POSITION SHALL NOT REDUCE
 THE REQUIRED WIDTH BY MORE THAN ONE-HALF.
 - WITH A MINIMUM CORRIDOR WIDTH OF 44 INCHES AND DOORS
 SWINGING INTO THE REQUIRED WIDTH, A DIMENSION BETWEEN
 DOORS WOULD HELP BECAUSE IT IS VERY CLOSE TO EXCEEDING
 SWING ALLOWED BY 1005.7.1
  
 40) 1009.1 FBC[B] ACCESSIBLE MEANS OF EGRESS REQUIRED.
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 - SEE FBC ACCESSIBILITY CODE
  
 41) 207.1 FBC[A] GENERAL. MEANS OF EGRESS SHALL COMPLY
 WITH SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING
 CODE (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007
 OF THE INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1). EXCEPTIONS:
 - SHOW HOW ACCESSIBLE EGRESS IS ACHIEVED ON LIFE SAFETY
 SHEET.
  
 42) 1011.12 FBC[B] STAIRWAY TO ROOF. IN BUILDINGS FOUR
 OR MORE STORIES ABOVE GRADE PLANE, ONE STAIRWAY SHALL
 EXTEND TO THE ROOF SURFACE UNLESS THE ROOF HAS A SLOPE
 STEEPER THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
 - REVIEW THIS CODE SECTION FOR COMPLIANCE BECAUSE ROOF
 HATCH IS PROPOSED. PROVIDE CODE SECTION THAT ALLOWS
 ROOF HATCH FOR A 4 STORY BUILDING.
  
 43) 1006.2.2.1 FBC[B] BOILER, INCINERATOR AND FURNACE
 ROOMS. TWO EXIT ACCESS DOORWAYS ARE REQUIRED IN BOILER,
 INCINERATOR AND FURNACE ROOMS WHERE THE AREA IS OVER
 500 SQUARE FEET (46 M2) AND ANY FUEL-FIRED EQUIPMENT
 EXCEEDS 400,000 BRITISH THERMAL UNITS (BTU) (422 000
 KJ) INPUT CAPACITY. WHERE TWO EXIT ACCESS DOORWAYS ARE
 REQUIRED, ONE IS PERMITTED TO BE A FIXED LADDER OR AN
 ALTERNATING TREAD DEVICE. EXIT ACCESS DOORWAYS SHALL BE
 SEPARATED BY A HORIZONTAL DISTANCE EQUAL TO ONE HALF
 THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE ROOM.
 - REVIEW THIS CODE SECTION AT MECHANICAL YARD FOR
 EXITS.
  
 44) 1607.8.1 FBC[B] HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) (0.73 KN/M) IN ACCORDANCE
 WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES
 AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407. (SEE
 EXCEPTIONS FOR 1607.8.1)
 - ADD HANDRAILS AND GUARDS TO DEFERRED SUBMITTAL LIST
 ON SHEET A0.1.
  
 45) 1023.6 FBC[B] VENTILATION. EQUIPMENT AND DUCTWORK
 FOR INTERIOR EXIT STAIRWAY AND RAMP VENTILATION AS
 PERMITTED BY SECTION 1023.5 SHALL COMPLY WITH ONE OF
 THE FOLLOWING ITEMS:
 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE INTERIOR EXIT STAIRWAY AND RAMP BY
 DUCTWORK ENCLOSED IN CONSTRUCTION AS REQUIRED FOR
 SHAFTS.
 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE INTERIOR EXIT STAIRWAY AND RAMP, THE INTAKE AIR
 SHALL BE TAKEN DIRECTLY FROM THE OUTDOORS AND THE
 EXHAUST AIR SHALL BE DISCHARGED DIRECTLY TO THE
 OUTDOORS, OR SUCH AIR SHALL BE CONVEYED THROUGH DUCTS
 ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS.
 3. WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT
 AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT,
 WITH CONSTRUCTION AS REQUIRED FOR SHAFTS. IN EACH CASE,
 OPENINGS INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION
 SHALL BE LIMITED TO THOSE NEEDED FOR MAINTENANCE AND
 OPERATION AND SHALL BE PROTECTED BY OPENING PROTECTIVES
 IN ACCORDANCE WITH SECTION 716 FOR SHAFT ENCLOSURES.
 THE INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS
 SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION
 SYSTEMS.
 -IS THERE ANY VENTILATION PROVIDED AT ENCLOSED
 STAIRWAYS?
  
 46) 1023.9 FBC[B] STAIRWAY IDENTIFICATION SIGNS. A SIGN
 SHALL BE PROVIDED AT EACH FLOOR LANDING IN AN INTERIOR
 EXIT STAIRWAY AND RAMP CONNECTING MORE THAN THREE
 STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS OF
 THE TOP AND BOTTOM OF THE INTERIOR EXIT STAIRWAY AND
 RAMP AND THE IDENTIFICATION OF THE STAIRWAY OR RAMP.
 THE SIGNAGE SHALL ALSO STATE THE STORY OF, AND THE
 DIRECTION TO, THE EXIT DISCHARGE AND THE AVAILABILITY
 OF ROOF ACCESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP
 FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE LOCATED 5
 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A POSITION
 THAT IS READILY VISIBLE WHEN THE DOORS ARE IN THE OPEN
 AND CLOSED POSITIONS. IN ADDITION TO THE STAIRWAY
 IDENTIFICATION SIGN, A FLOOR-LEVEL SIGN IN VISUAL
 CHARACTERS, RAISED CHARACTERS AND BRAILLE COMPLYING
 WITH THE FLORIDA BUILDING CODE, ACCESSIBILITY SHALL BE
 LOCATED AT EACH FLOOR-LEVEL LANDING ADJACENT TO THE
 DOOR LEADING FROM THE INTERIOR EXIT STAIRWAY AND RAMP
 INTO THE CORRIDOR TO IDENTIFY THE FLOOR LEVEL.
  
 47) 1023.9.1 FBC[B] SIGNAGE REQUIREMENTS. STAIRWAY
 IDENTIFICATION SIGNS SHALL COMPLY WITH ALL OF THE
 FOLLOWING REQUIREMENTS:
  
 48) 1030.1 FBC[B] GENERAL. IN ADDITION TO THE MEANS OF
 EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE
 MADE FOR EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP
 R-2 OCCUPANCIES IN ACCORDANCE WITH TABLES 1006.3.2(1)
 AND 1006.3.2(2).
 - HOW ARE PROVISIONS OF THIS SECTION BEING PROVIDED
 FOR. I DON?T SEE A WINDOW SCHEDULE FOR THIS PROJECT.
 ARE THE WINDOWS OPERABLE? PLEASE PROVIDE WINDOW
 SCHEDULE, OR INDICATE WHERE I CAN FIND THIS INFORMATION
 ON THE PLANS. SHEET A0.1 MENTIONS NO FIRE ESCAPE
 WINDOWS DUE TO SPRINKLER PROVIDED. IF THERE IS
 EXCEPTION TO 1030.1 PLEASE PROVIDE THE APPLICABLE CODE
 SECTION FOR 2ND REVIEW.
  
 49) 705.8.1 FBC[B] ALLOWABLE AREA OF OPENINGS. THE
 MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
 - (SEE TABLE 705.8) THIS WILL BE REVIEWED ONCE A SITE
 PLAN WITH SEPARATION DISTANCES IS PROVIDED.
  
 50) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION
 - (SEE TABLE 705.8 FOR ALLOWABLE AMOUNTS OF OPENINGS)
  
 51) 705.8 TABLE FBC[B] MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION
  
 52) 713.13.4 FBC[B] CHUTE DISCHARGE ROOM. WASTE OR
 LINEN CHUTES SHALL DISCHARGE INTO AN ENCLOSED ROOM
 SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE
 SHAFT ENCLOSURE AND CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO THE
 DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL
 BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR
 THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR
 AUTOMATICCLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. WASTE CHUTES SHALL
 NOT TERMINATE IN AN INCINERATOR ROOM. WASTE AND LINEN
 ROOMS THAT ARE NOT PROVIDED WITH CHUTES NEED ONLY
 COMPLY WITH TABLE 509.
 - PLEASE CHECK DOOR 20 TO MEET THE REQUIRED PROTECTION
 RATING EQUAL TO THE SHAFT ENCLOSURE.
  
 53) 714.4 FBC[B] HORIZONTAL ASSEMBLIES. PENETRATIONS OF
 A FIRE-RESISTANCE- RATED FLOOR, FLOOR/CEILING ASSEMBLY
 OR THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT
 REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1
 THROUGH 714.4.4. 714.4.1 THROUGH PENETRATIONS. THROUGH
 PENETRATIONS OF HORIZONTAL ASSEMBLIES SHALL COMPLY WITH
 SECTION 714.4.1.1 OR 714.4.1.2. EXCEPTIONS:
 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS,
 PIPES, TUBES OR VENTS OR CONCRETE OR MASONRY ITEMS
 THROUGH A SINGLE FIRE-RESISTANCE- RATED FLOOR ASSEMBLY
 WHERE THE ANNULAR SPACE IS PROTECTED WITH MATERIALS
 THAT PREVENT THE PASSAGE OF FLAME AND HOT GASES
 SUFFICIENT TO IGNITE COTTON WASTE WHEN SUBJECTED TO
 ASTM E119 OR UL 263 TIME-TEMPERATURE FIRE CONDITIONS
 UNDER A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01
 INCH (2.49 PA) OF WATER AT THE LOCATION OF THE
 PENETRATION FOR THE TIME PERIOD EQUIVALENT TO THE
 FIRE-RESISTANCE RATING OF THE CONSTRUCTION PENETRATED.
 PENETRATING ITEMS WITH A MAXIMUM 6-INCH (152 MM)
 NOMINAL DIAMETER SHALL NOT BE LIMITED TO THE
 PENETRATION OF A SINGLE FIRE-RESISTANCE-RATED FLOOR
 ASSEMBLY, PROVIDED THE AGGREGATE AREA OF THE OPENINGS
 THROUGH THE ASSEMBLY DOES NOT EXCEED 144 SQUARE INCHES
 (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF FLOOR
 AREA.
 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL,
 FERROUS OR COPPER CONDUITS, PIPES, TUBES OR VENTS WITH
 A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER, PROVIDED
 THE CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL
 THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO
 MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING
 ITEMS SHALL NOT BE LIMITED TO THE PENETRATION OF A
 SINGLE CONCRETE FLOOR, PROVIDED THE AREA OF THE OPENING
 THROUGH EACH FLOOR DOES NOT EXCEED 144 SQUARE INCHES
 (92 900 MM2).
 3. PENETRATIONS BY LISTED ELECTRICAL BOXES OF ANY
 MATERIAL, PROVIDED SUCH BOXES HAVE BEEN TESTED FOR USE
 IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN
 ACCORDANCE WITH THE INSTRUCTIONS INCLUDED IN THE
 LISTING.
 - SHEETS A7.1 AND 7.2 DO NOT MENTION HOW CEILING
 PENETRATIONS ARE HANDLED. 420.3 HORIZONTAL SEPARATION
 OF DWELLING UNIT FLOORS TO BE HORIZONTAL ASSEMBLIES
 WITH SECTION 711.
  
  
 54) 714.4.2 FBC[B] MEMBRANE PENETRATIONS. PENETRATIONS
 OF MEMBRANES THAT ARE PART OF A HORIZONTAL ASSEMBLY
 SHALL COMPLY WITH SECTION 714.4.1.1 OR 714.4.1.2. WHERE
 FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE WILL
 NOT BE REDUCED.
 - (SEE 714.4.2 FOR EXCEPTIONS)
  
 55) 715.1 FBC[B] GENERAL. JOINTS INSTALLED IN OR
 BETWEEN FIRE-RESISTANCE RATED WALLS, FLOOR OR
 FLOOR/CEILING ASSEMBLIES AND ROOFS OR ROOF/CEILING
 ASSEMBLIES SHALL BE PROTECTED BY AN APPROVED
 FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH THE SYSTEM IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 715.3.
 - COMMENT IS FOR HORIZONTAL FLOOR ASSEMBLIES
  
 56) 716.5 FBC TABLE[B] OPENING FIRE PROTECTION
 ASSEMBLIES, RATINGS AND MARKINGS
 - IF FIRE PARTITIONS ARE .5 HOURS AS STATED ON A0.1
 DOORS WOULD ONLY REQUIRE 1/3 HOUR RATING MINIMUM. THIS
 IS GENERAL COMMENT AND NO RESPONSE IS REQUIRED.
  
 57) 107.2.5 FBC[AMENDED] PROVIDE SURVEY OF PROPERTY
 SHOWING EASEMENTS AND DISTANCE FROM PROPERTY LINES TO
 NEW STRUCTURE. SURVEY TO INCLUDE SLAB ELEVATION AND
 SHOW POSITIVE DRAINAGE FROM FOUNDATION.
 - 107.2.5 FBC[AMENDED](FL. STATUTE 472.025)SURVEY TO BE
 SIGNED AND SEALED BY THE SURVEYOR OF RECORD.
  
 58) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 - THIS CAN BE ADDED TO SUPPORTING DOCUMENTS AS MULTI
 PAGE PDF.
  
 59) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
 - PROVIDE CIVIL PLANS THAT SHOW DRAINAGE AND ELEVATIONS
 RELEVANT TO PARKING, BUILDING ENTRY AND ACCESSIBLE
 PATH.
  
 60) 1804.6 FBC[B] COMPACTED FILL MATERIAL. WHERE
 SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL, THE COMPACTED FILL SHALL COMPLY WITH THE
 PROVISIONS OF AN APPROVED GEOTECHNICAL REPORT, AS SET
 FORTH IN SECTION 1803. EXCEPTION: COMPACTED FILL
 MATERIAL 12 INCHES (305 MM) IN DEPTH OR LESS NEED NOT
 COMPLY WITH AN APPROVED REPORT, PROVIDED THE IN-PLACE
 DRY DENSITY IS NOT LESS THAN 90 PERCENT OF THE MAXIMUM
 DRY DENSITY AT OPTIMUM MOISTURE CONTENT DETERMINED IN
 ACCORDANCE WITH ASTM D1557.
 - THIS WILL BE VERIFIED WITH CIVIL PLANS AND
 GEOTECHNICAL REPORT THAT HAVE BEEN REQUESTED IN THIS
 REVIEW.
  
 61) 1603.1.4 FBC[B] WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCERESISTING SYSTEM OF THE STRUCTURE:
  
 62) 3002.1.2 FBC[B] HARDWARE. HARDWARE ON OPENING
 PROTECTIVES SHALL BE OF AN APPROVED TYPE INSTALLED AS
 TESTED, EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL
 LOCKS AND ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC
 CONTACTS AND DOOR-OPERATING MECHANISMS SHALL BE EXEMPT
 FROM THE FIRE TEST REQUIREMENTS. 3002.2 NUMBER OF
 ELEVATOR CARS IN A HOISTWAY. WHERE FOUR OR MORE
 ELEVATOR CARS SERVE ALL OR THE SAME PORTION OF A
 BUILDING, THE ELEVATORS SHALL BE LOCATED IN NOT FEWER
 THAN TWO SEPARATE HOISTWAYS. NOT MORE THAN FOUR
 ELEVATOR CARS SHALL BE LOCATED IN ANY SINGLE HOISTWAY
 ENCLOSURE.
  
 63) 3002.3 FBC[B] EMERGENCY SIGNS. AN APPROVED
 PICTORIAL SIGN OF A STANDARDIZED DESIGN SHALL BE POSTED
 ADJACENT TO EACH ELEVATOR CALL STATION ON ALL FLOORS
 INSTRUCTING OCCUPANTS TO USE THE EXIT STAIRWAYS AND NOT
 TO USE THE ELEVATORS IN CASE OF FIRE. THE SIGN SHALL
 READ: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE.
 USE EXIT STAIRS. EXCEPTIONS: (SEE 3002.3 FOR
 EXCEPTIONS)
  
 64) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES
 HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING
 EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY
 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS
 CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE
 PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
 - SHOW HOW STRECHER WILL FIT IN ONE OF THE ELEVATORS. A
 GRAPHIC REPRESENTAION OF 24X74 INCH RECTANGLE WITH
 MAXIMUM 5 INCH RADIUS CORNERS FROM ENTRY TO FINAL
 POSITION ON PLAN VIEW WILL HELP CLARIFY THAT THIS
 REQUIREMENT IS MET.
  
 65) 2207.5 FBC[B] CERTIFICATION. AT COMPLETION OF
 MANUFACTURE, THE STEEL JOIST MANUFACTURER SHALL SUBMIT
 A CERTIFICATE OF COMPLIANCE TO THE OWNER OR THE OWNER?S
 AUTHORIZED AGENT FOR SUBMITTAL TO THE BUILDING OFFICIAL
 AS SPECIFIED IN SECTION 1704.5 STATING THAT WORK WAS
 PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION
 DOCUMENTS AND WITH SJI SPECIFICATIONS LISTED IN SECTION
 2207.1
 - ADD TO DEFFERED SUBMITTAL L;IST
  
 66) 1504.3 FBC[B] WIND RESISTANCE OF NONBALLASTED
 ROOFS. ROOF COVERINGS INSTALLED ON ROOFS IN ACCORDANCE
 WITH SECTION 1507 THAT ARE MECHANICALLY ATTACHED OR
 ADHERED TO THE ROOF DECK SHALL BE DESIGNED TO RESIST
 THE DESIGN WIND LOAD PRESSURES FOR COMPONENTS AND
 CLADDING IN ACCORDANCE WITH SECTION 1609.
 - ROOF PRODUCT APPROVAL 14083. PLEASE ADD THE 5 PAGE
 EVALUATION REPORT TO THE PRODUCT APPROVAL, AS STATED IN
 THE EVALUATION REPORT 5.7 THE INSULATION AND INSULATION
 ATTACHMENT NEEDS TO BE PART OF THE ROOFING SUBMITTAL.
 ALSO, SELECT THE SYSTEM BEING USED ON FL14803, OR ONLY
 PROVIDE THE SHEETS FOR THE SYSTEM BEING INSTALLED.
  
 THE ROOFING SUBMITTAL CAN BE DEFERRED SUBMITTAL IF THE
 FULL SUBMITTAL IS NOT READY YET.
 - IF THE SUBMITTAL ID TO BE DEFERRED, ADD IT TO THE
 LIST ON SHEET A0.1.
  
 67) FL 16554 AND FL 14218 FOR STOREFRONT.
 - PLEASE SELECT THE SYSTEMS BEING USED AS MORE THAN ONE
 OPTION IS SHOWN ON SUMMARY OF PRODUCTS
  
 68) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 - PLEASE ADD ANY ADDITIONAL DEFERRED SUBMITTALS TO THE
 LIST ON SHEET A0.1. AIPP COMPLIANCE REQUIRED;
 VERIFICATION REQUIRED PRIOR TO C.O., SHORING AND
 RE-SHORING(IF APPLICABLE), TILT UP TEMPORARY BRACING BY
 ENGINEER, ROOM DIVIDER IN EVENT ROOM, HANDRAILS AND
 GUARDRAILS, FLOOR UNDERLAYMENT/SOUNDPROOFING AND WASTE
 CHUTE ACCESS DOOR (713.13.1)
  
 69) PLEASE ADVISE ,VIA EMAIL, WHAT FLOORING AND
 UNDERLAYMENT ARE PROPOSED? IF THE UNDERLAYMENT PRODUCT
 PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST REPORTS ON
 FILE, THE FOLLOWING REPORTS WILL BE REQUIRED:
 - THIS APPLIES TO FLOORING IN DWELLINGS ON FLOORS 2-4
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
  
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
  
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 - IF FLOORING IS TO BE A DEFERRED SUBMITTAL, ADD IT TO
 THE LIST ON SHEET A0.1.
  
 70) 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND
 FLOOR COVERING MATERIALS SHALL COMPLY WITH SECTIONS
 804.2 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-23 Cont ID  
Sent By jleahy Date 2019-08-23 Time 15:01 Rev Time 0.00
Received By jleahy Date 2019-08-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-16 Cont ID  
Sent By jleahy Date 2019-07-16 Time 08:31 Rev Time 0.00
Received By jleahy Date 2019-07-10 Time 10:33 Sent To  
Notes
2019-07-16 08:34:29RESPONSE STATES CHANGES WHERE MADE TO PLANS BUT BOT
 SHOWN ON OUR SET.
  
 #1,4,5 NOT ADDRESSED ON PLANS JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By jleahy Date 2019-04-23 Time 08:50 Rev Time 0.00
Received By jleahy Date 2019-04-16 Time 17:01 Sent To  
Notes
2019-04-23 11:42:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PGS. E3.1. THOUGH E3.4 NO NOTE FRO ARC FAULT PROTECTION
 PER 210.12(C)
  
 ELECTRICAL ROOM #120 MAIN SWBD REQUIRES WORK SPACE IN
 FRONT ATS-LS DOES NOT APPEAR TO BE 3' AWAY, SAME FOR
 PANEL 10-S.
  
 PG. E5.1 NOTE #13 NEED TO FIGURE SIZE OF GUTTER.
  
 TRANSFER SWITCH OFF CT CAN REQUIRES COMPLIANCE WITH
 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY.
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE
 AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE
 INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING
 OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS
 INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS
  
 FIRE PUMP FEED OFF GENERATOR HAS TWO DISCONNECT BEFORE
 FP CONTROLLER 695.4(B)(1)
 800A AT GENERATOR AND 125A UNDER GUTTER.
  
 SUPPLY CUT SHEETS FOR FIRE PUMP CONTROLLER 110.3
  
 SEPARATE PERMITS REQUIRED FOR FIRE ALARM, GENRATOR,
 SITE LIGHTING, LOW VOLTAGE, LIGHTNING PROTECTION.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2019-08-28 Cont ID  
Sent By rrossano Date 2019-08-28 Time   Rev Time 0.00
Received By rrossano Date 2019-08-28 Time   Sent To  
Notes
2019-08-28 10:19:24ENGINEERING SUBMITTAL IS UNDER SEPARATE REVIEW (PERMIT
 E19070028).
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2019-08-07 Cont ID  
Sent By rrossano Date 2019-08-07 Time   Rev Time 0.00
Received By rrossano Date 2019-08-07 Time   Sent To  
Notes
2019-08-07 14:57:47A SEPARATE FORMAL ENGINEERING PERMIT IS REQUIRED.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 09:55 Rev Time 0.00
Received By shill Date 2019-07-09 Time 09:55 Sent To  
Notes
2019-07-09 09:55:52CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 16:37 Rev Time 0.00
Received By shill Date 2019-03-22 Time 16:37 Sent To  
Notes
2019-03-22 16:37:43CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By pleduc Date 2019-08-14 Time   Rev Time 0.00
Received By pleduc Date 2019-08-12 Time 14:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By pleduc Date 2019-06-13 Time   Rev Time 0.00
Received By pleduc Date 2019-06-13 Time 09:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By pleduc Date 2019-03-27 Time   Rev Time 0.00
Received By pleduc Date 2019-03-26 Time 12:41 Sent To  
Notes
2019-03-26 12:41:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 0.1 - THERE IS AN INDICATION UNDER THE
 BUILDING DATA SECTION OF THE FBC OCCUPANCY AS
 APARTMENT: HOWEVER THERE IS NO FLORIDA FIRE PREVENTION
 CODE REFERENCE.
  
 PER NFPA 101, CH 3 DEFINITIONS THIS IS DORMITORY
 OCCUPANCY AND SHALL COMPLY WITH THE REQUIREMENTS;
 HOWEVER, IT SHALL BE CLASSIFIED AS AN APARTMENT
  
 3.3.64* DORMITORY. A BUILDING OR A SPACE IN A BUILDING
 IN WHICH
 GROUP SLEEPING ACCOMMODATIONS ARE PROVIDED FOR MORE
 THAN 16
 PERSONS WHO ARE NOT MEMBERS OF THE SAME FAMILY IN ONE
 ROOM, OR A
 SERIES OF CLOSELY ASSOCIATED ROOMS, UNDER JOINT
 OCCUPANCY AND SINGLE
 MANAGEMENT, WITH OR WITHOUT MEALS, BUT WITHOUT
 INDIVIDUAL COOKING
 FACILITIES.
  
 28.1.1.4 ANY DORMITORY DIVIDED INTO SUITES OF ROOMS,
 WITH ONE OR
 MORE BEDROOMS OPENING INTO A LIVING ROOM OR STUDY THAT
 HAS A
 DOOR OPENING INTO A COMMON CORRIDOR SERVING A NUMBER OF
 SUITES,
 SHALL BE CLASSIFIED AS AN APARTMENT BUILDING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET A 2.1 - THERE ARE ROOM DOORS THAT OPEN INTO
 THE CORRIDOR. THESE DOORS MAY BE OPENED AT THE SAME
 TIME AND ENCROACH THE REQUIRED WIDTH OF THE MEANS OF
 EGRESS.
  
 THERE ARE NO DIMENSIONS INDICATED ON THE PLAN TO
 CONFIMR THE REQUIRED WIDTH 44" IS MAINTAINED.
  
 PLEASE REVIEW AND PROVIDE OF JUSTIFY.CLARIFY.
  
  
  
  
  
 3) SHEET A 2.2 - THERE ARE ROOM DOORS THAT OPEN INTO
 THE CORRIDOR. THESE DOORS MAY BE OPENED AT THE SAME
 TIME AND ENCROACH THE REQUIRED WIDTH OF THE MEANS OF
 EGRESS.
  
 THERE ARE NO DIMENSIONS INDICATED ON THE PLAN TO
 CONFIMR THE REQUIRED WIDTH 44" IS MAINTAINED.
  
 PLEASE REVIEW AND PROVIDE OF JUSTIFY.CLARIFY.
  
  
  
 4) SHEET A 2.3 - THERE ARE WINDOWS INDICATED WITHIN THE
 STAIRWELL WALLS.
  
 PER NFPA 101, CH 28
  
 28.2.2.3 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 PER NFPA 101, CH 7
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 *OPENINGS IN EXIT ENCLOSURES SHALL BE LIMITED TO DOOR
 ASSEMBLIES FROM NORMALLY OCCUPIED SPACES AND CORRIDORS
 AND
 DOOR ASSEMBLIES FOR EGRESS FROM THE ENCLOSURE, UNLESS
 ONE OF
 THE FOLLOWING CONDITIONS EXISTS:
 (A) VESTIBULES THAT SEPARATE NORMALLY UNOCCUPIED SPACES
 FROM AN EXIT ENCLOSURE SHALL BE PERMITTED, PROVIDED THE
 VESTIBULE IS SEPARATED FROM ADJACENT SPACES BY CORRIDOR
 WALLS AND RELATED OPENING PROTECTIVES AS REQUIRED FOR
 THE
 OCCUPANCY INVOLVED BUT NOT LESS THAN A SMOKE PARTITION
 IN ACCORDANCE WITH SECTION 8.4.
 (B) IN BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION, AS
 DEFINED
 IN NFPA 220, STANDARD ON TYPES OF BUILDING
 CONSTRUCTION, (SEE 8.2.1.2) FIRE PROTECTION?RATED DOOR
 ASSEMBLIES TO NORMALLY UNOCCUPIED BUILDING SERVICE
 EQUIPMENT SUPPORT AREAS AS ADDRESSED IN SECTION 7.13
 SHALL BE PERMITTED, PROVIDED THE SPACE IS SEPARATED
 FROM
 THE EXIT ENCLOSURE BY FIRE BARRIERS AS REQUIRED BY
 7.1.3.2.1(3).
 (C) OPENINGS IN EXIT PASSAGEWAYS IN MALL BUILDINGS AS
 PROVIDED IN CHAPTERS 36 AND 37 SHALL BE PERMITTED.
 (D) IN BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION, AS
 DEFINED
 IN NFPA 220, STANDARD ON TYPES OF BUILDING
 CONSTRUCTION, (SEE 8.2.1.2) EXISTING FIRE PROTECTION?
 RATED
 DOOR ASSEMBLIES TO INTERSTITIAL SPACES SHALL BE
 PERMITTED,
 PROVIDED THAT SUCH SPACES MEET ALL OF THE FOLLOWING
 CRITERIA:
 I. THE SPACE IS USED SOLELY FOR DISTRIBUTION OF PIPES,
 DUCTS, AND CONDUITS.
 II. THE SPACE CONTAINS NO STORAGE.
 III. THE SPACE IS SEPARATED FROM THE EXIT ENCLOSURE IN
 ACCORDANCE WITH SECTION 8.3.
 (E) EXISTING OPENINGS TO MECHANICAL EQUIPMENT SPACES
 PROTECTED BY APPROVED EXISTING FIRE PROTECTION?RATED
 DOOR ASSEMBLIES SHALL BE PERMITTED, PROVIDED THAT THE
 FOLLOWING CRITERIA ARE MET:
 I. THE SPACE IS USED SOLELY FOR NON-FUEL-FIRED
 MECHANICAL EQUIPMENT.
 II. THE SPACE CONTAINS NO STORAGE OF COMBUSTIBLE
 MATERIALS.
 III. THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 9.7.
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE
 ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS
 ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE
 PROTECTED IN ACCORDANCE WITH 8.3.5
 (11) PENETRATIONS OR COMMUNICATING OPENINGS SHALL BE
 PROHIBITED BETWEEN ADJACENT EXIT ENCLOSURES.
 (12) MEMBRANE PENETRATIONS SHALL BE PERMITTED ON THE
 EXIT
 ACCESS SIDE OF THE EXIT ENCLOSURE AND SHALL BE
 PROTECTED IN
 ACCORDANCE WITH 8.3.5.6.
  
  
 A WINDOW SCHEDULE COULD NOT BE IDENTIFIED THAT SHOWED
 THESE WINDOWS WITH A 2 HOUR RATING.
  
 PLEASE REVIEW AND CORRECT WITH DETAILS.
  
  
  
 5) SHEET E 0.1 - THERE ARE INDICATIONS OF FIRE ALARM
 EQUIPMENT.
  
 ANY INSTALLATION OF FIRE ALARM EQUIPMENT SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY A CERTIFIED
 FIRE ALARM CONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
  
 6) SHEET A 2.1 - THERE ARE ELVATORS INDICATED.
  
 PLEASE CONFIRM MEETING THE REQUIREMENTS BELOW AND
 IDENTIFY WHICH ELEVATOR WILL HOLD THE STAR OF LIFE
 SYMBOL.
  
 28.5.3 ELEVATORS, ESCALATORS, AND CONVEYORS.
 28.5.3.1 ELEVATORS, ESCALATORS, AND CONVEYORS SHALL
 COMPLY WITH
 THE PROVISIONS OF SECTION 9.4.
 9.4.3 FIRE FIGHTERS? EMERGENCY OPERATIONS.
 9.4.3.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS?
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44,
 SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 7) SHEET A 4.1 - THERE IS AN INDICATION OF A ROOF
 ACCESS OPENING THAT APPEARS TO BE IN AN UNSAFE
 POSITION.
  
 THERE APPEARS TO BE CURBING WITHIN A FOOT OF THE EDGE
 OF THE HATCH WHICH REPRESENTS A TRIP HAZARD.
  
 A GUARD/RAILING SHOULD BE PROVIDED TO ASSIST THE USER.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 8) SHEET A 6.3 - THERE ARE NO INDICATIONS OF STAIR
 SIGNAGE, INCLUDING BUT NOT LIMITED TO :
  
 NFPA 1 CH 10
  
 10.11.3.1.13* SIGNAGE THAT READS NO ROOF ACCESS SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING
 SHALL BE A MINIMUM OF 1 IN. (25 MM) HIGH AND SHALL BE
 IN
 ACCORDANCE WITH 14.14.8.2.
  
 NFPA 101, CH 7
  
 7.2.2.5.4* STAIRWAY IDENTIFICATION.
 7.2.2.5.4.1 NEW ENCLOSED STAIRS SERVING THREE OR MORE
 STORIES AND
 EXISTING ENCLOSED STAIRS, OTHER THAN THOSE ADDRESSED IN
 7.2.2.5.4.1(P), SERVING FIVE OR MORE STORIES SHALL
 COMPLY WITH
 7.2.2.5.4.1(A) THROUGH 7.2.2.5.4.1(O).
  
 (M)* SIGNAGE THAT READS NO ROOF ACCESS SHALL DESIGNATE
 STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. LETTERING
 SHALL BE A
 MINIMUM OF 1 IN. (25 MM) HIGH AND SHALL BE IN
 ACCORDANCE WITH
 7.10.8.2.
  
 HOWEVER, "4TH FL ROOF HATCH" SHOULD BE PROVIDED IN LIEU
 OF NO ROOF ACCESS, AS WELL AS A SIGN ON THE DOOR OF THE
 ROOM CONTAINING THE HATCH.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 9) SHEET A 6.3 - THERE ARE NO INDICATIONS OF
 HARNDRAIL/GUARDS FOR THE STAIRWELLS.
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 PLEASE REIVEW AND PROVIDE.
  
  
  
 10) SHEET A 4.3 - ON THE OUTSIDE WALL PARAPET, THERE IS
 NO INDICATION OF THE HEIGHT.
  
 WILL THERE BE AT ANY POINT ALONG THIS WALL EDGE WILL
 THE PARAPET BECOME LESS THAN DISCERNABLE?
  
 WHAT WILL BE THE MINIMUM HEIGHT?
  
 THIS IS IMPORTANT FOR FIREFIGHTER SAFETY.
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 11) SHEET A 2.1 - DOOR 21 IS NOT INDICATED WITH A RIFE
 RESISTIVE RATING.
  
 THIS DOOR SEPARATES THE CORRIDOR FROM A ROOM INDICATED
 AS TRASH, ADDITIONALLY, CORRIDOR WALLS ARE REQUIRED TO
 BE SEPARATED.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIRED SEPARATION.
  
  
  
 12) SHEET F 1.1 - THERE IS AN INDICATION OF A FIRE PUMP
 ENCLOSURE. THIS ENCLOSURE WILL NOT BE APPROVED WITH
 THIS PERMIT.
  
 THE FIRE PUMP ENCLOSURE SHALL BE UNDER SEPARATE PERMIT
 SUBMITTAL AND COMPLY WITH THE APPLICABLE REQUIREMENTS
 INCLUDING, BUT NOT LIMITED TO, FBS, FFPC & NFPA 20.
  
 IT APPEARS TO BE TOO CLOSE TO THE BUILDING.
  
 4.12.1.2 OUTDOOR FIRE PUMP UNITS.
 4.12.1.2.1 FIRE PUMP UNITS THAT ARE OUTDOORS SHALL BE
 LOCATED
 AT LEAST 50 FT (15.3 M) AWAY FROM ANY BUILDINGS AND
 OTHER FIRE
 EXPOSURES EXPOSING THE BUILDING.
 4.12.1.2.2 OUTDOOR INSTALLATIONS SHALL BE REQUIRED TO
 BE PROVIDED
 WITH PROTECTION AGAINST POSSIBLE INTERRUPTION, IN
 ACCORDANCE
 WITH 4.12.1.
 4.12.1.3 FIRE PUMP BUILDINGS OR ROOMS WITH DIESEL
 ENGINES.
 FIRE PUMP BUILDINGS OR ROOMS ENCLOSING DIESEL ENGINE
 PUMP
 DRIVERS AND DAY TANKS SHALL BE PROTECTED WITH AN
 AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH NFPA 13,
 STANDARD
 FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE WITH APPLICABLE
 CODES.
  
 PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
  
  
 13) SHEET F 1.1 - THE FOUNDATION OF THE FIRE PUMP
 ENCLOSURE SHALL HAVE A FLOOR DRAIN TIED INTO THE
 PLUMBING SYSTEM AS APPLICABLE PER UTILITIES
 REQUIREMENTS.
  
 PER NFPA 20
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
  
  
  
 14) SHEET F 1.1 - THE PROPOSED FIRE HYDRANT AND FDC
 LOCATIONS ARE ON OPPOSITE SIDES OF THE ROADWAY.
  
 FOR THE MOST EFFECTIVE AND EFFICIENT FIRE GROUND
 OPERATIONS THE FDC AND FIRE HYDRANT SHOULD BE ON THE
 SAME SIDE.
  
 IT IS HIGHLY RECOMMENDED TO MOVE THE HYDRANT, IF
 POSSIBLE, TO THE OTHER SIDE OF THE ROADWAY, (IT WOULD
 ALSO BE ACCPETABLE TO MOVE THE FDC TO THE HYDRANT SIDE)
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
  
 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-08-30 Cont ID  
Sent By gjohnson Date 2019-08-30 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2019-08-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-07-02 Cont ID  
Sent By gjohnson Date 2019-07-02 Time 12:43 Rev Time 0.00
Received By gjohnson Date 2019-07-02 Time 12:43 Sent To  
Notes
2019-07-02 13:11:591ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P3.1 SHOWS GAS PIPING UNDERGROUND METALLIC
 PIPING SHALL NOT BE DIRECTLY BURIED UNDERGROUND IT MUST
 BE SLEAVED PROVIDE DETAIL ON SLEAVEING PER FBC FG
 404.11 - 404.14
  
 2. PLEASE PLACE NOTE ON PLAN SEPARATE PERMIT REQUIRED
 FOR GENERATOR. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-17 Cont ID  
Sent By gjohnson Date 2019-04-17 Time 10:15 Rev Time 0.00
Received By gjohnson Date 2019-04-17 Time 10:08 Sent To  
Notes
2019-04-17 10:15:271ST REVIEW: 19030147
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 FUEL GAS COMMENTS:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 5. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
  
 6. SEPARATE PERMITS REQUIRED FOR THE GAS AND GENERATOR.
  
  
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 10. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
  
 11. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
  
 12. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-02 Cont ID  
Sent By lmarchan Date 2019-10-02 Time 10:58 Rev Time 0.00
Received By lmarchan Date 2019-09-20 Time 13:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-10 Cont ID  
Sent By gjohnson Date 2019-09-10 Time 10:14 Rev Time 0.00
Received By gjohnson Date 2019-08-07 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 05:22 Rev Time 0.00
Received By shill Date 2019-06-10 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 10:41 Rev Time 0.00
Received By dbattles Date 2019-03-15 Time 12:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-10-02 Cont ID  
Sent By lmarchan Date 2019-10-02 Time 10:58 Rev Time 0.00
Received By lmarchan Date 2019-08-29 Time 08:02 Sent To  
Notes
2019-09-25 09:08:14RECEIPT MU-2019-0925-138 - $55,152.71 PAID
2019-09-18 07:41:599/18/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM
2019-08-29 08:02:46PER EMAIL UPLOADED FROM WILLIE, NO IMPACT FEES NEEDED
 FOR THIS PERMIT. SEE ATTACHMENT. EMAILED WILLIE TO
 CONFIM ON 8/29. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By dbattles Date 2019-05-14 Time 12:43 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 09:15 Sent To  
Notes
2019-05-14 12:43:49109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By cmontell Date 2019-08-20 Time 14:08 Rev Time 0.00
Received By cmontell Date 2019-08-20 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-12 Cont ID  
Sent By ccole Date 2019-07-12 Time 12:23 Rev Time 0.00
Received By ccole Date 2019-07-11 Time 09:49 Sent To  
Notes
2019-07-12 12:38:082ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19030147
 7/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE O/A DUCTS THAT ARE PENETRATING THE FIRE-RATED
 FLOOR/CEILING ASSEMBLIES AT EACH LEVEL SHALL BE
 ENCLOSED IN FIRE-RATED SHAFTS PER SECTION 607.6, OR
 SHALL BE PROTECTED WITH LISTED CEILING RADIATION
 DAMPERS AT ECH FLOOR/CEILING PENETRATION.
  
 2) THE PLANS INDICATE DOOR UNDERCUTS FOR REQUIRED
 MAKEUP AIR FOR TRASH AND LAUNDRY ROOM EXHAUST SYSTEMS.
 PLEASE NOTE THAT THESE ROOMS ARE FIRE-RATED AND THE
 DOORS INTO THEM ARE FIRE-RATED. DOOR UNDERCUTS ON
 FIRE-RATED DOORS ARE NOT PERMITTED ON LABELED DOORS-
 SECTION 716.5.1 FBC B AND SECTION 1.3.4 NFPA 252.
 MAKEUP AIR IN THESE ROOMS MUST BE PROVIDED BY DUCTS OR
 TRANSFER GRILLS- SECTION 504.6. THWE LAUNDRY ROOM PLANS
 SHALL SHOW THE LOCATIONS AND NUMBER OF DRYERS TO BE
 INSTALLED- SECTION 107.2.1 WPB.
  
 3) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. SHEET
 M3.1: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR CHILLERS, BOILERS, STORAGE TANKS,
 GENERATOR, AND THE ROOFTOP O/A INTAKES, EXHAUST
 OUTLETS, AND ELEVATOR RELIEF HOOD- SECTION 301.15 FBC
 M. PLEASE NOTE THAT THE PLANS SHOW A FIRE PUMP
 ENCLOSURE. IS THIS A MANUFACTURED PRODUCT, OR AN
 ENCLOSURE TO BE CONSTRUCTED ON-SITE? IF THIS IS A
 MANUFACTURED PRODUCT IT MUST EITHER HAVE FL.
 MANUFACTURED BUILDING APPROVAL OR FLORIDA PRODUCT
 APPROVAL- RULE 9N-3 FAC. TO BE CONSTRUCTED ON-SITE,
 PLEASE PROVIDE COMPLETE STRUCTURAL DRAWINGS AND
 DETAILS. PLEASE SEE SECTION 4.13 NFPA 20 FOR OTHER
 COMPLIANCE REQUIREMENTS.
  
 4) COMMENT #5 BELOW LISTED FOR REFERENCE
  
 5) REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 B) MOTORIZED O/A DAMPERS
 C) DUCT SMOKE DETECTORS
 D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 E) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 F) CHILLERS
 G) CLOTHES DRYERS
 H) COOKING APPLIANCES
 I) TEST AND BALANCE REPORTS
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 B) GENERATOR
 C) BOILERS AND WATER HEATERS INCLUDING VENT FLUES
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-22 Cont ID  
Sent By ccole Date 2019-04-19 Time 10:51 Rev Time 0.00
Received By ccole Date 2019-04-19 Time 10:33 Sent To  
Notes
2019-04-22 10:52:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030147
 4/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS A-I LISTED BELOW ARE APPLICABLE TO ALL OR
 SOME OF 1-4 FLOOR LEVEL PLAN SHEETS M2.1A, M2.1B,
 M2.1C, M2.2A, M2.2B, M2.2C, M2.3A, M.2.3B, M2.3C,
 M2.4A, M.2.4B, & M2.4C:
  
 A) RETURN AIR FROM BEDROOMS SHALL BE DUCTED OR
 TRANSFERRED IN COMBINATION WITH 1" DOOR UNDERCUTS-
 SECTION 601.6 FBC M.
 B) SHOW THE LOCATIONS AND INDICATE THE TYPES OF
 AUTOMATIC DAMPERS (MOTORIZED OR GRAVITY) TO BE USED TO
 CONTROL O/A SUPPLY TO THE AHU'S- SECTION C403.2.4.3 FBC
 EC.
 C) NO VENTILATION HAS BEEN PROVIDED FOR TRASH ROOM 112
 ON 1ST FLOOR LEVEL. THIS SAME ROOM ON LEVELS 2-4 IS NOT
 IDENTIFIED ON THE PLANS, AND ALSO NO VENTILATION HAS
 BEEN PROVIDED TO THOSE ROOMS.
 D) MAKEUP AIR FOR TRASH ROOM AND JANITOR ROOM EXHAUST
 SYSTEMS NOT PROVIDED- SECTION 501.4 FBC M. PLEASE
 PROVIDE A SEQUENCE OF OPERATION FOR THE FANS- SECTION
 501.4 FBC M.
 E) THE 12X12 RETURN BY THE COOKING APPLIANCE IN SUITE
 101 KITCHEN IS PROHIBITED PER SECTION 601.5 (7) FBC M.
 THIS 12X12 RETURN IS ALSO SHOWN ON FLOOR LEVELS 2-4
 HOWEVER THE ROOMS ARE NOT IDENTIFIED.
 F) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS
 IN THE LAUNDRIES- SECTION 504.1 FBC M
 G) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR THE
 DRYERS- 504.6 FBC M.
 H) THE FIRE DAMPER SHOWN IN THE DRYER EXHAUST DUCT ON
 SHEET M2.1B IS PROHIBITED- SECTION 504.2 FBC M.
 I) FIRE DAMPERS MISSING FOR THE 16X12 SUPPLY DUCTS AND
 14X8 RETURN DUCTS PENETRATING THE CORRIDOR/MECHANICAL
 ROOM WALLS- SECTION 607.5.3 FBC M.
  
 2) SHEET M3.1: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE EXTERIOR CHILLERS, BOILERS, STORAGE
 TANKS, GENERATOR, AND THE ROOFTOP O/A INTAKES, EXHAUST
 OUTLETS, AND ELEVATOR RELIEF HOOD- SECTION 301.15 FBC
 M.
  
 3) M3.1, GENERATOR:
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, GAS PIPING, ENGINE EXHAUST PIPE, MUFFLER,
 AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION
 616.1 FBC FG
 B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE
 GENERATOR- SECTION 616.1 FBC FG. THE MANUFACTURER'S
 SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE
 GENERATOR IS IN COMPLIANCE WITH NFPA 37.
 C) PROVIDE A GAS PIPING PLAN AND ISOMETRIC DRAWING-
 SECTION 616.2
 D) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION
 LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL
 AIR INTAKES INTO THE BUILDING. PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE
 SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M.
 E) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND
 EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT
 PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13
 NFPA 30.
  
 4) ASHRAE O/A CALCULATIONS: THE CALCULATIONS SHOW AN
 O/A CFM TOTAL USING THE VENTILATION RATE PROCEDURE, AND
 A TOTAL USING A 30% INCREASE. WHICH OF THESE TWO TOTAL
 SUMS IS THE TOTAL BEING PROVIDED.
  
 5) REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 B) MOTORIZED O/A DAMPERS
 C) DUCT SMOKE DETECTORS
 D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 E) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 F) CHILLERS
 G) CLOTHES DRYERS
 H) COOKING APPLIANCES
 I) TEST AND BALANCE REPORTS
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 B) GENERATOR
 C) BOILERS AND WATER HEATERS INCLUDING VENT FLUES
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-10 Cont ID  
Sent By gjohnson Date 2019-08-30 Time 10:14 Rev Time 0.00
Received By gjohnson Date 2019-08-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By gjohnson Date 2019-07-03 Time 12:39 Rev Time 0.00
Received By gjohnson Date 2019-06-28 Time 17:35 Sent To  
Notes
2019-07-03 12:39:34 
 2ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
 PREVIOUS COMMENTS NOT COMPLIED : COPIED FROM RESPONSE
 LETTER
  
 3) PROVIDE A MATRIX FOR THE FHA REQUIREMENTS INDICATE
 THE DESIGN SPEC FOR THE BATHROOMS A OR B PER WPB AMEND
 TO FBC 107.2.1
 RESPONSE: THE FAIR HOUSING ACT CHECKLIST AS PRODUCED BY
 THE EQUAL RIGHTS CENTER IS REFERENCED ATTACHMENT
 A-3-FHA CHECKLIST.
 THE DESIGN SPEC FOR THE BATHROOMS IS A.
 THE COMPARTMENTALIZED BATHROOMS ARE RE-DESIGNED TO
 COMPLY WITH THIS STANDARD. PLEASE REFER TO REVISED AND
 CLOUDED DRAWINGS.
  
 THE FHA CHECKLIST REFERENCED ABOVE IS NOT AN APPROVED
 SAFE HARBOR AND SHALL NOT BE USED. PLEASE SHOW ON THE
 EXPANDED BATHROOM PLANS WHICH DESIGN SPEC THE BATHROOM
 IS COMPLYING WITH.
  
 HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH THE
 FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THEY ARE:
  
 HUD FAIR HOUSING ACCESSIBILITY GUIDELINES PUBLISHED ON
 MARCH 6, 1991 AND THE SUPPLEMENTAL NOTICE TO FAIR
 HOUSING ACCESSIBILITY GUIDELINES: QUESTIONS AND ANSWERS
 ABOUT THE GUIDELINES, PUBLISHED ON JUNE 28, 1994.
  
 HUD FAIR HOUSING ACT DESIGN MANUAL
  
 ANSI A117.1 (1986), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 CABO/ANSI A117.1 (1992), USED WITH THE FAIR HOUSING
 ACT, HUD'S REGULATIONS, AND THE GUIDELINES.
  
 ICC/ANSI A117.1 (1998), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 CODE REQUIREMENTS FOR HOUSING ACCESSIBILITY 2000
 (CRHA).
  
 INTERNATIONAL BUILDING CODE 2000 AS AMENDED BY THE 2001
 SUPPLEMENT TO THE INTERNATIONAL CODES.
  
 INTERNATIONAL BUILDING CODE 2003, WITH ONE CONDITION*.
  
 ICC/ANSI A117.1 (2003), USED WITH THE FAIR HOUSING ACT,
 HUD'S REGULATIONS, AND THE GUIDELINES.
  
 2006 INTERNATIONAL BUILDING CODE? (LOOSE LEAF)
  
 * EFFECTIVE FEBRUARY 28, 2005 HUD DETERMINED THAT THE
 IBC 2003 IS A SAFE HARBOR, CONDITIONED UPON ICC
 PUBLISHING AND DISTRIBUTING A STATEMENT TO
 JURISDICTIONS AND PAST AND FUTURE PURCHASERS OF THE
 2003 IBC STATING, "ICC INTERPRETS SECTION 1104.1, AND
 SPECIFICALLY, THE EXCEPTION TO SECTION 1104.1, TO BE
 READ TOGETHER WITH SECTION 1107.4, AND THAT THE CODE
 REQUIRES AN ACCESSIBLE PEDESTRIAN ROUTE FROM SITE
 ARRIVAL POINTS TO ACCESSIBLE BUILDING ENTRANCES, UNLESS
 SITE IMPRACTICALITY APPLIES. EXCEPTION 1 TO SECTION
 1107.4 IS NOT APPLICABLE TO SITE ARRIVAL POINTS FOR ANY
 TYPE B DWELLING UNITS BECAUSE SITE IMPRACTICALITY IS
 ADDRESSED UNDER SECTION 1107.7."
  
 INFORMATION ABOUT THESE SAFE HARBORS AS WELL AS HUD?S
 POLICY WITH RESPECT TO THEIR USE MAY BE FOUND IN REPORT
 OF HUD REVIEW OF THE FAIR HOUSING ACCESSIBILITY
 REQUIREMENTS IN THE 2006 INTERNATIONAL BUILDING CODE
  
  
 13) SHOW CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM AND THE
 HEIGHT AND DEPTH OF THE APPLIANCES AND SINK SHALL
 COMPLY WITH FHA AND ANSI 4.32.6, 4.25, 4.19
 RESPONSE: THE DRAWINGS ARE MODIFIED TO INDICATE THE
 CLEAR FLOOR REQUIREMENTS. PLEASE REFER TO SHEET A2.3
 FOR AN ENLARGED PLAN.
  
 PLEASE SHOW ON PLAN A 30X48 CLEAR FLOOR SPACE IS
 REQUIRED. PLACE NOTE ON PLAN THE WASHER AND DRYER SHALL
 COMPLY WITH ANSI 1986 4.32.6, 4.25, 4.19
  
  
 19) SHEET P5.2 PROVIDE PIPING DETAIL FOR BOOSTER PUMP
 WITH LOCATION OF BLADDER TANK CALLED FOR IN NOTE G. PER
 WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P2.4 FOR ADDED BLADDER
 TANK. BLADDER TANK IS TO BE LOCATED IN MECHANICAL ROOM
 M-09 ON THE FOURTH FLOOR.
  
 I COULD NOT LOCATE PIPING DETAILS FOR BOOSTER PUMP.
 SHOW BLADDER TANK AND BOOSTER PUMP ON WATER RISER AND
 FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1
  
  
 22) SHEET PROVIDE SIZING CALCULATION FOR THE LINT TRAP.
 PER WPB AMEND TO FBC 107.2.1
 RESPONSE: PLEASE REFER TO SHEET P6.1 FOR LINT
 INTERCEPTOR CALCULATION.
 COULD NOT FIND CALCULATIONS
  
 NEW COMMENT :
  
 1. A RECIRCULATION LINE FOR HOT WATER SYSTEM WILL BE
 REQUIRED ON THE 3RD + 4TH FLOOR PER FBC PL 607.2 HOT OR
 TEMPERED WATER SUPPLY TO FIXTURES. THE DEVELOPED LENGTH
 OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE OF HOT
 WATER TO THE FIXTURES THAT REQUIRE HOT OR TEMPERED
 WATER, SHALL NOT EXCEED 50 FEET (15 240 MM).
 RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER.
  
 2. PROVIDE SIZING CALCULATIONS OR SIZING CHART FOR
 EXPANSION TANK. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-17 Cont ID  
Sent By gjohnson Date 2019-04-17 Time 10:07 Rev Time 0.00
Received By gjohnson Date 2019-04-16 Time 10:23 Sent To  
Notes
2019-04-17 10:07:401ST REVIEW: 19030147
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT
 WAS USED TO COMPLY WITH FHA
  
 2. SHT. A0.1 UNDER CODE DATA FBC IN EFFECT IS THE 2017
 6TH EDITION ALSO LIST FBC ACCESSIBILITY AND THE PLAN
 WHICH DESIGN DOCUMENT WAS USED TO COMPLY WITH FHA. PER
 WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE A MATRIX FOR THE FHA REQUIREMENTS INDICATE
 THE DESIGN SPEC FOR THE BATHROOMS A OR B PER WPB AMEND
 TO FBC 107.2.1
  
 4. SHT. A2.3 DETAIL #8
 A) PROVIDE DIMENSIONS FOR THE TOILET ROOMS.
 B) SHOW CLEAR FLOOR SPACE FOR SHOWER.
 C) SHOW DIMENSIONS ON CLEAR FLOOR SPACE OR LABEL THEM
 TO MATCH THE NOTES.
 PER WPB AMEND TO FBC 107.2.1
  
 5. JUST FOR CLARIFICATION IS THERE ANY FEDERAL FUNDING
 ON THIS PROJECT IF THERE IS IT WILL BE REQUIRED TO
 COMPLY WITH UFAS. PER FHA
  
 6. SHT. A2.3 DETAIL #4
 A) SHOW CLEAR FLOOR SPACE FOR THE TOILET, LAVATORY AND
 SHOWER.
 B) PROVIDE DIMENSIONS FOR THE TOILET ROOM.
  
 7. SHT. A2.3 SHOW LOCATION OF THE GRAB BAR BACKING ON
 THE ENLARGED FLOOR PLANS FOR THE FHA UNITS.PER WPB
 AMEND TO FBC 107.2.1
  
 8. THE GRAB BARS IN THE FBC ACC COMPLIANT DWELLING
 UNITS D-1 + C-1 SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE NOT THE CENTER OF THE BAR. PER FBC ACC
 609.4
  
 9. THE HEIGHT OF THE TOILET SEATS IN THE ACCESSIBILITY
 DWELLING UNITS D-1 + C-1 AND COMMON AREA BATHROOMS
 SHALL BE 17"- 19". PER FBC ACC 604.4 AND ANSI
 117.1-1986 4.16.3
  
 10. THE TOILET PAPER DISPENSER IN D-1 AND C-1 SHALL BE
 7"-9" MEASURED FROM THE FRONT OF THE TOILET TO THE
 CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 11. PROVIDE MOUNTING DETAILS FOR BACKING IN SHOWERS IN
 BATHROOMS C-2, D-2, C-3, D-3, C-4, D-4. PER FHA
  
 12. PROVIDE ENLARGED DETAIL FOR THE KITCHENS SHOWING
 THE REQUIRED CLEAR FLOOR SPACE AT THE APPLIANCES AND
 SINK ALSO INCLUDE THE DIMENSIONS BETWEEN THE CABINETS
 AND ANY ADJACENT ELEMENTS. PER FHA
  
 13. SHOW CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM AND THE
 HEIGHT AND DEPTH OF THE APPLIANCES AND SINK SHALL
 COMPLY WITH FHA AND ANSI 4.32.6, 4.25, 4.19
  
 14. SHOW COMPLIANCE FOR THE SHOWERS IN C-1, D-1 FBC ACC
 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES MAXIMUM
 FROM ADJACENT WALLS.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. IN
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO THE
 SEAT WALL AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM
 THE SEAT WALL.
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A
 FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS
 REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH
 610.
  
 15. SHOW COMPLIANCE FOR ACCESSIBLE WATER FOUNTAIN. PER
 ANSI A117.1-1986 4.15
  
 16. PROVIDE STORM DRAIN SIZING CALCULATIONS. PER WPB
 AMEND TO FBC 107.2.1
  
 17. PROVIDE OVERALL WATER ISOMETRIC DRAWING.
 107.3.5.1.3(13)
  
 18. PROVIDE AN UNDERGROUND COLLECTION SANITARY
 ISOMETRIC DRAWING WITH TAGGED STACKS. 107.3.5.1.3(13)
  
 19. SHT P5.2 PROVIDE PIPING DETAIL FOR BOOSTER PUMP
 WITH LOCATION OF BLADDER TANK CALLED FOR IN NOTE G).
 PER WPB AMEND TO FBC 107.2.1
  
 20. SHT P6.1 PROVIDE AN EXPANDED ISOMETRIC SHOWING
 DIRECTION OF FLOW AND TYPE OF WATER. PER WPB AMEND TO
 FBC 107.2.1
  
 21. SHT P6.1 I COULD NOT FIND ET-1 ON SCHEDULE PLEASE
 CLARIFY.
  
 22. SHT PROVIDE SIZING CALCULATION FOR THE LINT TRAP.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:19 Rev Time 0.00
Received By dbattles Date 2019-08-26 Time 10:12 Sent To  
Notes
2019-08-27 11:20:25FL14083-R20

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-20 Time 16:45 Rev Time 0.00
Received By dbattles Date 2019-06-20 Time 16:45 Sent To  
Notes
2019-06-21 11:20:54BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19030147
 REVIEWED: JUNE 21, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
  
 1) 107.3.4 FBC[AMENDED] THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 RULE 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  -PLEASE SELECT THE SYSTEM BE USED IN THE PRODUCT
 APPROVAL. THIS WILL PROVIDE THE MAXIMUM DESIGN
 PRESSURE.
  
 2) [RAS 117]PROVIDE ENGINEERING FOR ENHANCED MECHANICAL
 ATTACHMENT AS STATED IN PRODUCT APPROVAL NOTES #9.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 10:41 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 09:15 Sent To  
Notes
2019-05-17 10:41:34COMMENTS IN BUILDING REVIEW.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-09-23 Cont ID  
Sent By shill Date 2019-09-23 Time 08:57 Rev Time 0.00
Received By shill Date 2019-09-23 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:11 Rev Time 0.00
Received By dbattles Date 2019-08-26 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 05:22 Rev Time 0.00
Received By shill Date 2019-07-19 Time 05:15 Sent To  
Notes
2019-07-19 05:22:21SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CIVIL - DIGITAL SIGNATURE OK BUT LACKS LANGUAGE
 REQUIRED BY FAC61G15-23.004 REGARDING PRINTED COPIES.
 PLEASE ADD TO ALL SHEETS BUT ONLY RESUBMIT PAGES WHICH
 CHANGE DUE TO CODE RELATED COMMENTS
  
 DIGITAL SIGNATURES/TITLE BLOCK OK FOR FOLLOWING; NEW
 SHEETS SUBMITTED NEXT REVIEW CYCLE REQUIRE VERIFICATION
 FMEP - OK
  
2019-06-20 16:45:33OK - A SHEETS
 OK - S-SHEETS (THIRD PARTY VERIFIED)

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By dbattles Date 2019-05-14 Time 12:39 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 09:15 Sent To  
Notes
2019-05-14 12:43:06107.2.1 FBC[AMENDED] PLACE A DIGITALLY CREATED IMAGE OF
 YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL
 SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  
 S-SHEET NEED GRAPHIC REPRESENTATION OF SEAL AND
 STATEMENT.
 ALL OTHER SHEETS OK INCLUDING MEP AND F SHEETS.
  
 ALL SHEETS SUBMITTED IN FOR COMMENT RESPONSE WILL NEED
 TO BE DIGITALLY SIGNED.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
2019-04-19 12:25:301ST REVIEW: MECH SHEETS ARE GOOD.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By dbattles Date 2019-08-27 Time 11:05 Rev Time 0.00
Received By dbattles Date 2019-08-26 Time 10:12 Sent To  
Notes
2019-08-27 11:10:13PROVISO:
 RECEIVED 3 ORIGINALS ON 9/4/2019
 PLEASE PROVIDE 3 ORIGINALS OF THRESHOLD AGREEMENT.
  
 THEY CAN BE DROPPED OFF OR MAILED
 C.O. DYLAN BATTLES
 DEVELOPMENT SERVICES 1ST FLOOR
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By dbattles Date 2019-06-20 Time 16:33 Rev Time 0.00
Received By dbattles Date 2019-06-17 Time 07:50 Sent To  
Notes
2019-06-20 16:38:41ONCE THE THRESHOLD INSPECTOR IS ON BOARD PLEASE SEND
 THE THRESHOLD AGREEMENT AND RESUMES VIA E-MAIL.
 I WILL HAVE THE CHIEF BUILDING INSPECTOR REVIEW AND
 THEN I WILL REQUEST 3 ORIGINALS OF THE THRESHOLD
 AGREEMENT.
  
 WE CAN WORK ON THIS WHILE PLAN REVIEW IS STILL
 OCCURING.
 IF ALL REVIEWS ARE APPROVED THE THRESHOLD CAN BE
 PROVISO AS LONG AS WE A WORKING TOWARDS HAVING THEM
 ON-SITE PRIOR TO START OF WORK AS REQUIRED BY THE
 THRESHOLD PLAN.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By dbattles Date 2019-05-14 Time 13:02 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 10:46 Sent To  
Notes
2019-05-14 13:06:44DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 F.S. 553.79(5) THRESHOLD BUILDING.
 THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD
 BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO
 COMMENCEMENT.
  
 A. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR. IF PDF OF AGREEMENT IS NEEDED PLEASE
 CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL
 PROVIDE VIA E-MAIL.
 OK-AGREEMENT SENT TO DESIGNER BY PLANS EXAMINER DYLAN
 BATTLES ON 5/14/2019
  
 B. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL
 INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY
 PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO
 BE ON-SITE. UPON COMPLETION OF AGREEMENT PLEASE E-MAIL
 TO [email protected] WITH RESUMES FOR ALL PARTIES LISTED
 ON THE AGREEMENT. UPON REVIEW AND ACCEPTANCE BY THE
 CHIEF INSPECTOR THE CITY WILL REQUEST THREE ORIGINAL
 COPIES OF THE AGREEMENT.
  
 C. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.?
  
 THE STATEMENT ABOVE SHOULD BE ADDED TO ALL STRUCTURAL
 SHEETS. THIS CAN BE IN THE TITLE BLOCK OR OTHER
 LOCATION. SINCE THE STRUCTURAL SHEETS ALSO NEED GRAPHIC
 REPRESENTATION OF SEAL (SEE SIGNATURE REVIEW) ALL
 STRUCTURAL SHEETS SHOULD BE RE-UPLOADED.
  
 D. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
 OK-INSPECTION PLAN FOUND ON SHEET 043 S0.1-NO RESPONSE
 NEEDED FOR THRESHOLD PLAN
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-10-02 Cont ID  
Sent By eschneid Date 2019-10-02 Time 09:39 Rev Time 0.50
Received By eschneid Date 2019-10-02 Time 08:41 Sent To  
Notes
2019-10-02 09:40:25PASSED W/PROVISOS
  
 1) PROVISO: PRIOR TO FINAL INSPECTION (104) PROVIDE THE
 RECORDED RELEASE/RELOCATION FOR THE EASEMENT RECORDED
 IN ORB 5832 PB 1420.
  
 2) PROVISO: ALL ROOFTOP MECHANICAL EQUIPMENT MUST BE
 SCREENED AT FINAL INSPECTION. ONE OF THE DRAWINGS
 DEMONSTRATES THAT ROOFTOP EQUIPMENT IS VISIBLE FROM
 NORTHWOOD UNIVERSITY DRIVE; HOWEVER, THE RESPONSE
 STATES THAT THIS WILL BE SCREENED BY THE PROPOSED
 LANDSCAPE. STAFF WILL LET THE PROJECT PROCEED, BUT IF
 THE ROOFTOP EQUIPMENT IS VISIBLE WHEN THE BUILDING IS
 READY FOR FINAL INSPECTION (CERTIFICATE OF OCCUPANCY),
 ZONING STAFF WILL NOT PASS THE INSPECTION.
  
 3) PROVISO: DUE TO CHANGES TO THE APPROVED PLANS, AN AS
 BUILT MINOR PD AMENDMENT IS REQUIRED TO BE SUBMITTED TO
 THE PLANNING DIVISION PRIOR TO THE FINAL INSPECTION.
  
 4) SEPARATE PERMITS REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE
 B. GENERATOR
 C. HARDSCAPE
 D. BICYCLE RACKS
 E. LANDSCAPE
 F. PARKING LOTS, INCLUDING STRIPING.
 E. DECK
 F. PAVILION
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-09-05 Cont ID  
Sent By eschneid Date 2019-09-05 Time 14:46 Rev Time 0.75
Received By eschneid Date 2019-09-05 Time 12:01 Sent To  
Notes
2019-09-05 15:03:35FAILED
  
 1) REPEAT COMMENT: SINCE THE BUILDING IS SHOWN ON TOP
 OF THE EXISTING EASEMENT RECORDED IN ORB 5832 PB 1420,
 YOU WILL NEED TO PROVIDE THE RELEASE AND RELOCATION
 AGREEMENT FOR THE EASEMENT PRIOR TO ZONING APPROVAL OF
 THIS PERMIT.
  
 2) REPEAT COMMENT: MANY OF THE DIMENSIONS LISTED ON
 SHEET C-5 ARE NO LONGER ACCURATE. IT APPEARS THAT
 DIGITS WERE LEFT OFF - EX. 21.3 FEET BECAME 1.3 FEET.
 CORRECT ALL LABELS. - NO NEW PLAN SUBMITTED.
  
 3) UPDATED COMMENT: ALL ROOFTOP MECHANICAL EQUIPMENT
 MUST BE SCREENED AT FINAL INSPECTION. ONE OF THE
 DRAWINGS DEMONSTRATES THAT ROOFTOP EQUIPMENT IS VISIBLE
 FROM NORTHWOOD UNIVERSITY DRIVE; HOWEVER, THE RESPONSE
 STATES THAT THIS WILL BE SCREENED BY THE PROPOSED
 LANDSCAPE. STAFF WILL LET THE PROJECT PROCEED, BUT IF
 THE ROOFTOP EQUIPMENT IS VISIBLE WHEN THE BUILDING IS
 READY FOR FINAL INSPECTION (CERTIFICATE OF OCCUPANCY),
 ZONING STAFF WILL NOT PASS THE INSPECTION.
  
 4) DUE TO CHANGES TO THE APPROVED PLANS, AN AS BUILT
 MINOR PD AMENDMENT IS REQUIRED TO BE SUBMITTED TO THE
 PLANNING DIVISION PRIOR TO THE FINAL INSPECTION.
  
 5) SEPARATE PERMITS REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE
 B. GENERATOR
 C. HARDSCAPE
 D. BICYCLE RACKS
 E. LANDSCAPE
 F. PARKING LOTS, INCLUDING STRIPING.
 E. DECK
 F. PAVILION
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By eschneid Date 2019-07-18 Time 17:13 Rev Time 2.00
Received By eschneid Date 2019-07-18 Time 09:56 Sent To  
Notes
2019-07-18 17:15:44FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE ELECTRICAL AND TRASH ROOMS HAVE BEEN FLIPPED
 FROM THE CITY COMMISSION APPROVAL, SO THE ELEVATIONS
 HAVE CHANGED. ADDITIONALLY, THE FINAL ELEVATIONS SHOW
 LOUVERS AND CANOPIES THAT WERE NOT INCLUDED ON THE
 ORIGINAL APPROVAL. AN AS BUILT MINOR PD AMENDMENT IS
 REQUIRED TO BE SUBMITTED TO THE PLANNING DIVISION PRIOR
 TO THE FINAL INSPECTION.
  
 2) THE ROOF PLANS SHOW MOUNTING CURBS FOR ROOFTOP
 EQUIPMENT.
  
 A. THE APPROVED PLANS DID NOT INCLUDE ANY ROOFTOP
 MECHANICAL EQUIPMENT. THE MECHANICAL EQUIPMENT, TO
 INCLUDE THE CHILLERS, WATER STORAGE TANKS AND THE
 GENERATOR WERE SHOWN THROUGH THE APPROVAL PROCESS IN
 THE SCREENED EQUIPMENT YARD ENCLOSURE AT GROUND LEVEL.
  
 B. EXPLAIN WHAT EQUIPMENT IS PROPOSED TO BE MOUNTED ON
 THE ROOF? THE MECHANICAL ROOF PLAN SHOWS OAR1, EAR2 AND
 EAR2 EQUIPMENT ON THE ROOF. ZONING STAFF WAS UNABLE TO
 LOCATED THE DETAILS FOR THESE FEATURES.
  
 C. PROVIDE INFORMATION THAT THE PROPOSED BUILDING
 PARAPETS ARE OF SUFFICIENT HEIGHT TO SCREEN THE ROOFTOP
 MECHANICAL EQUIPMENT, TO INCLUDE THE TRASH CHUTE VENT.
  
 3) PRIOR TO ZONING APPROVAL OF THIS PERMIT, A TREE
 ALTERATION PERMIT MUST BE SUBMITTED TO THE PLANNING
 DIVISION AND APPROVED BY THE CITY'S LANDSCAPE PLANNER
 FOR THE DEVELOPMENT AREA.
  
 4) SHEET C-5 SITE LAYOUT SHOWS A NEW 10 FOOT FPL
 EASEMENT AND LINE AND A RELOCATED EXISTING 12 FOOT
 UTILITY EASEMENT COMPARED TO THE APPROVED PLANS (NOTE:
 THE SURVEY PROVIDED WITH THE APPROVAL PROCESS SHOWS A
 10 FOOT SOUTHERN BELL EASEMENT AT THIS LOCATION). THE
 PROPOSED FPL EASEMENT AND LINE DIRECTLY INTERFERE WITH
 THE LOCATION OF TREE LOCATIONS ON THE CITY COMMISSION
 APPROVED PLANS. ALL UTILITIES MUST USE THE EXISTING
 EASEMENT, SUBJECT TO ADJUSTMENT TO AVOID THE PROPOSED
 BUILDING, AND AVOID THE APPROVED TREES. THERE IS NO
 JUSTIFICATION FOR 22 FEET OF UTILITY EASEMENT.
  
 5) SINCE THE BUILDING IS SHOWN ON TOP OF THE EXISTING
 EASEMENT RECORDED IN ORB 5832 PB 1420, YOU WILL NEED TO
 PROVIDE THE RELEASE AND RELOCATION AGREEMENT FOR THE
 EASEMENT PRIOR TO ZONING APPROVAL OF THIS PERMIT.
  
 NOTE: THE EXISTING CONDITIONS PLAN DOES NOT SHOW
 ANYTHING IN THE RECORDED EASEMENT.
  
 6) MANY OF THE DIMENSIONS LISTED ON SHEET C-5 ARE NO
 LONGER ACCURATE. IT APPEARS THAT DIGITS WERE LEFT OFF ?
 EX. 21.3 FEET BECAME 1.3 FEET. CORRECT ALL LABELS.
  
 7) SEPARATE PERMITS REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE
 B. GENERATOR
 C. HARDSCAPE
 D. BICYCLE RACKS
 E. LANDSCAPE
 F. PARKING LOTS, INCLUDING STRIPING.
 E. DECK
 F. PAVILION
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By eschneid Date 2019-04-08 Time 13:45 Rev Time 0.25
Received By eschneid Date 2019-04-08 Time 13:45 Sent To  
Notes
2019-04-08 13:50:03FAILED
  
 THIS BUILDING REQUIRES APPROVAL BY THE CITY COMMISSION
 AFTER A PUBLIC HEARING, WHICH BEST CASE WILL NOT HAPPEN
 UNTIL JUNE 3, 2019. ZONING WILL NOT REVIEW THE PERMIT
 UNTIL AFTER THIS DATE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]