Plan Review Details - Permit 19030096
Plan Review Stops For Permit 19030096
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-12 Cont ID  
Sent By thunt Date 2019-03-12 Time 08:36 Rev Time 0.00
Received By shill Date 2019-03-12 Time 06:17 Sent To  
Notes
2019-03-12 06:18:24PROVISO - NO SOUNDPROOFING PROPOSED, LOCATED ON FIRST
 FLOOR
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 15:53 Rev Time 0.00
Received By shill Date 2019-03-11 Time 15:53 Sent To  
Notes
2019-03-11 15:53:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 06:25 Rev Time 0.00
Received By thunt Date 2019-03-14 Time 14:17 Sent To  
Notes
2019-03-14 14:17:47ROUTED DENIED PLAN & FHA LETTER TO T.HUNT DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-12 Cont ID  
Sent By thunt Date 2019-03-12 Time 08:36 Rev Time 0.00
Received By thunt Date 2019-03-04 Time 15:43 Sent To B
Notes
2019-03-11 15:54:093/11 TO PLUMBING BIN
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 06:24 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 06:04 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By thunt Date 2019-03-12 Time 08:15 Rev Time 0.00
Received By thunt Date 2019-03-12 Time 08:15 Sent To I
Notes
2019-03-12 08:36:41PLUMBING 1ST REVIEW**DENIED**
  
 BUILDINGS CONSTRUCTED AFTER MARCH 13, 1991 MUST COMPLY
 WITH FAIR HOUSING ACT (FHA). THIS BUILDING WAS
 CONSTRUCTED IN 2001. YOU MAY WANT TO CONSULT A DESIGN
 PROFESSIOAL WHO IS FAMILIAR WITH THE REQUIREMENTS OF
 FAIR HOUSING.
  
 1) PROVIDE FLOOR PLAN SHOWING WHAT FHA DESIGN
 SPECIFICATION EACH BATHROOM IS. FBC 107.2.1
  
 2) YOU SCOPE OF WORK DRAWING IS BACKWARDS AND DOES NOT
 MATCH THE EXISTING FLOOR PLAN ORIENTATION. FBC 107.1
  
 3) PROVIDE DETAIL MEARSUREMENTS SHOWING NEW DOUBLE
 SINKS WILL COMPLY WITH FHA 7.48 AND MAX CABINET HEIGHT
 WILL BE 34" FHA 7.52
  
 4) PROVIDE PLAN SHOWING ALL REQUIRED CLEAR FLOR SPACES
 AND APPROCH AS REQUIRED IN FHA CHAPTER 7B
  
 5) YOUR PLAN SHOW THE SHOWER @ 42" WHICH IS 6" WIDER
 THEN THE EXISTING TUB. TOILETS ARE REQUIRED TO BE A
 18"MIN FROM THE GRAB BAR SIDE AND 15" ON THE SINK SIDE
 OVERALL MIN 33". FHA 7.43
  
 6) SHOWERS ARE NOT PERMITTED TO BE ADJACENT TO A TOILET
 IN A FHA BATHROOM. FHA 7.44
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 561-248-2703
  
 SAMANTHA HILL
 CHIEF PLAN EXAMINER
 561-805-6724