Plan Review Details - Permit 19030087
Plan Review Stops For Permit 19030087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-08 Cont ID  
Sent By cthroop Date 2019-04-08 Time 10:50 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 10:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 09:44 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 09:09 Sent To  
Notes
2019-03-06 09:49:34BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IN ADDITION TO THE STANDARD TIE-DOWN DETAIL, FLAME
 SPREAD REPORT AND SITE PLAN REQUIRED FOR ALL TEMORARY
 MEMBRANE STRUCTURES, THE FOLLOWING REQUIREMENTS ARE
 REQUIRED FOR ANY STRUCTURE WITH A SPAN OF 30 FEET OR
 MORE.
  
 **ADDITIONAL REQUIREMENTS
 FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
  
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By scaldero Date 2019-04-10 Time 12:09 Rev Time 0.00
Received By scaldero Date 2019-04-10 Time 12:04 Sent To  
Notes
2019-04-10 12:09:15PERMIT #19030087
 FIRE REVIEW COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 4) IF APPLICABLE, GENERATORS AND OTHER INTERNAL
 COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS
 BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM
 CONTACT BY FENCING OR ENCLOSURE.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By scaldero Date 2019-03-06 Time 10:35 Rev Time 0.00
Received By scaldero Date 2019-03-06 Time 10:29 Sent To  
Notes
2019-03-06 10:35:04PERMIT #19030087
 FIRE REVIEW COMMENTS:
  
 1) APPLICATION STATES THAT TENTS ARE OF "VARIOUS
 SIZES". THE TENT DIAGRAM PROVIDED STATES 10' X 20'. THE
 SITE PLAN SHOWS WHAT MAY BE 40 OR MORE TENTS VARYING IN
 SIZE. PLEASE SPECIFY THE SIZES AND LOCATIONS OF EACH
 TENT.
  
 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) IF APPLICABLE, GENERATORS AND OTHER INTERNAL
 COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS
 BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM
 CONTACT BY FENCING OR ENCLOSURE.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 06:54 Rev Time 0.00
Received By shill Date 2019-03-05 Time 08:33 Sent To  
Notes
***NONE***