Plan Review Details - Permit 19030087
| Plan Review Stops For Permit 19030087 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-04-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-04-08 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-08 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-03-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-03-06 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-03-06 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2019-03-06 09:49:34 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. IN ADDITION TO THE STANDARD TIE-DOWN DETAIL, FLAME | | | SPREAD REPORT AND SITE PLAN REQUIRED FOR ALL TEMORARY | | | MEMBRANE STRUCTURES, THE FOLLOWING REQUIREMENTS ARE | | | REQUIRED FOR ANY STRUCTURE WITH A SPAN OF 30 FEET OR | | | MORE. | | | | | | **ADDITIONAL REQUIREMENTS | | | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN | | | OF 30 FEET OR GREATER IN ANY DIRECTION: | | | | | | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE | | | BASEPLATE/TIEDOWN DETAILS. | | | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. | | | | | | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY | | | A DESIGN PROFESSIONAL. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-04-10 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-04-10 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-04-10 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2019-04-10 12:09:15 | PERMIT #19030087 | | | FIRE REVIEW COMMENTS: | | | | | | 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 4) IF APPLICABLE, GENERATORS AND OTHER INTERNAL | | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | | CONTACT BY FENCING OR ENCLOSURE. | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-03-06 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-03-06 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-03-06 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2019-03-06 10:35:04 | PERMIT #19030087 | | | FIRE REVIEW COMMENTS: | | | | | | 1) APPLICATION STATES THAT TENTS ARE OF "VARIOUS | | | SIZES". THE TENT DIAGRAM PROVIDED STATES 10' X 20'. THE | | | SITE PLAN SHOWS WHAT MAY BE 40 OR MORE TENTS VARYING IN | | | SIZE. PLEASE SPECIFY THE SIZES AND LOCATIONS OF EACH | | | TENT. | | | | | | 2) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 5) IF APPLICABLE, GENERATORS AND OTHER INTERNAL | | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | | CONTACT BY FENCING OR ENCLOSURE. | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-04-08 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-11 |
Time |
06:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-05 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
|