Plan Review Details - Permit 19030079
Plan Review Stops For Permit 19030079
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 09:07 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 09:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-06 Cont ID  
Sent By scaldero Date 2019-03-06 Time 10:28 Rev Time 0.00
Received By scaldero Date 2019-03-06 Time 10:20 Sent To  
Notes
2019-03-06 10:27:58PERMIT #19030079
 FIRE REVIEW COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 4) IF APPLICABLE, GENERATORS AND OTHER INTERNAL
 COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS
 BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM
 CONTACT BY FENCING OR ENCLOSURE.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-08 Cont ID  
Sent By sholder Date 2019-03-08 Time 07:32 Rev Time 0.00
Received By sholder Date 2019-03-08 Time 07:32 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved