Plan Review Details - Permit 19030018
Plan Review Stops For Permit 19030018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-23 Cont ID  
Sent By pvalenti Date 2019-04-23 Time 10:26 Rev Time 0.00
Received By pvalenti Date 2019-04-23 Time 10:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By pvalenti Date 2019-04-22 Time 10:02 Rev Time 0.00
Received By pvalenti Date 2019-04-22 Time 07:47 Sent To  
Notes
2019-04-22 10:24:18***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW DENIED:
  
 1. OK
  
 2. A. OK
 2. B. OK
 2. C. FAIL (PLEASE PROVIDE THE FLAME SPREAD TEST
 SPECIFICATIONS WITH RESULTS FOR THE FLOORING
 UNDERLAYMENT).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By jwitmer Date 2019-03-13 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2019-03-12 Time 14:07 Sent To  
Notes
2019-03-13 09:46:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030018
 ADD: 550 OKEECHOBEE BLVD. SUITE: MPH22
 CONT: T-SQUARE CONSTRUCTION & SERVICES
 TEL: 561-482-4052
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 13, 2019
 ACTION: DENIED
 1) SHEET A-2:
 1A) SHEET A-2 DOES INDICATE THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-EXISTING BUILDING CODE LEVEL II
 ALTERATION. UNDER THE SECTION 806.1 FOR LEVEL II
 ALTERATIONS THE CODE TAKES YOU TO THE PROVISIONS OF THE
 2017 FBC-ACCESSIBILITY CODE, THE SECOND OR BACK HALF OF
 THE BOOK CONTAINS THE FAIR HOUSING GUIDELINE. THIS
 HIGHRISE WAS BUILT AFTER THE FAIR HOUSING GUIDELINES
 WENT IN AFFECT. THEY WENT INTO EFFECT MARCH 13, 1991.
 ALL HABITAL FLOORS HAVE ACCESS BY ELEVATORS AND ALL
 UNITS HAVE TO COMPLY WITH THE FAIR HOUSING ACT. NEITHER
 OF THE BATHROOMS SHOWN INDICATE IF THEY WERE DESIGNED
 TO SPECIFICATION A OR SPECIFICATION B.
 1B) THE PLANS DO INDICATE THE TWO BATHROOMS ARE TO BE
 REMODELED. THE GUIDELINE UNDER REQUIREMENT 7 GIVES
 DESIGN CHOICES:
 1) ALL BATHROOMS COMPLY WITH SPECIFICATION A
 OR
 2) ONE BATHROOM COMPLIES WITH SPECIFICATION B AND ALL
 OTHER BATHROOM(S) NOT REQUIRED TO MEET
 MANEUVERING AND CLEAR FLOOR SPACE REQUIREMENTS. TAKEN
 FROM THE TECHNICAL OVERVIEW/PARTICIPANT
 MANUAL.
 1C) SPECIFICATION A OR B CLEAR FLOOR SPACE- SHOWERS.
 SHOWER STALLS MAYBE OF ANY SIZE OR CONFIGURATION EXCEPT
 WHEN:
 1) THE SHOWER STALL IS THE ONLY BATHING FIXTURE IN THE
 DWELLING; OR
 2) WHEN THE SHOWER STALL IS DESIGNED THE ACCESSIBLE
 BATHING FIXTURE IN A SPECIFICATION B BATHROOM.
 IN BOTH OF THESE EXCEPTIONS, THE GUIDELINE SPECIFY THAT
 THE SHOWER STALL SHALL BE A MINIMUM OF 36
 INCHES X 36 INCHES.
 IT MUST HAVE A 30 X 48 INCH CLEAR FLOOR SPACE PARALLEL
 TO THE STALL AND FLUSH WITH THE CONTROL WALL. THE
 SHOWER WALL OPPOSITE THE CONTROLS MUST BE REINFORCED TO
 ALLOW FOR THE INSTALLATION OF A WALL-HUNG SEAT.
  
 2) SHEET A-2 INDICATES THE REMOVAL OF FLOOR FINISHES
 NEW FINISHES PER THE OWNERS SELECTION, PLEASE SHOW
 COMPLIANCE WITH:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL (LVT) OR (LVP) AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-21 Cont ID  
Sent By jpearson Date 2019-03-21 Time 09:55 Rev Time 0.00
Received By jpearson Date 2019-03-21 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-28 Cont ID  
Sent By pleduc Date 2019-03-28 Time   Rev Time 0.00
Received By pleduc Date 2019-03-28 Time 13:44 Sent To  
Notes
2019-03-28 13:54:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK INVOLVING THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS.
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-22 Cont ID  
Sent By pvalenti Date 2019-04-22 Time 10:25 Rev Time 0.00
Received By pvalenti Date 2019-03-26 Time 15:43 Sent To  
Notes
2019-03-27 15:43:35B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-21 Time 06:56 Rev Time 0.00
Received By shill Date 2019-03-01 Time 12:58 Sent To  
Notes
2019-03-04 13:04:31B09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-11 Cont ID  
Sent By ccole Date 2019-04-11 Time 16:00 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By jesmith Date 2019-04-09 Time 10:06 Rev Time 0.00
Received By jesmith Date 2019-04-09 Time 10:06 Sent To  
Notes
2019-04-09 10:06:31APPROVED
 PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. SHOWER COMPARTMENTS REQUIRE NEW SHOWER LINERS TO
 COMPLY WITH FBC PL SECTION 417. SEE RED LINED NOTES ON
 PLAN SHEET A-2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-21 Cont ID  
Sent By jesmith Date 2019-03-21 Time 15:45 Rev Time 0.00
Received By jesmith Date 2019-03-21 Time 14:31 Sent To  
Notes
2019-03-21 15:45:49FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. FALLS UNDER THE RULES OF THE FAIR HOUSING ACT.
 INDICATE ON THE FLOOR PLAN, COMPLIANCE WITH THE FAIR
 HOUSING ACT, INDICATING TYPE OF BATHROOM(S), (TYPE A,
 TYPE B), IN ACCORDANCE WITH GUIDELINES UNDER
 REQUIREMENT 7, INCLUDING CLEAR FLOOR SPACE AND
 MANEUVERING.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715